Plan Review Details - Permit 19100236
Plan Review Stops For Permit 19100236
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-17 Cont ID  
Sent By cthroop Date 2019-12-17 Time 14:27 Rev Time 0.00
Received By cthroop Date 2019-12-17 Time 06:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 13:22 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 09:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-30 Cont ID  
Sent By cthroop Date 2019-10-30 Time 15:29 Rev Time 0.00
Received By cthroop Date 2019-10-30 Time 13:45 Sent To  
Notes
2019-10-30 15:40:06PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVAL FOR EXTERIOR MOUNT SLIDING
 DOOR TRACK.
 2. PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED BY
 DESIGNER.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 3. ROOFING PERMIT REQUIRED.
 PERMITS
 105.1 REQUIRED.
  
 4. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 5. PROVIDE ROUGH OPENING AND DESIGN PRESSURE OF EACH
 OPENING TO RECIEVE NEW WINDOWS AND DOORS. YOU MAY
 GENERATE A WINDOW AND DOOR SCHEDULE OR PLACE THE R.O. &
 D.P. NEXT TO EACH OPENING ON THE ELEVATION PAGE.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-21 Cont ID  
Sent By jleahy Date 2020-01-21 Time 16:06 Rev Time 0.00
Received By jleahy Date 2020-01-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 08:27 Rev Time 0.00
Received By jleahy Date 2019-11-18 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-29 Cont ID  
Sent By jleahy Date 2019-10-29 Time 12:15 Rev Time 0.00
Received By jleahy Date 2019-10-29 Time 12:04 Sent To  
Notes
2019-10-29 12:17:29FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED RISER DIAGRAM SHOW WHERE SERVICE IS LOCATED
  
 NEED SMOKE ALARMS PER R314 OF THE FBC RESIDENTIAL

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-01-17 Cont ID  
Sent By jesmith Date 2020-01-17 Time 13:16 Rev Time 0.00
Received By jesmith Date 2020-01-17 Time 13:16 Sent To  
Notes
2020-01-17 13:16:25A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF WORK TO BE PERFOMED PER WPB FBC 107.2.1.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By fmittner Date 2019-11-25 Time 16:36 Rev Time 0.00
Received By fmittner Date 2019-11-25 Time 16:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-10-29 Cont ID  
Sent By fmittner Date 2019-10-29 Time 08:31 Rev Time 0.00
Received By fmittner Date 2019-10-29 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2020-02-10 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-05 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-01-22 Cont ID  
Sent By jleahy Date 2020-01-22 Time 07:31 Rev Time 0.00
Received By jleahy Date 2020-01-14 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-12-17 Cont ID  
Sent By cthroop Date 2019-12-17 Time 14:27 Rev Time 0.00
Received By cthroop Date 2019-12-11 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-27 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-15 Time 12:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-30 Cont ID  
Sent By cthroop Date 2019-10-30 Time 15:40 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 13:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-01-30 Cont ID  
Sent By lmarchan Date 2020-01-30 Time 07:49 Rev Time 0.00
Received By lmarchan Date 2020-01-16 Time 08:48 Sent To  
Notes
2020-01-29 09:53:13RECEIPT 2020-0129-77 - $3,415.63 - PAID
2020-01-16 08:49:091/16/20 SENT TO IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-30 Cont ID  
Sent By shill Date 2019-10-30 Time 06:11 Rev Time 0.00
Received By shill Date 2019-10-30 Time 06:11 Sent To  
Notes
2019-10-30 06:12:11PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2020-02-10 Cont ID  
Sent By ccole Date 2020-02-10 Time 12:04 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2020-01-17 Cont ID  
Sent By ccole Date 2020-01-17 Time 15:07 Rev Time 0.00
Received By ccole Date 2020-01-17 Time 13:14 Sent To  
Notes
2020-01-17 15:46:185TH REVIEW FBC-2017 MECHANICAL
 PERMIT #19100236
 12/4/2019
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE PROVIDE AN AHRI CERTIFICATE FOR
 THE NEW TRANE/MITSUBISHI SPLIT SYSTEM TO VERIFY IT IS A
 MATCHING SYSTEM- SECTION R501.7 FBC EC.
  
 2) M-1: THE AC SCHEDULE INDICATES THE AIR HANDLER WILL
 PRODUCE 388 CFMS OF AIR, HOWEVER THE PLAN INDICATES AIR
 DISTRIBUTION OF 514 CFMS, PLEASE CORRECT- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-12-17 Cont ID  
Sent By cthroop Date 2019-12-17 Time 14:27 Rev Time 0.00
Received By cthroop Date 2019-12-17 Time 06:48 Sent To  
Notes
2019-12-17 15:55:26PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING
 MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH,
 AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE
 INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN
 INDICATES 577 CFMS- SECTION 107.2.1 WPB.
 (PROPOSED EQUIPMENT ON PLAN IS A MITSUBISHI MODEL
 SUK-KA18NA MINI-SPLIT SYSTEM. PLAN SHOWS A DUCTED
 SYSTEM. PROVIDE EQUIPMENT THAT COMPLIES WITH THE
 DESIGN. MANUAL J SHALL LIST MAKE AND MODEL OF HEATING
 AND COOLING EQUIPMENT. BTUH AND CFM CAPACITY OF
 EQUIPMENT ON PLAN EXCEEDS SIZING LIMITATIONSOF DESIGN
 PER RE 403.7.1.1).
  
 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR
 THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION
 M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR
 MAKEUP AIR. - CORRECTED
  
 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING
 UNITS IN ATTICS: - CORRECTED
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET: (405 SUBMITTED)
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS. (TO BE FEILD
 VERIFIED)
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY. (SEE DETAIL ON MECH. PLAN)
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER. (TO BE FEILD VERIFIED)
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD: (TO BE FEILD VERIFIED)
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES. - (NOT ADDRESSED)
 (M1411.8 LOCKING ACCESS PORT CAPS)
  
 NEW COMMENT
  
 5) E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-12-04 Cont ID  
Sent By ccole Date 2019-12-04 Time 07:45 Rev Time 0.00
Received By ccole Date 2019-12-04 Time 07:25 Sent To  
Notes
2019-12-04 07:55:333RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19100236
 12/4/2019
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE ARCHITECT OF RECORD HAS NOT RESPONDED TO THE 1ST
 REVIEW COMMENTS. HE HAS STATED IN HIS RESPONSE
 NARRATIVE THAT RESPONSES ARE TO BE PROVIDED BY AC
 SUB-CONTRACT. PLEASE NOTE THAT ALL PLANS SHALL BE
 SUBMITTED UNDER THE MAIN PERMIT, UNLESS MECHANICAL IS
 TO BE COMPLETELY EXCLUDED FROM THE MAIN PERMIT, AND A
 SEPARATE PRIMARY PERMIT IS PULLED FOR MECHANICAL.
 PLEASE REQUEST THE ARCHITECT TO PROVISDE PLANS AND
 SPECIFICATIONS IN RESPONSE TO THE 1ST REVIEW COMMENTS
 LISTED BELOW.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING
 MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH,
 AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE
 INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN
 INDICATES 577 CFMS- SECTION 107.2.1 WPB.
  
 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR
 THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION
 M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR
 MAKEUP AIR.
  
 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING
 UNITS IN ATTICS:
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-11-26 Cont ID  
Sent By ccole Date 2019-11-26 Time 11:05 Rev Time 0.00
Received By ccole Date 2019-11-26 Time 11:05 Sent To  
Notes
2019-11-26 11:34:242ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19100236
 11/26/19
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW STILL EXIST.
 PLEASE NOTE THAT THE PLAN IS AN (8-1/2"X11") DOCUMENT
 ATTACHED WITH THE UPLOADED AC CALCULATIONS.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING
 MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH,
 AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE
 INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN
 INDICATES 577 CFMS- SECTION 107.2.1 WPB.
  
 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR
 THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION
 M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR
 MAKEUP AIR.
  
 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING
 UNITS IN ATTICS:
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-17 Cont ID  
Sent By ccole Date 2019-10-17 Time 17:15 Rev Time 0.00
Received By ccole Date 2019-10-17 Time 16:54 Sent To  
Notes
2019-10-17 17:17:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19100236
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE AC PLAN LISTING
 MAKE AND MODEL OF THE SYSTEM, COOLING AND HEATING BTUH,
 AND CFM CAPACITY. PLEASE NOTE THAT THE CALCULATIONS ARE
 INDICATING 411 CFMS OF SUPPLY AIR, HOWEVER THE PLAN
 INDICATES 577 CFMS- SECTION 107.2.1 WPB.
  
 2) EXHAUST VEMTILATION AT A RATE OF 100 CFMS
 INTERMITTENT OR 25 CFMS CONTINOUS SHALL BE PROVIDED FOR
 THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE SECTION
 M1503.1 FOR RANGE HOOD REQUIRMENTS, AND M1503.4 FOR
 MAKEUP AIR.
  
 3) VERIFY COMPLIANCE WITH SECTION R403.3.6 AIR-HANDLING
 UNITS IN ATTICS:
  
 AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC
 WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION
 R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR
 COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING
 CONDITIONS ARE MET:
  
 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN
 THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
  
 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1 AND M1401.4 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-01-17 Cont ID  
Sent By jesmith Date 2020-01-17 Time 13:22 Rev Time 0.00
Received By jesmith Date 2020-01-17 Time 13:16 Sent To  
Notes
2020-01-17 13:22:09PLUMBING COMMENTS: APPROVED W/PROVISO
 REVISE ENERGY FORM R405-2017 TO SHOW A GAS TANKLESS
 WATER HEATER; A 40 GALLON TANK TYPE IS INDICATED ON THE
 FORM. REVISED FORM SHALL BE SUBMITTED, APPROVED AND ON
 SITE PRIOR TO FINAL INSPECTION.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 09:40 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 09:24 Sent To  
Notes
2019-11-21 09:44:55PROVISO:
  
 1. REVISE ENERGY FORM R405-2017 TO SHOW A GAS TANKLESS
 WATER HEATER A 40 GAL TANK TYPE IS SHOWN NOW.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-30 Cont ID  
Sent By shill Date 2019-10-30 Time 06:05 Rev Time 0.00
Received By shill Date 2019-10-29 Time 11:27 Sent To  
Notes
2019-10-30 06:05:39PLUMBING 1ST REVIEW**DENIED**19100236
 1) PLEASE CLARIFY WHICH WATER HEATER YOU ARE USING. THE
 R405/2017 CALLS OUT CONVENTIONAL 40 GALLON STORAGE
 TANK, SHT.EP-1 NOTE #22 CALL OUT A.O SMITH GPD-75 (
 POWER VENT GAS STORAGE TANK), AND THE FLOOR PLAN SHOW
 GAS TANKLESS WATER HEATER. PLEASE CLARIFY. ALSO IF NOT
 THE UNIT CALLED OUT IN THE R405/2017 YOU WILL NEED TO
 CORRECT AND RESUBMIT. IF A GAS HEATER IS CHOSEN A GAS
 PERMIT AND COMPLETE GAS ISOMETRIC TO INCLUDE ANY AND
 ALL EXISTING BTU?S ON THE SYSTEM, MATERIAL. ETC. FBC
 107.3.5
 2) KITCHEN IS DISCHARGING INTO THE BATHROOM GROUP WET
 VENT. THE KITCHEN SHALL DISCHARGE DOWNSTREAM. FBCR-P
 3108.1
 3) ONLY 1 WET VENT FIXTURE IS PERMITTED BEYOND THE
 BATHROOM GROUP VENT. FBCR-P3108.22
 4) THESE PLANS LACK THE REQUIRED SIGN AND SEAL BY THE
 DESIGN PROFESSIONAL REQUIRED BY 61G1.16005
 5) PROVIDE BATHROOM DIMENSIONS. FBC 107.2
  
 TIM HUNT
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2020-02-10 Cont ID  
Sent By ccole Date 2020-02-10 Time 12:12 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 12:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-01-21 Cont ID  
Sent By jleahy Date 2020-01-21 Time 16:07 Rev Time 0.00
Received By jleahy Date 2020-01-21 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-12-17 Cont ID  
Sent By cthroop Date 2019-12-17 Time 14:27 Rev Time 0.00
Received By cthroop Date 2019-12-17 Time 06:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By ccole Date 2019-12-04 Time 07:57 Rev Time 0.00
Received By ccole Date 2019-12-04 Time 07:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-19 Cont ID  
Sent By cthroop Date 2019-11-19 Time 13:22 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 09:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-10-30 Cont ID  
Sent By shill Date 2019-10-30 Time 06:07 Rev Time 0.00
Received By shill Date 2019-10-30 Time 06:07 Sent To  
Notes
2019-10-30 06:09:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FS481, DOCUMENTS PREPARED BY AN ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS.
  
 ALL PAGES WERE PREPARED BY JEREMY K. WALTER. PAGES LACK
 A DIGITAL SIGNATURE AND SEAL. IF YOU ARE NOT CLEAR ON
 HOW TO ADDRESS THIS, HAVE THE ARCHITECT'S OFFICE
 CONTACT ME TO DISCUSS OPTIONS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-25 Cont ID  
Sent By fmittner Date 2019-11-25 Time 16:35 Rev Time 0.00
Received By fmittner Date 2019-11-25 Time 16:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-29 Cont ID  
Sent By fmittner Date 2019-10-29 Time 08:31 Rev Time 0.00
Received By fmittner Date 2019-10-29 Time 08:31 Sent To  
Notes
***NONE***