Plan Review Details - Permit 19090844
Plan Review Stops For Permit 19090844
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2020-03-09 Cont ID  
Sent By cpuell Date 2020-03-09 Time 16:29 Rev Time 0.00
Received By cpuell Date 2020-03-09 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-24 Cont ID  
Sent By pvalenti Date 2020-09-24 Time 11:29 Rev Time 0.00
Received By pvalenti Date 2020-09-24 Time 10:10 Sent To  
Notes
2020-09-24 11:37:55PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 PRIOR TO INSPECTIONS, PROVIDE THE ENGINEER REVIEW
 STAMPED PRODUCT APPROVALS FOR WINDOWS AND DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-10 Cont ID  
Sent By dbattles Date 2019-10-10 Time 15:42 Rev Time 0.00
Received By dbattles Date 2019-10-10 Time 15:42 Sent To  
Notes
2019-10-10 15:43:18BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19090844
 REVIEWED: OCTOBER 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA COMPLIANCE OR PERFORMANCE)
 - IF WORK AREA COMPLIANCED METHOD PLEASE ADD LEVEL OF
 ALTERATION TO DESIGN DATA.
  
 2) R314.1 FBC[R] GENERAL. SMOKE ALARMS SHALL COMPLY
 WITH NFPA 72 AND SECTION R314.
 - PLEASE SHOW LOCATION OF SMOKE ALARM
  
 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  
 4) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE
 PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5
  
 5) 301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED
 FOR THE LIVE LOAD INDICATED IN TABLE R301.6
 - ADD ROOF LOAD TO DESIGN DATA
  
 6) 301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED
 FOR THE LIVE LOAD INDICATED IN TABLE R301.6
  
 7) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 - PLEASE ADD NOTE FOR DOUBLE UNDERLAYMENT.
  
 8) INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD
 THAT WILL BE USED BY MARKING THE APPROPRIATE
 INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE
 WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC
 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE
 PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT
 WILL MEET WINDLOADS.
  
 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERRED.
  
 10) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERRED.
  
 11) PROVIDE WIND DESIGN PROJECT DATA: 301.2(2) TABLE
 FBC[R]
 TYPE OF CONSTRUCTION = _________(VB?)
 RISK CATEGORY = ___(?)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 OF ROOF DECK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 COMPONANT & CLADDING:
 FBC TABLE 301.2(2) FBC[R]
 DESIGN PRESSURE = +___ & -___
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By ppetty Date 2020-09-17 Time 13:03 Rev Time 0.00
Received By ppetty Date 2020-09-17 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-10-10 Cont ID  
Sent By jpearson Date 2019-10-10 Time 11:18 Rev Time 0.00
Received By jpearson Date 2019-10-08 Time 15:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 16:25 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 16:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 11:29 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By shill Date 2020-10-02 Time 07:08 Rev Time 0.00
Received By shill Date 2020-09-11 Time 15:00 Sent To  
Notes
2020-09-16 15:01:17R06
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-10 Cont ID  
Sent By dbattles Date 2019-10-10 Time 15:42 Rev Time 0.00
Received By dbattles Date 2019-09-20 Time 12:24 Sent To  
Notes
2019-09-23 12:24:18R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2021-03-02 Cont ID  
Sent By pvalenti Date 2021-03-02 Time 07:05 Rev Time 0.00
Received By pvalenti Date 2021-03-02 Time 07:04 Sent To  
Notes
2021-03-02 07:10:39****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEE REVIEW APPROVED:
  
 PAPER SET OF PLANS RETURNED WITH COUNTY IMPACT FEE
 STAMP AND PAYMENT RECEIPT.
  
 TRACKING # MU-2021-008580-0000
 RECEIPT # 2021-0302-3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-09-24 Cont ID  
Sent By pvalenti Date 2020-09-24 Time 13:12 Rev Time 0.00
Received By pvalenti Date 2020-09-24 Time 10:11 Sent To  
Notes
2020-09-24 13:15:25PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 IMPACT FEE REVIEW DENIED:
  
 109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. - CALL (561) 233?5025. - UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. - PLEASE RETURN STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-10 Cont ID  
Sent By dbattles Date 2019-10-10 Time 14:48 Rev Time 0.00
Received By dbattles Date 2019-10-10 Time 14:48 Sent To  
Notes
2019-10-10 14:48:43109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-16 Cont ID  
Sent By pvalenti Date 2021-02-16 Time 09:18 Rev Time 0.00
Received By pvalenti Date 2021-02-16 Time 09:18 Sent To  
Notes
2021-02-16 10:02:10PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW APPROVED.
  
 NOTE: PRIOR TO MECHANICAL WORK A MECHANICAL SUB-PERMIT
 IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-09-19 Cont ID  
Sent By pvalenti Date 2020-09-19 Time 12:07 Rev Time 0.00
Received By pvalenti Date 2020-09-19 Time 10:26 Sent To  
Notes
2020-09-19 12:32:23PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW DENIED:
  
 1) FBC B 107.2.1, PLAN SHEET A-3 INDICATES TWO
 MINI-SPLIT AIR HANDLERS (2) ZONES. THIS DOES NOT MATCH
 MECHANICAL SHEET M-1 WHICH INDICATES ONLY ONE AIR
 HANDLER (1) ZONE FOR THE MINI-SPLIT SYSTEM. PROVIDE
 MATCHING PLAN SHEETS FOR AIR HANDLERS.
  
 PROVISO:
 FBC B 107.2.1 & FBC R M 1506.2, THE BATHROOM EXHAUST
 FAN (50 CFM) NEEDS TO BE SUFFICIENT TO MEET THE MINIMUM
 50 CFM .25 STATIC PRESSURE EXHAUST SYSTEM REQUIREMENT.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By lcrespo Date 2020-09-21 Time 18:24 Rev Time 0.00
Received By lcrespo Date 2020-09-21 Time 18:24 Sent To  
Notes
2020-09-21 18:25:2909/21/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-04 Cont ID  
Sent By gjohnson Date 2019-10-04 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2019-10-04 Time 10:48 Sent To  
Notes
2019-10-04 12:52:531ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY ISOMETRIC SHALL SHOW THE UTILITY SINK
 VENTED SEPARATELY AND CONNECTED DOWN STREAM OF THE
 BATHROOM GROUP. PER FBC RES P3108.1
  
 2. PROVIDE SHOWER PAN DETAIL SHOW COMPLIANCE WITH FBC
 RES P2709.1, P2709.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-02-16 Cont ID  
Sent By pvalenti Date 2021-02-16 Time 09:03 Rev Time 0.00
Received By pvalenti Date 2021-02-16 Time 09:03 Sent To  
Notes
2021-02-16 09:08:06PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW APPROVED:
 PRIOR TO ROOF WORK A ROOFING SUB-PERMIT IS REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-09-24 Cont ID  
Sent By pvalenti Date 2020-09-24 Time 12:55 Rev Time 0.00
Received By pvalenti Date 2020-09-24 Time 11:38 Sent To  
Notes
2020-09-24 11:39:57PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE SUBMIT THE ROOFING PRODUCT
 APPROVALS WITH THE OPTIONS THAT WILL BE USED CIRCLED OR
 MARKED.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-25 Cont ID  
Sent By fmittner Date 2020-09-25 Time 16:26 Rev Time 0.00
Received By fmittner Date 2020-09-25 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 11:29 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 11:29 Sent To  
Notes
***NONE***