Plan Review Details - Permit 19090792
Plan Review Stops For Permit 19090792
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-01 Cont ID  
Sent By cthroop Date 2020-02-01 Time 06:56 Rev Time 0.00
Received By cthroop Date 2020-02-01 Time 06:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-14 Cont ID  
Sent By cthroop Date 2019-12-14 Time 10:40 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 10:49 Rev Time 0.00
Received By cthroop Date 2019-10-03 Time 16:17 Sent To  
Notes
2019-10-19 11:01:27BUILDING PLAN REVIEW
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 ADMINISTRATIVE NOTICE:
  
 A SEPERATE PERMIT NUMBER (19100856) HAS BEEN ASSIGNED
 TO THE CABANA. A VALUE OF $30,000.00 HAS BEEN ASSIGNED
 TO IT WITH A CORRESPONDING REDUCTION IN VALUE OF THE
 MAIN RESIDENCE, PERMIT NUMBER (19090792).
  
 1. AN ELEVATION CERTIFICATE IS REQUIRED. SEE COMMENTS
 UNDER THE NFIP REVIEW.
  
 2. PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 3. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 SEE COMMENTS UNDER THE IMPACT FEE REVIEW.
  
 4. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT.
 DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE
 A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR
 REVIEW.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-02-04 Cont ID  
Sent By fgiaquin Date 2020-02-04 Time 11:40 Rev Time 0.00
Received By fgiaquin Date 2020-01-30 Time 07:36 Sent To  
Notes
2020-02-04 11:40:28OK PER CHRIS TROOP
  
 I ACCIDENTLY CHECKED IN PLAN BY MISTAKE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-16 Cont ID  
Sent By cthroop Date 2019-12-16 Time 09:08 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:40 Sent To  
Notes
2019-12-16 09:21:56PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SERVICE OUTLET AT CU-1 & CU-6.
 E3901.12 HVAC OUTLET.
  
 2. AVAILABLE FAULT CURRENT FROM FPL TRANSFORMER IS
 30684. FAULT CURRENT USED ON PAGE E-5 FOR AVAILABLE
 FAULT CURRENT CALCULATIONS IS 52,205. PLEASE CORRECT.
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10 & FBC RE E3404.3
  
 3. REMOVE PANEL DP FROM RISER DIAGRAHM. PANEL DP IS TO
 BE REMOVED FROM SOW PER RESPONSE LETTER FROM DESIGNER.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PANEL B SHOWS A TOTAL LOAD OF 119 AMPS. OVERCURRENT
 PROTECTION FROM MDP IS 100 AMPS. PLEASE CORRECT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-12 Cont ID  
Sent By fgiaquin Date 2019-10-12 Time 12:32 Rev Time 0.00
Received By fgiaquin Date 2019-10-10 Time 06:36 Sent To  
Notes
2019-10-12 12:26:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FIRST FLOOR
  
 1. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS.(FOYER AND FAMILY ROOM) FIXED
 PANELS IN FAMILY ROOM COUNT FOR WALL SPACING.
  
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1
  
 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE, GENERATOR,
 AND ELEVATOR WILL REQUIRE SEPARATE PERMITS. FBC 107.2.1
 FBC 105.1
  
 3. RECEPTACLE REQUIRED FOR PATIO OUTSIDE OF BEDROOM #1
 NEC 210.52E3
  
 4. DISCONNECTS BEHIND CU2 DO NOT HAVE THE REQUIRED
 WORKING CLEARANCE. NEC 110.26A
  
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 6. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
  
 SECOND FLOOR,
  
 1. RECEPTACLES REQUIRED ON ALL BALCONIES OUTSIDE. NEC
 210.52E3
  
 2.PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AND SWITCH
 CONTROLLED LIGHT FOR SERVICING EACH AHU LOCATED IN AN
 ATTIC. FBC MECHANICAL CODE M306.3.1
  
 3. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3901.2.9
  
 SERVICE/RISER
  
 1. FAULT CURRENT CALCULATION FOR SERVICE IS BLURRY AND
 NOT READABLE, ALSO PROVIDE FAULT CURRENT LETTER FROM
 POWER UTILITY (FPL). FBC 107.2.1
  
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 3. LOCATION OF DOCK PANEL NOT SHOWN? HOW FAR AWAY FROM
 SERVICE IS DOCK PANEL LOCATED AND WHAT IS THE VOLTAGE
 DROP? FBC 107.2.1
  
 4. PANEL SCHEDULE FOR DOCK NOT SHOWN, WHAT IS LOAD OF
 DOCK PANEL? FBC 107.2.1
  
 5.THE RISER DIAGRAM SHOWS THE FEEDERS FOR ALL PANELS
 FED FROM MDP, EXCEPT PANEL B, AS "TWO SETS OF 350 MCM
 CU". SHOW ACTUAL FEEDER SIZE FOR ALL PANELS. FBC
 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-02-04 Cont ID  
Sent By jesmith Date 2020-02-04 Time 10:49 Rev Time 0.00
Received By jesmith Date 2020-02-04 Time 10:46 Sent To  
Notes
2020-02-04 10:46:42GAS COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-12-19 Cont ID  
Sent By jesmith Date 2019-12-19 Time 13:04 Rev Time 0.00
Received By jesmith Date 2019-12-19 Time 11:21 Sent To  
Notes
2019-12-19 13:04:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMENTS: DENIED
  
 1. PLAN SHEET P-4: GAS RISER DIAGRAM IS MISSING SECOND
 FLOOR FIREPLACE. PER WPB FBC 107.2.1 AND 107.3.5.3
 (12), INCLUDE IN DIAGRAM.
 2. PLAN SHEET P-4 REGARDING "GAS NOTES & CALCULATIONS",
 DELETE NOTE "PROVIDE A 1-1/4" GAS LINE PER:".
 3. PLAN SHEET A-1.1 AND A-2.2 DO NOT NOTE TWO OF THE
 FIVE FIREPLACES NOTED ON PLAN SHEETS P-1 AND P-2 AND ON
 P-4 TOTAL GAS LOAD GAS EQUIPMENT SCHEDULE. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) FOR FIREPLACES PER FBC FG
 SECTIONS 502 THRU 505 OR FBC RES SECTIONS G2426 THROUGH
 G2439.
 5. PER WPB FBC 107.2.1, PROVIDE A NOTE STATING "PLASTIC
 PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY.
 PLASTIC PIPE SHALL NOT BE USED WITHIN OR UNDER ANY
 BUILDING OR SLAB." TO COMPLY WITH FBC FG 404.17.1 AND
 FBC RES G2415.17.1.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090792 3030 WASHINGTON RD

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-10-23 Cont ID  
Sent By shill Date 2019-10-23 Time 05:54 Rev Time 0.00
Received By shill Date 2019-10-21 Time 10:51 Sent To  
Notes
2019-10-21 10:51:48GAS 1ST REVIEW**DENIED** A SEPARATE GAS PERMIT FOR THE
 HOME AND SEPARATE GENERATOR PERMIT IS REQUIRED. FBC
 105.1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER. 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2. SECTION OF PIPING WHICH I
 BUBBLED IN ON THE ISOMETRIC ARE MISSING CUT SECTIONS.
 PLEASE ADD TO CLARIFY.
  
 2. YOUR CALCULATIONS FOR COMBUSTION AIR LIST AN AIR KIT
 IS REQUIRED FOR THE LIBRARY IS REQUIRED. PLEASE PROVIDE
 HOW YOU INTENT TO COMPLY WITH THE REQUIRED MAKE UP AIR.
 FBCR G2407.9.3
  
 3. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC-RES. SEC. G2421.1.
  
 4. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. IT APPEARS THE
 TANKLESS OUTSIDE OF BATHROOM #1 MAY BE TOO CLOSE.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 6. R405/2017 FORM ONLY LIST 1 TANKLESS GAS WATER HEATER
 THIS HOME HAS 3. PLEASE CORRECT AND SUBMIT MANUFACTURES
 INSTALLATION MANUAL TO SHOW THEY COMPLY WITH THE 2017
 FLORIDA ENERGY CODE AND FEDERAL MIN STANDARDS. FBC
 107.3.5
  
 7. PLEASE ADD NOTE THAT ALL EXTERIOR PIPING SHALL HAVE
 A PROTECTIVE PAINT COATING. NFPA 54
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By fmittner Date 2020-02-06 Time 15:40 Rev Time 0.00
Received By fmittner Date 2020-02-06 Time 15:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-10-08 Cont ID  
Sent By fmittner Date 2019-10-08 Time 15:16 Rev Time 0.00
Received By fmittner Date 2019-10-08 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-06 Cont ID  
Sent By lmarchan Date 2020-02-06 Time 15:47 Rev Time 0.00
Received By lmarchan Date 2020-01-27 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-24 Cont ID  
Sent By lmarchan Date 2019-12-24 Time 08:03 Rev Time 0.00
Received By lmarchan Date 2019-12-09 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-31 Cont ID  
Sent By lmarchan Date 2019-10-31 Time 11:35 Rev Time 0.00
Received By lmarchan Date 2019-10-01 Time 11:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By lmarchan Date 2020-02-06 Time 15:48 Rev Time 0.00
Received By lmarchan Date 2019-10-21 Time 07:54 Sent To  
Notes
2020-02-05 11:39:21RECEIPT 2020-0206-102 - $22.46 - PAID
2019-10-21 07:54:1310/21/19 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 11:01 Rev Time 0.00
Received By cthroop Date 2019-10-08 Time 16:21 Sent To  
Notes
2019-10-19 11:03:23PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-14 Cont ID  
Sent By cthroop Date 2019-12-14 Time 10:43 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 08:44 Rev Time 0.00
Received By cthroop Date 2019-10-18 Time 16:58 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status P Date 2020-03-02 Cont ID  
Sent By cthroop Date 2020-03-02 Time 14:41 Rev Time 0.00
Received By cthroop Date 2020-03-02 Time 14:41 Sent To I
Notes
2020-03-02 15:05:43NFIP REVIEW - PASSED WITH PROVISO'S:
  
 UPON SUBMITTAL OF THE UNDER CONSTRUCTION ELEVATION
 CERTIFICATE -
  
 1. PROVIDE THE ELEVATION OF THE GARAGE FINISHED FLOOR -
 SEE SECTION C2 (D).
  
 2. CHANGE TYPE OF FLOOD OPENINGS IN GARAGE FROM
 NON-ENGINEERED TO ENGINEERED PER CONVERSATION WITH
 CONTRACTOR - SEE SECTION A9 (D).
  
 3. PROVIDE ICC ES EVALUATION REPORT FOR ENGINEERED
 FLOOD OPENINGS.
  
 4. REDLINE GARAGE FLOOR PLAN WITH FINISHED FLOOR
 ELEVATION.
  
 NOTE: THE GREEHECK AF J60 1X VENTS SHOWN ON PLAN PAGE
 A-1-1 ARE NOT APPROVED FLOOD VENTS.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2020-02-03 Cont ID  
Sent By cthroop Date 2020-02-03 Time 16:25 Rev Time 0.00
Received By cthroop Date 2020-02-03 Time 16:25 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2020-02-01 Cont ID  
Sent By cthroop Date 2020-02-01 Time 06:49 Rev Time 0.00
Received By cthroop Date 2020-02-01 Time 06:49 Sent To  
Notes
2020-02-01 06:50:03PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION C2 REQUIRES BENCHMARK UTILIZED TO BE
 DESCRIBED IN COMMENTS SECTION.
  
 2. SECTION C2 (D) REQUIRES TOP OF SLAB FOR ATTACHED
 GARAGE TO BE STATED. THIS ELEVATION ALSO NEEDS TO BE
 PLACED ON PLAN.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-12-23 Cont ID  
Sent By cthroop Date 2019-12-23 Time 09:27 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:39 Sent To  
Notes
2019-12-23 09:30:04PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION C2 REQUIRES BENCHMARK UTILIZED TO BE
 DESCRIBED IN COMMENTS SECTION.
  
 2. SECTION C2 (D) REQUIRES TOP OF SLAB FOR ATTACHED
 GARAGE TO BE STATED. THIS ELEVATION ALSO NEEDS TO BE
 PLACED ON PLAN.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 11:19 Rev Time 0.00
Received By cthroop Date 2019-10-12 Time 07:41 Sent To  
Notes
2019-10-19 11:24:49NFIP REVIEW
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THIS PROPERTY IS LOCATED IN A FLOOD ZONE AE. AN
 ELEVATION CERTIFICATE IS REQUIRED.
  
 NFIP REVIEW
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A TWO
 FOOT FREEBOARD ABOVE THE (BFE).
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 AE WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 9. 0 FEET. PLEASE NOTE THIS
 INFORMATION ON YOUR PLANS.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET NAVD.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING
 FINAL.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-02-04 Cont ID  
Sent By jesmith Date 2020-02-04 Time 10:51 Rev Time 0.00
Received By jesmith Date 2020-02-04 Time 10:50 Sent To  
Notes
2020-02-04 10:51:41PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 SEE PERMIT 19100856 FOR CABANA APPROVAL

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-19 Cont ID  
Sent By jesmith Date 2019-12-19 Time 11:15 Rev Time 0.00
Received By jesmith Date 2019-12-19 Time 07:43 Sent To  
Notes
2019-12-19 11:15:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. ADD NOTE: IRRIGATION REQUIRES SEPARATE PERMIT. ANY
 BACKFLOW THAT IS REQUIRED BY THE FBC OR CITY ORD WILL
 REQUIRE A SEPARATE PERMIT INSTALLED BY PLUMBING
 CONTRACTOR ONLY.
 2. RE: PLAN SHEET P-1; DETAIL 5. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER?S SPECIFICATION AND INSTALLATION
 GUIDE. TO BE CLEAR, ALL PLUMBING CONNECTIONS, BACKFLOW
 PREVENTION REQUIREMENTS, TEMPERATURE OUTPUT, WORKING
 PRESSURE, PRESSURE RATINGS, SAFETY DEVICES, WASTE
 DISCHARGE TEMPERATURE, ELECTRICAL CHARACTERISTICS, ETC.
 SHALL BE INCLUDED
 INDICATE TEMPERATURE OF DISCHARGE; IF IN EXCESS OF 140
 DEGREES F THEN PER FBC RES P2601.1 AND FBC PL 702.5,
 SANITARY PIPING MATERIAL RECEIVING THE DISCHARGE SHALL
 BE RATED FOR THE TEMPERATURE OF THE DISCHARGE WASTE AND
 SHALL CONFORM TO THE TABLES OF FBC PL 702.1, 702.2,
 702.3 AND 702.4 OR PROVIDE AFTERCOOLER WITH APPROPRIATE
 BACKFLOW PREVENTION.
 3. SEE PLAN SHEET P-1: TO CONFORM WITH THE DEFINITION
 OF A BUILDING DRAIN AS STATED IN FBC RES R202, PLEASE
 NOTE THAT THERE ARE FOUR SEPARATE BUILDING DRAINS
 SERVING THE FOLLOWING AREAS; CABANA, NORTH SIDE OF MAIN
 HOUSE, SOUTH SIDE OF MAIN HOUSE AND GARAGE. PER FBC RES
 P3102.1, PROVIDE A VENT TO THE EXTERIOR FOR EACH THE
 NORTH SIDE AND THE SOUTH SIDE OF THE MAIN HOUSE.
 4. SHOWER IN HIS BATH IS NOT VENTED IN ACCORDANCE WITH
 FBC RES P3108.1. INDIVIDUALLY VENT TO COMPLY WITH FBC
 RES P3105.1.
 5. WATER CLOSET IN HIS BATH IS NOT VENTED. INDIVIDUALLY
 VENT TO COMPLY WITH FBC RES P3105.1.
 6. BRANCH DOWNSTREAM OF WASHER SHALL BE SIZED 3? PER
 FBC RES P3005.1.6
 7. SHOWER IN HER BATH SHALL BE LABELED ON SANITARY
 ISOMETRIC WPB FBC 107.2.1
 8. LAVATORY IN ROOF BATH SHALL BE LABELED ON SANITARY
 ISOMETRIC WPB FBC 107.2.1
 9. SHOWER IN HER BATH SHALL CONNECT ABOVE THE WATER
 CLOSET PER FBC RES P3107.3 OR BE INDIVIDUALLY VENTED
 PER FBC RES P3105.1. PER FBC RES P3105.2, THE SHOWER
 FIXTURE DRAIN SHALL NOT RISE VERTICALLY ABOVE THE
 CONNECTION OF THE VENT.
 10. LAVATORY IN HER BATH SHALL CONNECT TO THE
 HORIZONTAL SECTION OF THE TUB FIXTURE DRAIN PER FBC RES
 P3108.1 AND FBC RES P3105.2, OR THE TUB SHALL BE
 INDIVIDUALLY VENTED PER FBC RES P3105.1.
 11. SEE PLAN SHEET P-1: PER FBC RES 2601.1 AND FBC PL
 607.2, PROVIDE RECIRCULATED HOT WATER PIPING FOR ANY
 HOT WATER DISTRIBUTION SYSTEM THAT EXCEEDS 50? FROM HOT
 WATER SOURCE TO FARTHEST OUTLET.PER WPB FBC 107.2.1,
 PROVIDE NOTE STATING THE SAME.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090792 3030 WASHINGTON RD
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-23 Cont ID  
Sent By shill Date 2019-10-23 Time 05:55 Rev Time 0.00
Received By shill Date 2019-10-18 Time 18:42 Sent To  
Notes
2019-10-21 10:51:18PLUMBING 1ST REVIEW**DENIED** PLEASE ADD NOTE
 IRRIGATION REQUIRES SEPARATE PERMIT. ANY BACKFLOW THAT
 IS REQUIRED BY THE FBC OR CITY ORD WILL REQUIRE A
 SEPARATE PERMIT INSTALLED BY PLUMBING CONTRACTOR ONLY.
  
 1) PROVIDE SHOWER PAN DETAIL SHOWING MATERIAL TO BE
 USED AND 2% SLOPE. FBCR-P 2709.
  
 2) PROVIDE STEAM UNIT DRAIN DETAIL FOR HIS STEAM UNIT.
 FBC 107.2.1
  
 3) THE CABANA BEING THAT IT HAS ITS OWN BUILDING DRAIN
 WITH NOT PERMIT THE USE OF AN AAV AS IT WILL REQUIRE A
 VENT TO THE OUTDOORS. FBCR-P3102.1
  
 4) PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 SEE MARK UPS ON ISO SHEET SHOWING ERRORS. THE FOLLOWING
 COMMENTS APPLY
  
 A-ONLY 1 WET VENTED FIXTURE IS PERMITTED BEYOND THE
 VENT. FBCR-P 3102.1
 B-CAN NOT USE THE VENT STACK ON A LOWER LEVEL WET VENT
 FOR 2ND FLOOR BATHROOM. FBCR-P 3108.1
 C- SHOWER MUST BE VENTED AND DIRECTLY CONNECTED INTO
 THE BATHROOM GROUP WET VENT. FBCR-P3108.1
 D- PROVIDE SIZING OF EACH SECTION OF BUILDING DRAIN IN
 THE HIGHLIGHTED SECTIONS. FBC 107.3.5
 E-NO OTHER FIXTURE OTHER THEN THOSE FIND IN THE
 BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE
 BATHROOM GROUP WET VENT.
  
 5) PROVIDE NOTE THAT ACCESS TO ALL AAV SHALL BE
 PROVIDED. FBCR-P3114.5
  
 6) PROVIDE BRANCH LINE SIZE OF WASHING MACHINE. PLEASE
 NOTE MUST BE 3? IN ORDER TO USE AAV PER THE
 INSTALLATION MANUAL FOR ALL AAV?S. FBCR-P 3114.2
  
 7) PROVIDE STORM ISOMETRIC DRAWING. FBC 107.3.5
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGASOLUTIONS)
 [email protected]?
 561-248-2703
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By cthroop Date 2020-01-28 Time 11:32 Rev Time 0.00
Received By cthroop Date 2020-01-28 Time 11:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-12-14 Cont ID  
Sent By cthroop Date 2019-12-14 Time 10:47 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:40 Sent To  
Notes
2019-12-14 10:48:34BUILDING PLAN REVIEW - ROOFING
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT.
 DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE
 A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR
 REVIEW.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 11:10 Rev Time 0.00
Received By cthroop Date 2019-10-03 Time 16:18 Sent To  
Notes
2019-10-19 11:13:06BUILDING PLAN REVIEW - ROOFING
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THIS PROPERTY IS LOCATED WITHIN A HISTORIC DISTRICT.
 DEFERRAL OF PRODUCT APPROVALS AS NOTED ON PLAN PAGE
 A-0.0 ARE NOT ALLOWED. SUBMIT ALL PRODUCT APPROVALS FOR
 REVIEW.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-02-01 Cont ID  
Sent By cthroop Date 2020-02-01 Time 06:57 Rev Time 0.00
Received By cthroop Date 2020-02-01 Time 06:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-12-14 Cont ID  
Sent By cthroop Date 2019-12-14 Time 09:05 Rev Time 0.00
Received By cthroop Date 2019-12-12 Time 16:40 Sent To  
Notes
2019-12-31 15:28:39HARD COPY OF SOILS REPORT SENT TO RECORDS. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-10-15 Cont ID  
Sent By cthroop Date 2019-10-15 Time 12:52 Rev Time 0.00
Received By cthroop Date 2019-10-08 Time 16:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By fmittner Date 2020-02-06 Time 15:40 Rev Time 0.00
Received By fmittner Date 2020-02-06 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-10-10 Cont ID  
Sent By fmittner Date 2019-10-08 Time 15:17 Rev Time 0.00
Received By fmittner Date 2019-10-10 Time 15:43 Sent To  
Notes
2019-10-08 15:18:44REQURIES SUBMITTAL OF SEPERATE LANDSCAPE PLAN OR
 AFFIDAVIT


Account Summary | Usage Policy | Privacy Policy