Plan Review Details - Permit 19090553
Plan Review Stops For Permit 19090553
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-10-01 Cont ID  
Sent By jwitmer Date 2019-10-01 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 13:34 Sent To  
Notes
2019-10-01 07:02:05BUILT IN 2006. NO ASBESTOS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-15 Cont ID  
Sent By jwitmer Date 2019-11-15 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2019-11-15 Time 05:55 Sent To  
Notes
2019-11-15 06:31:51SEE PROVISO ON PLANS, PAGE 3.
  
 DATE: 11/15/2019
 BUILDING PROVISO:
 BATHROOM WALLS AT TUB SHALL COMPLY WITH THE 2017 FBC-B
 SECTION:
 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS
 AND WALL AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS
 LISTED IN TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 THE
 MANUFACTURER?S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING
 BOARD SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND
 THE MANUFACTURER?S RECOMMENDATIONS. REGULAR GYPSUM
 WALLBOARD IS
 PERMITTED UNDER TILE OR WALL PANELS IN OTHER WALL AND
 CEILING AREAS
 WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-01 Cont ID  
Sent By jwitmer Date 2019-10-01 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 13:34 Sent To  
Notes
2019-10-01 07:07:022017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090553
 ADD: 801 S OLIVE AVE SUITE: 1407
 CONT: FAIRBANKS CONSTRUCTION
 TEL: 352-732-8600X 702
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 01/2019
 ACTION: DENIED
  
 1) SUBMITTED PLANS ARE NOT DRAFTSMAN QUALITY. W 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
 2) PLANS DRAWN BY THE CONTRACTOR MUST COMPLY WITH
 CERTIFICATION BY CONTRACTOR. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR.
  
 3) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE
 SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED 2017
 FBC-B TABLES 504.3, 504.4 & 506.2.
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 WALL ELEVATIONS/ SECTIONS/ MATERIALS
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 08:35 Rev Time 0.00
Received By jleahy Date 2019-11-18 Time 08:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By jleahy Date 2019-10-03 Time 15:13 Rev Time 0.00
Received By jleahy Date 2019-10-03 Time 15:13 Sent To  
Notes
2019-10-03 15:14:27NEED TO SHOW LOCATION OF ELECTRICAL OUTLET ON PLANS
 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-09-20 Cont ID  
Sent By pleduc Date 2019-09-20 Time   Rev Time 0.00
Received By pleduc Date 2019-09-20 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-12 Cont ID  
Sent By jesmith Date 2019-12-12 Time 14:56 Rev Time 0.00
Received By jesmith Date 2019-12-09 Time 15:37 Sent To  
Notes
2019-12-10 15:37:11RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-18 Cont ID  
Sent By jleahy Date 2019-11-18 Time 08:36 Rev Time 0.00
Received By jleahy Date 2019-10-30 Time 14:43 Sent To  
Notes
2019-10-31 14:43:59B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-03 Cont ID  
Sent By jleahy Date 2019-10-03 Time 15:14 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 09:20 Sent To  
Notes
2019-09-18 09:21:01B05

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-12-12 Cont ID  
Sent By jesmith Date 2019-12-12 Time 14:37 Rev Time 0.00
Received By jesmith Date 2019-12-12 Time 14:36 Sent To  
Notes
2019-12-12 14:53:45PLUMBING COMMENTS: APPROVED W/PROVISO
 SEE PLAN SHEET 4
 A. PROVIDE ACCESSIBLE SHUT OFF VALVES FOR THE TUB PER
 FBC PL 606.2 AND 606.3
 B. REPLACE EXISTING WATER HEATER WITH NEW; SEE ATTACHED
 SUBMITTAL
 C. PROVIDE VACUUM BREAKER FOR HAND HELD SHOWER;
 D. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS DEFERRED SUBMITTALS THE FOLLOWING ITEMS INCLUDED
 WITH THE K-156-LCP BELAY WALK IN TUB: 1) N/A; 2) K-368
 HAND SHOWER HOLDER; 3) K-438-K BATH VALVE WITH
 DIVERTER. THE DOCUMENTS SHALL BE SUBMITTED, APPROVED
 AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR
 OWN RISK.
 E. PROVIDE EXPANSION TANK AT WATER HEATER
  
2019-12-12 14:37:22PLUMBING COMMENTS: APPROVED W/PROVISO
 SEE PLAN SHEET 4
 1. PROVIDE ACCESSIBLE SHUT OFF VALVES FOR THE TUB PER
 FBC PL 606.2 AND 606.3
 2. REPLACE EXISTING WATER HEATER WITH NEW; SEE ATTACHED
 SUBMITTAL
 3. PROVIDE VACUUM BREAKER FOR HAND HELD SHOWER;
 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS DEFERRED SUBMITTALS THE FOLLOWING ITEMS INCLUDED
 WITH THE K-156-LCP BELAY WALK IN TUB: 1) MANUFACTURER?S
 SPEC FOR THE KOHLER 1283230 THERMOSTATIC MIXING VALVE
 (FBC PL 424.5); 2) K-368 HAND SHOWER HOLDER; 3) K-438-K
 BATH VALVE WITH DIVERTER. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-14 Cont ID  
Sent By jesmith Date 2019-11-14 Time 13:11 Rev Time 0.00
Received By jesmith Date 2019-11-14 Time 08:05 Sent To  
Notes
2019-11-14 13:11:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLEASE NOTE THAT I HAVE TRIED TO REACH OUT TO THE
 BUILDER AND THE PLUMBER FOR CLARIFICATIONS AND HAVE NOT
 BEEN ABLE TO GET RESPONSE.
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLEASE NOTE THAT I HAVE TRIED TO REACH OUT TO THE
 BUILDER AND THE PLUMBER FOR CLARIFICATIONS AND HAVE NOT
 BEEN ABLE TO GET RESPONSE.
  
 1. SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE
 MANUFACTURER SPECIFICATION FOR TUB VALVE. ADDITIONALLY,
 PLEASE PROVIDE THE MANUFACTURER?S TECHNICAL
 SPECIFICATION/CUT SHEETS WITH MODEL NUMBER SELECTED
 (THERE ARE TWO SEPARATE MODEL NUMBERS LISTED ON TWO
 SEPARATE PAGES), SHOWING ALL TRIM, ROUGH-IN, INTERNAL
 PIPING, TRIM, ELECTRICAL CHARACTERISTICS, PUMP,
 MECHANICAL BOOSTER HEATER, AND ACCESS PANEL; IN-LINE
 HEATER AS WELL AS OTHER PERTINENT OPTIONS NOTED ON THE
 FAIRBANKS CUSTOMER INFORMATION SHEET. INCLUDE VACUUM
 BREAKER FOR HAND HELD SHOWER (FBC PL 424.2).
 2. PER WPB FBC 107.2.1, DESIGNATE ONE OF THE PLAN
 SHEETS SUBMITTED AS A PLUMBING INFORMATION PLAN. NOTE
 ON THE PLAN ACCESSIBLE SEPARATE SHUT OFF VALVES FOR THE
 TUB (FBC PL 606.2 AND 606.3).
 3. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER
 SPECIFICATION FOR NEW WATER HEATER AND VERIFY THAT THIS
 IS A REPLACEMENT OF THE EXISTING WATER HEATER WITH THE
 SAME FOOTPRINT AS THE ORIGINAL. NOTE TO REFLECT THAT ON
 THE PLAN SHEET SUBMITTED AS A PLUMBING INFORMATION
 PLAN.
 4. THE SUBMITTAL FOR THE REQUIRED TEMPERATURE LIMITING
 DEVICE (FBC PL 424.5) IS SOMEWHAT ILLEGIBLE AND IS
 CONVOLUTED. PER WPB FBC 107.2.1, PROVIDE CLEAN AND
 LEGIBLE CUT SHEET(S).
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
 19090553 801 S OLIVE AVE 1407
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-10-02 Cont ID  
Sent By gjohnson Date 2019-10-02 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2019-09-27 Time 15:47 Sent To  
Notes
2019-10-02 10:34:251ST REVIEW: 19090553
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATIONS FOR TUB VALVE.
 PER WPB AMEND TO FBC 107.2.1 SHALL COMPLY WITH NSF 372
 + 61
 2. SHUT OFF VALVES FOR THE TUB SHALL REMAIN ACCESSIBLE.
 PER FBC PL 606.2, 606.3
 3. A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO
 ASSE 1070 OR CSA B125.3,IS REQUIRED ON THE TUB VALVE.
 PER FBC PL 424.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]