| 2019-12-09 15:15:23 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19090606 |
| | ADD: 1645 PALM BEACH LAKES BLVD. SUITE: 800 |
| | CONT: NIXON HOME IMPROVEMENTS |
| | TEL: 561-305-8215 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. DEC. 09/2019 |
| | ACTION: DENIED |
| | |
| | *****************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B)******************* |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1A)2ND REQUEST. THE COVERSHEET INDICATES THE MINIMUM |
| | BUILDING TYPE AS CONSTRUCTION TYPE III-B. GOOGLE MAPS |
| | SHOWS 1645 PALM BEACH LAKES BLVD. AS A 11 STORY |
| | HIGH-RISE OFFICE BUILDING. PLEASE REVIEW THE 2017 FBC-B |
| | TABLE 504.4 AS A CONSTRUCTION TYPE I-B CONSTRUCTION. |
| | PLEASE CORRECT THE PLANS. |
| | |
| | 1B)COMPLIED. |
| | |
| | 1C) NEW COMMENT. THE CONTRACTOR HAS NOT COLLATED THE |
| | PLANS WITH THE OLD PLANS, MISSING SHEETS A-0 AND D-1 |
| | MISSING IN THE NEW SETS. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2-3) COMPLIED |
| | |
| | 4) THE LIFE SAFETY SHEET A-2 DOES NOT SHOW TABLE AND |
| | CHAIR LAYOUT, NOR IS THERE ANY DETAILS SHOWING |
| | COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE: |
| | 4A-4C)(1) COMPLIED. |
| | |
| | 4C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK AREAS SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4D) 2ND REQUEST. SEMI-COMPLIED. THE NEW DETAIL 8 ON |
| | SHEET A-4 SHOWS THE SINK AT 34 INCHES BUT NOT THE |
| | COUNTERTOP OF THE BOTTOM CABINETS. MUST COMPLY WITH: |
| | 2017 FBC-ACCESSIBILITY CODE. 902.3 HEIGHT. THE TOPS OF |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 1ST ROUND COMMENTS. THERE IS NO DETAIL OF THE EXISTING |
| | BREAK ROOM BOTTOM CABINETS AND SINK. CODE COMPLIANCE |
| | CANNOT BE ACHIEVED. THE 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 202.4.1 DISPROPORTIONATE COST. UP TO 20% OF THE |
| | CONSTRUCTION COST ($6,000.00) COULD BE REQUIRED TO HAVE |
| | THE COUNTERTOP AND SINK ACCESSIBLE. |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 2017 FBC-ACCESSIBILITY CODE. 902.3 HEIGHT. THE TOPS OF |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |