Plan Review Details - Permit 19100397
Plan Review Stops For Permit 19100397
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 13:39 Rev Time 0.00
Received By shill Date 2019-10-11 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-05 Cont ID  
Sent By jpearson Date 2019-11-05 Time 14:14 Rev Time 0.00
Received By jpearson Date 2019-11-05 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-11 Cont ID  
Sent By jpearson Date 2019-10-11 Time 13:46 Rev Time 0.00
Received By jpearson Date 2019-10-11 Time 13:46 Sent To  
Notes
2019-10-11 13:46:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-17 Cont ID  
Sent By sathomas Date 2019-10-17 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-10-17 Time 00:00 Sent To M
Notes
2019-10-17 13:51:07PROVISO:
  
 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2. PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3. PER NFPA 241 SECTION 8.6.2 TEMPORARY SEPARATION
 WALLS: PROTECTION SHALL BE PROVIDED TO SEPARATE AN
 OCCUPIED PORTION OF THE STRUCTURE FROM A PORTION OF THE
 STRUCTURE UNDERGOING ALTERATION, CONSTRUCTION, OR
 DEMOLITION OPERATIONS WHEN SUCH OPERATIONS ARE
 CONSIDERED AS HAVING A HIGHER LEVEL OF HAZARD THAN THE
 OCCUPIED PORTION OF THE BUILDING. WALLS SHALL HAVE AT
 LEAST A 1-HOUR FIRE RESISTANCE RATING. OPENING
 PROTECTIVES SHALL HAVE AT LEAST A 45-MINUTE FIRE
 PROTECTION RATING. NONRATED WALLS AND OPENING
 PROTECTIVES SHALL BE PERMITTED WHEN AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED.
  
 4. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-22 Cont ID  
Sent By shill Date 2019-10-22 Time 16:51 Rev Time 0.00
Received By shill Date 2019-10-09 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-10-10 Cont ID  
Sent By ccole Date 2019-10-10 Time 12:26 Rev Time 0.00
Received By ccole Date 2019-10-10 Time 10:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-10-11 Cont ID  
Sent By gjohnson Date 2019-10-11 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2019-10-11 Time 13:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 13:38 Rev Time 0.00
Received By shill Date 2019-10-11 Time 13:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-22 Cont ID  
Sent By eschneid Date 2019-10-22 Time 13:52 Rev Time 0.25
Received By eschneid Date 2019-10-22 Time 13:52 Sent To  
Notes
***NONE***