Plan Review Details - Permit 19100324
| Plan Review Stops For Permit 19100324 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2019-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-10-22 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-22 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-10-11 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-11 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2019-10-11 13:33:53 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-10-11 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-11 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-10-15 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-10-15 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-10-15 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2019-10-15 06:51:55 | PERMIT APPLICATION RECEIVED BY EMAIL, ORIGINAL MUST BE | | | SUBMITTED AT PERMIT PICK UP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-10-11 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-10-11 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2019-10-11 13:45:56 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | (S) | | | | | | 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | | APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL. | | | PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO | | | [email protected] AND CC [email protected] AND | | | [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL | | | IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN | | | REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE | | | SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-10-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-10-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-10-10 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2019-10-10 15:28:47 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS | | | AND SHOP DRAWINGS. | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-10-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-10-08 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-10-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-10-10 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-10-10 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-10-11 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-11 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
|