Plan Review Details - Permit 19090606
Plan Review Stops For Permit 19090606
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2020-03-11 Cont ID  
Sent By jwitmer Date 2020-03-11 Time 15:09 Rev Time 0.00
Received By jwitmer Date 2020-03-11 Time 15:09 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-01-14 Cont ID  
Sent By jwitmer Date 2020-01-14 Time 16:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-01-14 16:15:37ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-12-09 Cont ID  
Sent By jwitmer Date 2019-12-09 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2019-12-09 Time 07:33 Sent To  
Notes
2019-12-09 15:16:05ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2019-10-01 13:55:18ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY.
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 837-5900 ASBESTOS PROGRAM COORDINATOR
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-03-11 Cont ID  
Sent By jwitmer Date 2020-03-11 Time 15:44 Rev Time 0.00
Received By jwitmer Date 2020-03-11 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-01-14 Cont ID  
Sent By jwitmer Date 2020-01-14 Time 16:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-01-14 16:14:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090606
 ADD: 1645 PALM BEACH LAKES BLVD. SUITE: 800
 CONT: NIXON HOME IMPROVEMENTS
 TEL: 561-305-8215
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JAN. 14/2020
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) NEW COMMENT. THE COVERSHEET & SHEET A-2 BOTH SHOW AN
 OCCUPANT LOAD OF 97 FOR 685 SQ. FT. OF THE BREAK ROOM.
 THE AREA OF THE BREAK ROOM IS CLOSER TO 24.5 X 27.5 =
 674 SQ. FT./ 15 SQ. FT. PER OCC= 45 OCCUPANTS PLEASE
 CORRECT. SEE 2017 FBC-B TABLE 1004.1.2. ASSEMBLY WITH
 TABLES AND CHAIRS. 15 SQ. FT. OCCUPANT LOAD FACTOR.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-09 Cont ID  
Sent By jwitmer Date 2019-12-09 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2019-12-09 Time 07:33 Sent To  
Notes
2019-12-09 15:15:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090606
 ADD: 1645 PALM BEACH LAKES BLVD. SUITE: 800
 CONT: NIXON HOME IMPROVEMENTS
 TEL: 561-305-8215
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. DEC. 09/2019
 ACTION: DENIED
  
 *****************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)*******************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1A)2ND REQUEST. THE COVERSHEET INDICATES THE MINIMUM
 BUILDING TYPE AS CONSTRUCTION TYPE III-B. GOOGLE MAPS
 SHOWS 1645 PALM BEACH LAKES BLVD. AS A 11 STORY
 HIGH-RISE OFFICE BUILDING. PLEASE REVIEW THE 2017 FBC-B
 TABLE 504.4 AS A CONSTRUCTION TYPE I-B CONSTRUCTION.
 PLEASE CORRECT THE PLANS.
  
 1B)COMPLIED.
  
 1C) NEW COMMENT. THE CONTRACTOR HAS NOT COLLATED THE
 PLANS WITH THE OLD PLANS, MISSING SHEETS A-0 AND D-1
 MISSING IN THE NEW SETS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2-3) COMPLIED
  
 4) THE LIFE SAFETY SHEET A-2 DOES NOT SHOW TABLE AND
 CHAIR LAYOUT, NOR IS THERE ANY DETAILS SHOWING
 COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE:
 4A-4C)(1) COMPLIED.
  
 4C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK AREAS SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4D) 2ND REQUEST. SEMI-COMPLIED. THE NEW DETAIL 8 ON
 SHEET A-4 SHOWS THE SINK AT 34 INCHES BUT NOT THE
 COUNTERTOP OF THE BOTTOM CABINETS. MUST COMPLY WITH:
 2017 FBC-ACCESSIBILITY CODE. 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1ST ROUND COMMENTS. THERE IS NO DETAIL OF THE EXISTING
 BREAK ROOM BOTTOM CABINETS AND SINK. CODE COMPLIANCE
 CANNOT BE ACHIEVED. THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 202.4.1 DISPROPORTIONATE COST. UP TO 20% OF THE
 CONSTRUCTION COST ($6,000.00) COULD BE REQUIRED TO HAVE
 THE COUNTERTOP AND SINK ACCESSIBLE.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 2017 FBC-ACCESSIBILITY CODE. 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-01 Cont ID  
Sent By jwitmer Date 2019-10-01 Time 13:55 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2019-10-01 13:53:262017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090606
 ADD: 1645 PALM BEACH LAKES BLVD. SUITE: 800
 CONT: NIXON HOME IMPROVEMENTS
 TEL: 561-305-8215
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 01/2019
 ACTION: DENIED
  
 1A) THE COVERSHEET INDICATES THE MINIMUM BUILDING TYPE
 AS CONSTRUCTION TYPE III-B. GOOGLE MAPS SHOWS 1645 PALM
 BEACH LAKES BLVD. AS A 11 STORY HIGH-RISE OFFICE
 BUILDING. PLEASE REVIEW THE 2017 FBC-B TABLE 504.4 AS A
 CONSTRUCTION TYPE I-B CONSTRUCTION. PLEASE CORRECT THE
 PLANS.
  
 1B) PLEASE NOTE UNDER THE HEADING OF CODE RESEARCH THE
 PLANS INDICATE THIS HIGH-RISE IS A NON-SPRINKLERED
 BUILDING. PLEASE CORRECT, THIS HIGHRISE IS FIRE
 SPRINKLERED.
  
 2) IN ONE SET OF PLANS SHEET A-1 IS MARKED UP WITH
 GREEN MAGIC MARKER. ONLY THE REGISTERED ARCHITECT CAN
 APPLY THEIR SEAL & SIGNATURE TO THE FINAL DOCUMENTS
 BEING SUBMITTED TO THE BUILDING DEPARTMENT. NO OTHER
 WORDING OR DETAILS CAN BE ADDED OTHER THAN THE DESIGNER
 OF RECORD. 2017 F. S. 481.2.2.1(2). IT WOULD APPEAR
 DOOR # 1 THE SWING OF THE DOOR MAYBE IS GOING TO BE
 REVISED.
  
 3A) IN BOTH SHEETS A-1 & A-2 THERE IS A HEAVY BLACK
 LINE ENCIRCLING THE PROPOSED WORK AREA, I AM NOT SURE
 WHAT THIS BLACK LINE IS TO INDICATE? THE HEAVY BLACK
 LINE DOES NOT SHOW ON THE WALL SCHEDULE, ADDITIONAL
 INFORMATION IS REQUIRED?
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) SHEETS A-1 & A-2 THE HEAVY BLACK LINE IS NOT IN THE
 SAME LOCATION FOR BOTH SHEETS? 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 OF
 THE ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) THE LIFE SAFETY SHEET A-2 DOES NOT SHOW TABLE AND
 CHAIR LAYOUT, NOR IS THERE ANY DETAILS SHOWING
 COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE:
 4A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4C) )(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4D) THERE IS NO DETAIL OF THE EXISTING BREAK ROOM
 BOTTOM CABINETS AND SINK. CODE COMPLIANCE CANNOT BE
 ACHIEVED. THE 2017 FBC-ACCESSIBILITY CODE SECTION
 202.4.1 DISPROPORTIONATE COST. UP TO 20% OF THE
 CONSTRUCTION COST ($6,000.00) COULD BE REQUIRED TO HAVE
 THE COUNTERTOP AND SINK ACCESSIBLE.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 2017 FBC-ACCESSIBILITY CODE. 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-22 Cont ID  
Sent By jpearson Date 2020-01-22 Time 10:56 Rev Time 0.00
Received By jpearson Date 2020-01-22 Time 10:56 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-11 Cont ID  
Sent By jpearson Date 2019-12-11 Time 07:48 Rev Time 0.00
Received By jpearson Date 2019-12-11 Time 07:48 Sent To I
Notes
2019-12-11 07:48:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUSLY APPROVED PLAN WAS VOIDED BY CONTRACTOR.
 NEW SUBMISSION DID NOT INCLUDE ELECTRICAL SHEETS.
 PROVIDE TWO COPIES OF ELECTRICAL PLAN FOR REVIEW,
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-12-11 Cont ID  
Sent By jpearson Date 2019-10-15 Time 14:48 Rev Time 0.00
Received By jpearson Date 2019-10-15 Time 13:01 Sent To I
Notes
2019-12-11 07:46:20CHANGES STATUS BASED ON 2ND REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-14 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-22 Cont ID  
Sent By pleduc Date 2019-11-22 Time   Rev Time 0.00
Received By pleduc Date 2019-11-22 Time 13:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-10-11 Cont ID  
Sent By pleduc Date 2019-10-11 Time   Rev Time 0.00
Received By pleduc Date 2019-10-11 Time 14:07 Sent To  
Notes
2019-10-11 14:20:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CRV - THERE ARE INDICATION OF THE BUILDING HAS
 "NO SPRINKLERED".
  
 THIS IS AN EXISTING HIGH RISE WITH A FULL FIRE
 SPRINKLER SYSTEM. FIRE SPRINKLER PROTECTION IS REQUIRED
 WITHIN THIS PROPOSED
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE ON SHEET A-2.
  
  
  
 3) SHEET A 2 - THE CREATED BREAKROOM IS AN ASSEMBLY
 OCCUPANCY; HOWEVER, NO OCCUPANCY LOAD NO SEATING PLAN
 IS INDICATED.
  
 PLEASE REVIEW AND PROVIDE A PROPOSED SEATING PLAN AND
 OCCUPANCY LOAD.
  
  
  
 4) SHEET A 1 - DOOR 1 IS INDICATED WITHIN THE DOOR
 SCHEDULE HOWEVER, THE HARDWARE AND LOCKING LATCHING IS
 NOT PROVIDED.
  
 THESE DOOR PROVIDE EGRESS TO THE NEW ASSEMBLY AREA AND
 THE HARDWARE SHALL COMPLY WITH NFPA 101, CH 7, MEANS OF
 EGRESS AND CH 12, NEW ASSEMBLY OCCUPANCIES.
  
 PLEASE REVIEW AND PROVIDE COMPLIANT HARDWARE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-03-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-10 Time 13:33 Sent To  
Notes
2020-03-11 13:33:15RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-01-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-08 Time 14:13 Sent To  
Notes
2020-01-09 14:13:44B08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By jpearson Date 2019-12-11 Time 07:46 Rev Time 0.00
Received By lmarchan Date 2019-11-20 Time 11:37 Sent To  
Notes
2019-11-21 11:37:40B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-24 Time 15:06 Sent To  
Notes
2019-09-24 15:07:01B03