Plan Review Details - Permit 19100398
Plan Review Stops For Permit 19100398
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-02 Cont ID  
Sent By rmcdouga Date 2019-12-02 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2019-12-02 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-11-14 Cont ID  
Sent By rmcdouga Date 2019-11-14 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2019-11-14 Time 14:24 Sent To  
Notes
2019-11-14 14:59:36PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ARCHITECT'S DIGITAL SIGNATURES ON THE
 ARCHITECTURAL SHEETS COULD NOT BE VEIFIED. THERE
 APPEARS TO BE AN ERROR IN THE UPLOADING OF THE
 DIGITALLY SIGNED ARCHITECTURAL SHEETS. FAC 61G1-16.003
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By rmcdouga Date 2019-10-16 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2019-10-16 Time 15:35 Sent To  
Notes
2019-10-16 15:56:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE COVERSHEET A-000 WAS NOT DIGITALLY SIGNED BY THE
 ARCHITECT. FAC 61G1-16.003
  
 2) THE DEMOLITION PLAN A-100 IS LISTED IN THE PLAN
 INDEX BUT IS MISSING FROM THE SUBMITTAL. FBC 107.2.1
  
 3) ELEVATION #7 ON A-250 HAS A DIMENSION FOR THE
 BREAK-ROOM SINK AS 3'-0". FBC ACCESSIBILITY SECTION
 606.3 REQUIRES THE HIGHER OF THE SINK RIM OR COUNTER
 TOP TO BE A MAXIMUM OF 34".
  
 4) FBC ACCESSIBILITY SECTION 904.4.1 FOR A PARALLEL
 APPROACH REQUIRES A PORTION OF THE SERVICE COUNTER AT
 THE RECEPTION DESK TO BE A MINIMUM OF 36" IN LENGTH.
 DETAIL 15 ON A-250 SPECIFIES 34.5".
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 09:07 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 09:07 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-17 Cont ID  
Sent By jpearson Date 2019-10-17 Time 08:27 Rev Time 0.00
Received By jpearson Date 2019-10-17 Time 08:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-11-27 Cont ID  
Sent By pleduc Date 2019-11-27 Time   Rev Time 0.00
Received By pleduc Date 2019-11-27 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-20 Cont ID  
Sent By sathomas Date 2019-11-20 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-11-20 Time 00:00 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-18 Cont ID  
Sent By sathomas Date 2019-10-18 Time 13:05 Rev Time 0.00
Received By sathomas Date 2019-10-18 Time 00:00 Sent To I
Notes
2019-10-18 13:04:541. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
 2. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
 3. ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 5. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 S.THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-05 Cont ID  
Sent By lmarchan Date 2019-12-05 Time 07:48 Rev Time 0.00
Received By lmarchan Date 2019-11-21 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-21 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-12 Time 10:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-22 Cont ID  
Sent By lmarchan Date 2019-10-22 Time 12:50 Rev Time 0.00
Received By lmarchan Date 2019-10-09 Time 11:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-12-03 Cont ID  
Sent By lmarchan Date 2019-12-03 Time 10:31 Rev Time 0.00
Received By lmarchan Date 2019-11-21 Time 11:41 Sent To  
Notes
2019-12-03 10:31:59NO FEES DUE - NO RECEIPT CREATED
2019-11-21 11:42:0611/21/19 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By rmcdouga Date 2019-10-16 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2019-10-16 Time 15:37 Sent To  
Notes
2019-10-16 15:38:55PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By ccole Date 2019-11-18 Time 12:22 Rev Time 0.00
Received By ccole Date 2019-11-18 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-15 Cont ID  
Sent By ccole Date 2019-10-15 Time 10:26 Rev Time 0.00
Received By ccole Date 2019-10-11 Time 15:36 Sent To  
Notes
2019-10-15 10:47:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100398
 10/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-300: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE FLEX INJECTION, COOL SCULPTING,
 AND LHR ROOMS- TABLE 403.3.1.1 FBC M.
  
 2) M-300: PROVIDE THE SEQUENCES OF OPERATION FOR THE
 EXHAUST FANS (EF-1-6)- SECTION 501.4 FBC M.
  
 3) SHEETS M103, M300: PLEASE INCLUDE EF-5 IN THE FAN
 SCHEDULE- SECTION 107.2.1 FBC M.
  
 4) S2: PROVIDE THE WIND DESIGN CRITERIA USED TO
 DETERMINE THE ROOFTOP MECHANICAL EQUIPMENT ENGINEERING-
 SECTION 301.15 FBC M, AND SECTION 1609 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By gjohnson Date 2019-11-18 Time 14:29 Rev Time 0.00
Received By gjohnson Date 2019-11-18 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By gjohnson Date 2019-10-17 Time 16:57 Rev Time 0.00
Received By gjohnson Date 2019-10-11 Time 15:16 Sent To  
Notes
2019-10-17 16:58:061ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.SHT. A-250 THE GRAB BARS SHALL BE MEASURED FROM
 FINISHED FLOOR TO THE TOP OF THE GRIPPING SURFACE NOT
 TO THE CENTER OF THE BAR AS SHOWN ON PLAN. PER FBC ACC
 609.4
  
 2. PLEASE LABEL CLEAR FLOOR FOR THE TOILET LAVATORY AND
 WATER FOUNTAIN. PER FBC PL 604.3.1, 606.2, 602.2
  
 3. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. PER
 FBC PL 604.4
  
 4. THE BREAK ROOM SINK AND AT LEAST ONE OF THE
 PROCEDURE ROOM SINKS SHALL COMPLY WITH FBC ACC 212.2,
 212.3, 606.2, 606.3, 804.4
  
 5. SHT. P-000 NOTE #29 HOT WATER PIPING SHALL COMPLY
 WITH FBC ENERGY 2017 6TH EDITION
  
 6. SHT. P-102 PLACE NOTE ON PLAN THE SANITARY VENT
 SHALL A MIN OF 10' AWAY OF ANY AIR INTAKES OR OPENINGS.
 PER FBC PL 903.5
  
 7. THE PLUMING SCHEDULE LIST FLOOR MOUNTED TOILETS AND
 THE SANITARY ISOMETRIC SHOWS WALL MOUNTED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-500 P-501, P-000 REMOVE ALL REFERENCES TO
 DIVISION 22 THE GOVERNING CODE SHALL BE LISTED ON THE
 PLAN AS FLORIDA BUILDING CODE PLUMBING 2017 6TH
 EDITION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-12-02 Cont ID  
Sent By rmcdouga Date 2019-12-02 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2019-12-02 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-11-14 Cont ID  
Sent By rmcdouga Date 2019-11-14 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2019-11-14 Time 15:00 Sent To  
Notes
2019-11-14 15:01:29ARITECTURAL SHEETS DIGITAL SIGNATURES CAN NOT BE
 VALIDATED. SIGNATURES ON STRUCTURAL PLAN SHEETS ARE
 GOOD.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-16 Cont ID  
Sent By rmcdouga Date 2019-10-16 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2019-10-16 Time 15:34 Sent To  
Notes
2019-10-16 15:34:54THE COVER SHEET A-000 IS NOT DIGITALLY SIGNED AND
 SEALED BY THE ARCHITECT.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By eschneid Date 2019-12-04 Time 17:51 Rev Time 0.50
Received By eschneid Date 2019-12-04 Time 17:36 Sent To  
Notes
2019-12-04 17:37:34PASSED WITH PROVISO
  
 IN THE EVENT THAT NEW EQUIPMENT IS VISIBLE, THE
 EQUIPMENT NEEDS TO BE PAINTED WITH A SKY PATTERN PRIOR
 TO THE FINAL INSPECTION (104) APPROVAL.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By eschneid Date 2019-11-18 Time 12:04 Rev Time 0.50
Received By eschneid Date 2019-11-18 Time 10:34 Sent To  
Notes
2019-11-18 11:35:24PASSED WITH PROVISO
  
 IN THE EVENT THAT NEW EQUIPMENT IS VISIBLE, THE
 EQUIPMENT NEEDS TO BE PAINTED WITH A SKY PATTERN PRIOR
 TO THE FINAL INSPECTION (104) APPROVAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By eschneid Date 2019-10-22 Time 10:37 Rev Time 1.00
Received By eschneid Date 2019-10-22 Time 09:13 Sent To  
Notes
2019-10-22 10:37:47FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE PLANS EITHER NEED TO CONTAIN THE PALM BEACH
 OUTLETS MANAGEMENT APPROVAL STAMP. ALTERNATIVELY YOU
 MAY SUBMIT A SEPARATE LETTER FROM THE PBO MANAGEMENT
 LISTING THE SPECIFIC PLANS THAT THEY APPROVE.
  
 2) THE ROOF PLAN SHOWS A NEW ROOFTOP UNIT ON A CURB,
 NEW MINI SPLIT CONDENSING UNIT ON AND EXISTING
 EQUIPMENT STAND AND AN NEW MECHANICAL HOOD. PROVIDE
 SITE LINE DRAWINGS SO THAT STAFF CAN VERIFY THAT THESE
 NEW ITEMS COMPLY WITH THE PALM BEACH OUTLETS SCREENING
 REQUIREMENTS.
  
 3) PLEASE DESCRIBE WHAT YOU WILL OCCUR IN THE DISPLAY
 AREA (ROOM 114).
  
 4) PLEASE ELABORATE ON THE WINDOW FILM WC-2. WILL THIS
 INCLUDE ADVERTISING OR GRAPHICS? PLEASE NOTE THAT YOU
 MAY ONLY COVER A MAXIMUM OF 10% OF THE GLAZED AREA WITH
 THE FILM. WHILE IT APPEARS THAT LESS THAN 10% IS
 COVERED, PLEASE PROVIDE CALCULATIONS TO VERIFY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  