| Plan Review Stops For Permit 19100217 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-01-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-29 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-29 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2020-01-29 10:22:43 | BUILDING REVIEW APPROVED WITH PROVISO: | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | 1- REVISE ENERGY CALCULATIONS: | | | (A) PROVIDE CORRECT JURISDICTION NUMBER (604700). | | | (B)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA | | | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR | | | NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3 | | | FBC-ENERGY CONSERVATION. | | | (C) REVISE OVERHANG DEPTH AND SEPARATION OF WINDOW | | | LOCATED ON THE NORTH SIDE. SEE PLANS AND REVISE AS | | | REQUIRED. . | | | | | | 2- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING. | | | PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND | | | COMPLETE INSTALLATION SCHEDULE. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS). | | | | | | 4- REVISE AND RE-SUBMIT TRUSS PACKAGE: | | | (A)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". SEE PLANS | | | AND REVISE AS REQUIRED. | | | (B)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE | | | TRUSS PACKAGE BEFORE SUBMITTAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-01-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-16 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-16 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2020-01-16 13:56:45 | BUILDING REVIEW APPROVED WITH PROVISO: | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | 1- REVISE ENERGY CALCULATIONS: | | | (A)PROVIDE CORRECT OWNER'S NAME. | | | (B)PROVIDE BUILDER'S NAME. | | | (C)PROVIDE CORRECT JURISDICTION NUMBER (604700). | | | (D)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA | | | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR | | | NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3 | | | FBC-ENERGY CONSERVATION. AND DOOR IS LOCATED ON THE | | | WEST SIDE NOT NORTH SIDE. SEE PLANS AND REVISE AS | | | REQUIRED. | | | E) REVISE WINDOWS ORIENTATION AND OVERHANG DEPTH AND | | | SEPARATION TO MATCH PLANS. | | | | | | 2- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING. | | | PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND | | | COMPLETE INSTALLATION SCHEDULE. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS). | | | | | | 4- REVISE AND RE-SUBMIT TRUSS PACKAGE: | | | (A)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". SEE PLANS | | | AND REVISE AS REQUIRED. | | | (B)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE | | | TRUSS PACKAGE BEFORE SUBMITTAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-10 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-10 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2020-01-10 11:11:53 | RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR (OWNER/BUILDER)WILL SUBMIT REQUIRED | | | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES | | | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED | | | INFORMATION BEFORE PERMIT ISSUANCE. | | | | | | ****NEED OWNER'S SIGNATURE ON THE ENERGY CALCULATIONS | | | PRIOR TO ISSUANCE OF PERMIT. | | | | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 | | | FBC-ENERGY CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | A) PROVIDE 2 COPIES OF ENERGY CALCULATIONS. ONLY ONE | | | WAS PROVIDED. NEED TWO AS REQUIRED BY SEC. 107.1 CITY | | | AMENDMENTS. | | | | | | B) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED | | | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S | | | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY | | | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY | | | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION | | | (2017). | | | | | | C) PROVIDE COMPLETE AND CORRECT ON TOP OF FORM. NEED | | | CORRECT OWNER'S NAME AND CORRECT JURISDICTION NUMBER . | | | CITY 'S JURISDICTION NUMBER IS 604700 NOT 602700. ALSO, | | | PROVIDE THE NAME OF THE BUILDER FOR THIS ADDITION. SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | D) REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA | | | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THEREFORE, | | | THIS DOOR NEEDS TO BE INCLUDED IN THE WINDOW GLAZING | | | AREA AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY | | | CONSERVATION. AND DOOR IS NOT LOCATED ON THE NORTH | | | SIDE. THE DOOR IS LOCATED ON THE WEST SIDE. SEE PLANS | | | AND REVISE AS REQUIRED. | | | | | | E) REVISE WINDOWS ORIENTATION AND OVERHANG DEPTH AND | | | SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION. | | | NOTE: THERE IS ONLY ONE WINDOWS ON THE NORTH SIDE. AND, | | | THERE ARE TWO WINDOWS ON THE WEST SIDE. SEE PLANS AND | | | REVISE AS REQUIRED. | | | | | | | | | 2- 6 OK | | | | | | ORIGINAL COMMENT: | | | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW | | | NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE | | | IMPACT GLAZING. | | | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 | | | FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING | | | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE | | | INSTALLATION SCHEDULE AS REQUIRED BY CITY | | | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT | | | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY | | | SAMPLE | | | | | | RESPONSE: | | | WINDOW NOA WAS REPLACED WITH NOA 17-1212.21. THESE ARE | | | IMPACT WINDOWS AND DON'T REQUIRE SHUTTERS. ON THE OTHER | | | HAND, DOOR DOES REQUIRE SHUTTERS BECAUSE IT IS NOT AN | | | IMPACT DOOR. | | | NOTE: THIS MAY BE A PROVISO AND CONTRACTOR MAY SUBMIT | | | AFTER THE PERMIT IS APPROVED BUT BEFORE INSPECTIONS. | | | | | | ADDITIONAL COMMENT: | | | CLARIFY WHY SUBMITTING NOA 18-0529.03 FOR ALUMINUM | | | MULLIONS. THERE ARE NO MULLIONS SHOWN ON PLANS FOR THE | | | ADDITION. | | | | | | ORIGINAL COMMENT: | | | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC. | | | 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 9- IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | 10-OK. | | | | | | ORIGINAL COMMENT: | | | 11- TRUSS PACKAGE SUBMITTED: | | | (A)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". | | | (B)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE | | | TRUSS PACKAGE. | | | | | | RESPONSE. | | | REPEAT COMMENT. NOT ADDRESSED AT ALL. TRUSS ENGINEER | | | NEEDS TO REVISE THE TRUSS PACKAGE. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-20 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2019-11-20 18:33:47 | RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 | | | FBC-ENERGY CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | NOT ADDRESSED. | | | | | | 2- OK. | | | 3- OK. | | | 4-OK. | | | 5-OK | | | 6- OK | | | | | | ORIGINAL COMMENT: | | | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW | | | NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE | | | IMPACT GLAZING. | | | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 | | | FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING | | | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE | | | INSTALLATION SCHEDULE AS REQUIRED BY CITY | | | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT | | | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY | | | SAMPLE | | | | | | RESPONSE: | | | NOT ADDRESSED. THIS MAY BE A PROVISO AND CONTRACTOR MAY | | | SUBMIT AFTER THE PERMIT IS APPROVED BUT BEFORE | | | INSPECTIONS. | | | | | | ORIGINAL COMMENT: | | | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC. | | | 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | NOT ADDRESSED. | | | | | | 9- IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | 10-OK. | | | | | | NOTE: | | | TRUSS PACKAGE SUBMITTED NOTES: | | | 1)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. | | | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". | | | 2)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE | | | TRUSS PACKAGE. | | | 3)SUBMIT REVISED TRUSS PACKAGE TO BUILDING INSPECTOR A | | | T TIME OF FRAMING INSPECTION. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-10-23 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-10-23 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2019-10-23 18:40:45 | RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED | | | BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 | | | FBC-ENERGY CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | SEC. R401.3 FBC-RESIDENTIAL. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | | | | 3- THERE IS ONE WINDOW ON EXISTING BEDROOM #2 THAT IS | | | GOING TO BE BLOCKED TO ALLOW FOR THE ADDITION. SPECIFY | | | TYPE AND SIZE OF EXISTING WINDOW TO REMAIN ON THE SAME | | | BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS | | | REQUIREMENTS. SEC. 1101.1 FBC-EXISTING BUILDING AND | | | SEC. R310.2 FBC-RESIDENTIAL. | | | NOTE: SIMILAR SITUATION APPLIES TO EXISTING BEDROOM #1. | | | SPECIFY TYPE AND SIZE OF WINDOW TO REMAIN. | | | | | | 4- REVISE DESIGN CRITERIA SPECIFIED ON AT THE BOTTOM OF | | | GENERAL NOTES ON SHEET 1 OF 2. | | | THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT EXPOSURE | | | "B". REVISE AS REQUIRED AND REVISE DOORS/WINDOWS DESIGN | | | PRESSURES ACCORDINGLY. SEC. 1101.1 FBC-EXISTING | | | BUILDING AND SEC. R301.2.1.4 FBC-RESIDENTIAL. | | | | | | 5- ROOF FRAMING PLAN SHOWN ON SHEET 2 OF 2: | | | NEED TO SPECIFY TRUSS CONNECTOR FOR TRUSSES RESTING ON | | | THE (2)2X10 LEDGER LOCATED ON THE EXISTING GABLE END | | | THAT IS RECEIVING THE NEW TRUSSES. SEC. 1101.1 | | | FBC-EXISTING BUILDING AND SEC. R301.1 FBC-RESIDENTIAL. | | | | | | 6- EXTERIOR WALL SECTION ON SHEET 1 OF 2: | | | A) ROOFING MATERIAL IS NOT CLEAR. EXISTING HOUSE AND | | | PRODUCT APPROVAL SUBMITTED ARE FOR ROOF SHINGLES. THIS | | | WALL SECTION SPECIFIED ROOF TILE. REVISE/CLARIFY AS | | | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | B) SPECIFY THE MIN. THICKNESS OF THE VAPOR BARRIER AS | | | REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL AND SEC. | | | 1101.1 FBC-EXISTING BUILDING. | | | NOTE: THIS APPLIES TO THE SPECIFICATIONS ON THE | | | FOUNDATION PLAN ALSO. | | | | | | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR THE HURRICANE SHUTTERS SINCE WINDOW | | | NOA 17-1212.19 AND DOOR NOA 17-1212.10 DON'T HAVE | | | IMPACT GLAZING. | | | PROTECTION OF OPENINGS IS REQUIRED BY SEC. R301.2.1.2 | | | FBC-RESIDENTIAL AND SEC. 1101.1 FBC-EXISTING BUILDING | | | NOTE: NEED TO PROVIDE ALSO A SHUTTERS COMPLETE | | | INSTALLATION SCHEDULE AS REQUIRED BY CITY | | | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT | | | PROTECTION FOR THE FLORIDA BUILDING CODE. SEE CITY | | | SAMPLE | | | | | | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, | | | WINDOWS, SHINGLES, SHUTTERS) AS REQUIRED BY SEC. | | | 107.3.4.1 CITY AMENDMENTS. | | | | | | 9- IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | 10-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, | | | CONTRACTOR'S (APPLIES TO OWNER/BUILDER TOO) OVERHEAD | | | AND PROFIT AND DESIGN PROFESSIONAL FEES AS REQUIRED BY | | | SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO | | | $45,343. THE PERMIT FEE BALANCE IS $999.67 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-01-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-16 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-22 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2020-01-10 10:16:47 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-11-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-11-20 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-11-20 |
Time |
07:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-10-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-10-22 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-10-22 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2019-10-22 15:10:59 | APPROVED WITH PROVISO ON PLAN. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-01-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-29 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-27 |
Time |
09:25 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-01-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-16 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-10 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-02 |
Time |
11:18 |
Sent To |
I |
|
| Notes |
| 2020-01-03 11:18:49 | RESUB ROUTED TO JGOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-01 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-10-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-10-24 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-10-03 |
Time |
11:10 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2020-01-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-16 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-16 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2020-01-16 14:00:13 | $1,043.60 PAID. MU-2020-000486. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-10 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-10 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2020-01-10 17:50:58 | IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-21 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2019-11-21 08:25:44 | IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-10-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-10-24 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-10-24 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2019-10-24 08:38:05 | IMPACT FEES - | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK | | | OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. | | | PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT | | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2020-01-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-29 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-29 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2020-01-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-16 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-16 |
Time |
16:18 |
Sent To |
E |
|
| Notes |
| 2020-01-16 16:20:21 | | | | 01/16/2020 MET WITH MIRIAM. TOLD HER I NEED THE SECOND | | | COPY OF DRAWING M.1 IN ORDER TO APPROVE MECHANICAL | | | REVIEW WITH THE PROVISO. ONLY ONE COPY WAS SUBMITTED. | | | | | | | | | RESIDENTIAL (R3) ADDITION FOURTH MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK | | | (LOAD CALCULATIONS AND PLANS). SEC. 1101.1 FBC-EXISTING | | | BUILDING AND SEC. R403.7 FBC-ENERGY CONSERVATION. | | | NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS | | | REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | A) EQUIPMENT LOAD CALCULATIONS SUBMITTED ARE DONE BASED | | | ON THE FRONT DOOR FACING SOUTH. THIS IS INCORRECT. | | | CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL | | | ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. | | | R403.7.1 FBC-ENERGY CONSERVATION. THE MAIN ENTRY DOOR | | | IS FACING EAST. REVISE AS REQUIRED. NOTE: COORDINATE | | | WITH COMMENTS DONE ON THE ENERGY CALCULATIONS UNDER THE | | | BUILDING REVIEW COMMENTS. | | | | | | B) DRAWING M.1 SUBMITTED. REVISE THE NORTH ORIENTATION | | | ARROW TO MATCH PLANS AND SURVEY | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-10 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-10 |
Time |
17:55 |
Sent To |
|
|
| Notes |
| 2020-01-10 17:56:21 | RESIDENTIAL (R3) ADDITION THIRD MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: | | | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR (OWNER/BUILDER)WILL SUBMIT REQUIRED | | | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE | | | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES | | | APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS | | | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED | | | INFORMATION BEFORE PERMIT ISSUANCE. | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK | | | (LOAD CALCULATIONS AND PLANS). SEC. 1101.1 FBC-EXISTING | | | BUILDING AND SEC. R403.7 FBC-ENERGY CONSERVATION. | | | NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS | | | REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | A) EQUIPMENT LOAD CALCULATIONS SUBMITTED ARE DONE BASED | | | ON THE FRONT DOOR FACING SOUTH. THIS IS INCORRECT. | | | CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL | | | ORIENTATION OF THE BUILDING AS REQUIRED BY SEC. | | | R403.7.1 FBC-ENERGY CONSERVATION. THE MAIN ENTRY DOOR | | | IS FACING EAST. REVISE AS REQUIRED. NOTE: COORDINATE | | | WITH COMMENTS DONE ON THE ENERGY CALCULATIONS UNDER THE | | | BUILDING REVIEW COMMENTS. | | | | | | B) PROVIDE TWO COPIES AS REQUIRED BY SEC. 107.1 CITY | | | AMENDMENTS. ONLY ONE COPY WAS PROVIDED. | | | | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-11-21 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-11-21 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2019-11-21 08:27:30 | RESIDENTIAL (R3) ADDITION SECOND MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK | | | (LOAD CALCULATIONS AND PLANS). SEC. 1101.1 FBC-EXISTING | | | BUILDING AND SEC. R403.7 FBC-ENERGY CONSERVATION. | | | NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS | | | REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-10-23 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-10-23 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2019-10-23 18:57:45 | RESIDENTIAL (R3) ALTERATION/ADDITION MECHANICAL REVIEW | | | COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PROVIDE COMPLETE INFORMATION FOR THE MECHANICAL WORK | | | (LOAD CALCULATIONS AND PLANS). SEC. 1101.1 FBC-EXISTING | | | BUILDING AND SEC. R403.7 FBC-ENERGY CONSERVATION. | | | NOTE: SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL AS | | | REQUIRED BY SEC. R403.7.1 FBC-ENERGY CONSERVATION. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-01-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-16 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-16 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-01-10 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-01-10 |
Time |
17:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-11-12 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-11-12 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2019-11-12 16:35:45 | PLUMBING COMMENTS: APPROVED | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2019-10-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-10-10 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-10-10 |
Time |
08:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-10-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-10-24 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-10-23 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2019-10-24 08:32:29 | GAF SHINGLES NOA 18-0123.07. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-11-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-11-12 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-10-11 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2019-10-11 |
Time |
|
Sent To |
|
|
| Notes |
|
|