| 2019-10-10 15:43:18 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19090844 |
| | REVIEWED: OCTOBER 10, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION, |
| | CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL |
| | EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3 |
| | SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER. |
| | A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE |
| | METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF |
| | OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN |
| | BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION |
| | CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE |
| | REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE |
| | SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS |
| | OF THIS CODE. |
| | C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD. |
| | REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY |
| | AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF |
| | THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE |
| | PROVISIONS OF THIS CODE. |
| | - WHICH METHOD IS BEING USED FOR COMPLIANCE? |
| | (PRESCRIPTIVE,WORK AREA COMPLIANCE OR PERFORMANCE) |
| | - IF WORK AREA COMPLIANCED METHOD PLEASE ADD LEVEL OF |
| | ALTERATION TO DESIGN DATA. |
| | |
| | 2) R314.1 FBC[R] GENERAL. SMOKE ALARMS SHALL COMPLY |
| | WITH NFPA 72 AND SECTION R314. |
| | - PLEASE SHOW LOCATION OF SMOKE ALARM |
| | |
| | 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | |
| | 4) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE |
| | PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| | R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| | R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 |
| | |
| | 5) 301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED |
| | FOR THE LIVE LOAD INDICATED IN TABLE R301.6 |
| | - ADD ROOF LOAD TO DESIGN DATA |
| | |
| | 6) 301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED |
| | FOR THE LIVE LOAD INDICATED IN TABLE R301.6 |
| | |
| | 7) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM |
| | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND |
| | LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. |
| | - PLEASE ADD NOTE FOR DOUBLE UNDERLAYMENT. |
| | |
| | 8) INDICATE THE CEMENT ROOF TILE AND ATTACHMENT METHOD |
| | THAT WILL BE USED BY MARKING THE APPROPRIATE |
| | INFORMATION ON THE PLANS. FBC 107.2.1 IF AN ADHESIVE |
| | WILL BE USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC |
| | 107.3.4 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE |
| | PRODUCT APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT |
| | WILL MEET WINDLOADS. |
| | |
| | 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERRED. |
| | |
| | 10) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERRED. |
| | |
| | 11) PROVIDE WIND DESIGN PROJECT DATA: 301.2(2) TABLE |
| | FBC[R] |
| | TYPE OF CONSTRUCTION = _________(VB?) |
| | RISK CATEGORY = ___(?) |
| | EXPOSURE CATEGORY = ___(B,C OR D) |
| | BUILDING CLASSIFICATION = __________(ENCLOSED) |
| | MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT |
| | OF ROOF DECK) |
| | WIND SPEED V ULT = _____(170) |
| | WIND SPEED V ASD = _____(132) |
| | COMPONANT & CLADDING: |
| | FBC TABLE 301.2(2) FBC[R] |
| | DESIGN PRESSURE = +___ & -___ |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |