Plan Review Details - Permit 19090493
Plan Review Stops For Permit 19090493
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-09 Cont ID  
Sent By jgomez Date 2020-04-09 Time 12:03 Rev Time 0.00
Received By jgomez Date 2020-04-09 Time 12:03 Sent To  
Notes
2020-04-09 12:36:53BUILDING REVIEW APPROVED WITH PROVISO:
 1)PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ALL WINDOWS SPECIFIED ON PLANS.
 B) ALL EXTERIOR DOORS SPECIFIED ON PLANS.
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 D)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 E)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2)DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.
  
 3) AIR CONDITIONED GARAGE: PROVIDE
 DETAILS/SPECIFICATIONS FOR THE SEALING OF THE 3 GARAGE
 DOORS AS REQUIRED BY SEC. R402.4.4.1.1 FBC-ENERGY
 CONSERVATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-27 Time 12:34 Rev Time 0.00
Received By jgomez Date 2020-03-27 Time 10:17 Sent To  
Notes
2020-03-27 12:36:13BUILDING REVIEW APPROVED WITH PROVISO:
 1)PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ALL WINDOWS SPECIFIED ON PLANS.
 B) ALL EXTERIOR DOORS SPECIFIED ON PLANS.
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 D)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 E)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2)DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.
  
 3) AIR CONDITIONED GARAGE: PROVIDE
 DETAILS/SPECIFICATIONS FOR THE SEALING OF THE 3 GARAGE
 DOORS AS REQUIRED BY SEC. R402.4.4.1.1 FBC-ENERGY
 CONSERVATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jgomez Date 2020-03-12 Time 11:38 Rev Time 0.00
Received By jgomez Date 2020-03-12 Time 10:38 Sent To  
Notes
2020-03-11 13:58:03RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 ORIGINAL COMMENT:
 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE THE
 DESIGN CRITERIA SHOWN ON SHEET A-3 AT THE BOTTOM LEFT
 OF THE PAGE. REVISE THE BUILDING EXPOSURE AND ALL THE
 DESIGN WIND PRESSURES ACCORDINGLY.
  
 RESPONSE:
 THE BUILDING EXPOSURE WAS REVISED ON SHEET A-3 BUT THE
 DESIGN PRESSURES WERE NOT REVISED. THE SAME DESIGN
 PRESSURES FROM PREVIOUS REVIEW WERE SPECIFIED.
 ARCHITECT STATES THAT DOORS & WINDOWS DESIGN PRESSURES
 ARE FOR WORST CASE. USING TABLE R301.2(2)
 FBC-RESIDENTIAL AS A REFERENCE, THE DESIGN PRESSURES
 FOR WALL OPENINGS ARE LOW. WORST CASE WOULD BE THE
 MINIMUM EFFECTIVE AREA OF 10PSF, AT THE MEAN ROOF
 HEIGHT OF 25 FEET, AT THE END ZONE (#5) AND BUILDING
 EXPOSURE "D". SEE TABLE R301.2(3) FBC-RESIDENTIAL FOR
 PROPER ADJUSTMENTS.
 REVISE DOORS AND WINDOWS DESIGN PRESSURES OR PROVIDE
 CALCULATIONS FOR EACH OPENING. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- SPECIFY CARBON MONOXIDE ALARMS BY THE BEDROOMS AS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY COMPLIED. SMOKE ALARM WITH CARBON MONOXIDE
 COMBO ALARM WAS SPECIFIED FOR THE BEDROOM IN THE SECOND
 FLOOR ADDITION. NEED TO SPECIFY THE CARBON MONOXIDE
 ALARM FOR ALL EXISTING BEDROOMS ALSO.
  
 3- OK
 4- OK
  
 ORIGINAL COMMENT:
 5- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT (2 COPIES) FOR THE ICYNENE R-30
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE
  
 RESPONSE:
 A) ARCHITECT'S RESPONSE LETTER STATES THAT THE
 INSULATION WILL BE R-20 BUT SPECIFICATION ON SHEET A-4
 WERE REVISED TO R-13. CLARIFY WHAT IS THE CORRECT R
 VALUE. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ICC EVALUATION REPORT SUBMITTED IS OLD. ESR-3199
 REPORT SUBMITTED WAS SUPPOSED TO BE RENEWED ON 04/2017.
 SEE UPPER RIGHT CORNER OF REPORT SUBMITTED. PROVIDE
 COPIES OF CURRENT REPORT.
 NOTE: ARCHITECT, PLEASE STAMP THE FRONT PAGE OF THE
 REPORT NOT THE BACK OF THE PAGE. THIS WILL FACILITATE
 PROPER SCANNING FOR RECORDS RETENTION. THANKS IN
 ADVANCE FOR YOUR COOPERATION.
  
 6- OK
 7- OK
  
 ORIGINAL COMMENT:
 8- ENERGY CALCULATIONS SUBMITTED:
 REVISE ENERGY CALCULATIONS TO MATCH PLANS. (A)ACCORDING
 TO PLANS SUBMITTED THERE IS NOT KITCHEN IN THE
 ADDITION. (B) REVISE CEILING R-VALUE TO MATCH PLANS.
 PROVIDE THE NAME OF THE BUILDER. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ENERGY CALCULATIONS WERE
 NOT REVISED.
  
 ORIGINAL COMMENT:
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ARCHITECT'S RESPONSE
 LETTER STATES "SEE REVISED DRAWING S-2". THERE IS NOT
 INFORMATION ON SHEET S-2 REGARDING THE FASTENING OF THE
 ROOF TILE. PRODUCT APPROVALS WERE NOT SUBMITTED YET.
 THEY WILL BE SUBMITTED LATER AS A DEFERRED SUBMITTAL.
 THERE IS NO INDICATION OF HOW THE ROOF TILES ARE GOING
 TO BE FASTENED. IN ORDER TO GO FORWARD WITH THIS ITEM,
 THIS WILL BE TAKEN CARE OF WHEN PRODUCT APPROVALS ARE
 SUBMITTED.
 NOTE: PRODUCT APPROVALS WILL NEED TO BE MARKED WITH THE
 SPECIFIC FASTENING METHOD AND REVIEWED/APPROVED BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
  
  
 10-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ALL WINDOWS SPECIFIED ON PLANS.
 B) ALL EXTERIOR DOORS SPECIFIED ON PLANS.
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 D)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 E)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By jgomez Date 2019-10-03 Time 18:22 Rev Time 0.00
Received By jgomez Date 2019-10-03 Time 15:52 Sent To  
Notes
2019-10-03 18:23:32RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE THE
 DESIGN CRITERIA SHOWN ON SHEET A-3 AT THE BOTTOM LEFT
 OF THE PAGE. REVISE THE BUILDING EXPOSURE AND ALL THE
 DESIGN WIND PRESSURES ACCORDINGLY.
  
 2- SPECIFY CARBON MONOXIDE ALARMS BY THE BEDROOMS AS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL
  
 3- BASED ON THE EXTERIOR ELEVATIONS PROVIDED IT LOOKS
 LIKE THE SECOND FLOOR WINDOW SILL OF THE OPERABLE
 WINDOWS IS LOCATED LESS THAN 24 INCHES ABOVE THE
 FINISHED FLOOR. NEED TO PROVIDE WINDOW FALL PROTECTION
 AS REQUIRED BY SEC. R312.2 FBC-RESIDENTIAL
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 HANDRAILS SHOWING COMPLIANCE WITH SEC. R311.7.8
 FBC-RESIDENTIAL.
  
 5- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT (2 COPIES) FOR THE ICYNENE R-30
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE
  
 6- REVISE ATTIC ACCESS SIZE SPECIFIED ON THE PARTIAL
 SECOND FLOOR PLAN ON SHEET A-1. SEE SEC. R807
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 7- SHEET S-2:
 A) TRUSS CONNECTORS ARE NOT CLEAR. CONNECTORS SPECIFIED
 ON THE ROOF FRAMING PLAN AND CONNECTORS SPECIFIED ON
 THE CONNECTOR SCHEDULE SHEET DON'T MATCH. SEE GIRDER
 TRUSS TO TIE BEAM CONNECTION. REVISE AS REQUIRED TO
 MATCH AND CLEARLY SPECIFY THE CONNECTOR FOR ALL TRUSS
 GIRDERS. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REVISE PLYWOOD SHEATHING NAILING SCHEDULE ON SHEET
 S-2. ACCORDING TO SEC. R803.2.3.1 FBC-RESIDENTIAL THE
 FASTENER NEED TO BE RING SHANK NAILS. CLEARLY SPECIFY
 RING SHANK NAILS ON THE PLYWOOD SHEATHING NAILING
 SCHEDULE.
  
 8- ENERGY CALCULATIONS SUBMITTED:
 REVISE ENERGY CALCULATIONS TO MATCH PLANS. (A)ACCORDING
 TO PLANS SUBMITTED THERE IS NOT KITCHEN IN THE
 ADDITION. (B) REVISE CEILING R-VALUE TO MATCH PLANS.
 PROVIDE THE NAME OF THE BUILDER. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED.
  
 10-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ALL WINDOWS SPECIFIED ON PLANS.
 B) ALL EXTERIOR DOORS SPECIFIED ON PLANS.
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 D)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 E)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-03-30 Cont ID  
Sent By jpearson Date 2020-03-30 Time 08:42 Rev Time 0.00
Received By jpearson Date 2020-03-30 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-06 Cont ID  
Sent By jpearson Date 2020-03-06 Time 14:50 Rev Time 0.00
Received By jpearson Date 2020-03-06 Time 14:50 Sent To  
Notes
2020-03-06 14:49:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL B AND
 PANEL C, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY IS ADEQUATE. PANEL C IS SHOWN AS BEING FED
 FROM PANEL B, WHICH ACCORDING TO PANEL SCHEDULE ONLY
 HAS A 50 AMP SERVICE. DEMAND FACTORS ARE NOT PERMITTED
 TO BE USED ON FEEDERS LESS THAN 100 AMPS. NEC 215.2,
 220, 408.30; FBC RE E3602.2, E3602.2.1 (NOT PROVIDED.)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-07 Cont ID  
Sent By jpearson Date 2019-10-07 Time 13:30 Rev Time 0.00
Received By jpearson Date 2019-10-07 Time 12:44 Sent To I
Notes
2019-10-07 13:30:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET CS-1 AND E-1STATE THE 2010 NEC AS THE BASIS
 CODE FOR DESIGN, WHICH IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 3. PROVIDE ACCURATE LOAD CALCULATION FOR PANEL B AND
 PANEL C, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY IS ADEQUATE. PANEL C IS SHOWN AS BEING FED
 FROM PANEL B, WHICH ACCORDING TO PANEL SCHEDULE ONLY
 HAS A 50 AMP SERVICE. DEMAND FACTORS ARE NOT PERMITTED
 TO BE USED ON FEEDERS LESS THAN 100 AMPS. NEC 215.2,
 220, 408.30; FBC RE E3602.2, E3602.2.1
 4. PLAN REFERENCES A PANEL GC. WHERE IS THIS PANEL, IT
 IS NOT SHOWN ON PLAN OR RISER DIAGRAM? ALSO, THERE ARE
 2 PANEL B SHOWN IN RISER DIAGRAM. PROVIDE ACCURATE
 RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; WPB FBC
 107.2.1
 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENERS.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.1
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 10. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 11. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. A NOTE FOR AREAS NOT SHOWN ON PLAN
 WILL SUFFICE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-09-26 Cont ID  
Sent By jesmith Date 2019-09-26 Time 15:37 Rev Time 0.00
Received By jesmith Date 2019-09-26 Time 15:35 Sent To  
Notes
2019-09-26 15:37:16GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19090493 6 CLOISTER CIR

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-20 Cont ID  
Sent By jgomez Date 2020-04-20 Time 15:21 Rev Time 0.00
Received By jgomez Date 2020-04-20 Time 15:17 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-03 Cont ID  
Sent By shill Date 2020-04-03 Time 17:07 Rev Time 0.00
Received By shill Date 2020-03-20 Time 15:40 Sent To  
Notes
2020-03-24 15:41:07R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By jgomez Date 2020-03-12 Time 14:07 Rev Time 0.00
Received By jgomez Date 2020-02-12 Time 14:33 Sent To I
Notes
2020-02-13 14:33:33R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-13 Time 14:10 Sent To  
Notes
2019-09-16 14:11:05R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2020-04-20 Cont ID  
Sent By jgomez Date 2020-04-20 Time 15:20 Rev Time 0.00
Received By jgomez Date 2020-04-20 Time 15:17 Sent To  
Notes
2020-04-20 15:21:06NO FEES. MU-2020-012837.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-27 Time 12:37 Rev Time 0.00
Received By jgomez Date 2020-03-27 Time 12:37 Sent To  
Notes
2020-03-27 12:37:32IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 11:33 Rev Time 0.00
Received By jgomez Date 2020-03-11 Time 11:33 Sent To  
Notes
2020-03-11 11:33:38IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By jgomez Date 2019-10-03 Time 18:25 Rev Time 0.00
Received By jgomez Date 2019-10-03 Time 18:25 Sent To  
Notes
2019-10-03 18:25:35IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-04-09 Cont ID  
Sent By ccole Date 2020-04-09 Time 08:26 Rev Time 0.00
Received By ccole Date 2020-04-09 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-03-25 Cont ID  
Sent By ccole Date 2020-03-25 Time 11:21 Rev Time 0.00
Received By ccole Date 2020-03-25 Time 07:55 Sent To  
Notes
2020-03-25 11:27:033RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19090493
 3/25/20
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MANUAL J AC CALCULATIONS ARE BASED ON INCORRECT
 INSIDE AND OUTSIDE DRYBULB TEMPERATURES. PLEASE SEE
 SECTION R302.1 FBC EC, AND
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-02-24 Cont ID  
Sent By ccole Date 2020-02-24 Time 11:12 Rev Time 0.00
Received By ccole Date 2020-02-24 Time 10:43 Sent To  
Notes
2020-02-24 11:20:502ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19090493
 10/3/19
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1, 2 & 5 FROM THE 1ST REVIEW STILL EXIST -
 PLEASE COMPLY.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL S AND J-
 SECTION R403.6.1 FBC EC.
  
 3) ENERGY FORM 405-2017 INDICATES 2079 SF NEW
 CONDITIONED AREA, HOWEVER SHEET A-1 LISTS THE PROPOSED
 NEW AREAS UNDER AIR AT 1297 SF WITH THE FIRST FLOOR
 AREA LISTED AT 188 SF. BASED ON THE PLAN THE ENTIRE
 GARAGE AREA WILL BE CONDITIONED. PLEASE CORRECT THE
 DISCREPANCIES.
  
 5) MP-1: PLEASE NOTE THAT MAKEUP AIR MAY BE REQUIRED
 FOR THE DRYER IN THE CLOSET. PLEASE REVIEW THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS AND CORRECT THE PLAN IF REQUIRED- SEE
 SECTION M1502.1 FBC R.
  
 NEW COMMENTS.
  
 1) SHEET MP-1: SHOW HOW AIR IS BEING RETURNED FROM THE
 MASTER BEDROOM SUITE. INDICATE THE SIZE OF THE GRILL
 AND THE RETURN TRANSFER DUCT- SEE SECTION M1602.3 FBC
 RES.
  
 2) MP-1: SHOW THE SIZE OF THE RETURN DUCT FROM THE
 20X20 GRILL TO THE AIRHANDLER- SECTION M1602.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By ccole Date 2019-10-03 Time 11:33 Rev Time 0.00
Received By ccole Date 2019-10-03 Time 11:04 Sent To  
Notes
2019-10-03 12:11:36 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090493
 10/3/19
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL S AND J-
 SECTION R403.6.1 FBC EC.
  
 2) THERE ARE DISCEPANCIES IN THE PLANS CONCERNING THE
 GARAGE DOOR OPENINGS: A) THE ENERGY EFFICIENCY FORM
 R405-2017 SHOWS WOOD GARAGE DOORS, SHEET A-1 SHOWS THEM
 AS GLASS WINDOWS IN THE SCHEDULE, SHEET A-2 SHOWS THE
 DOOR OPENINGS TO REMAIN U.N.O. PLEASE CORRECT THE PLANS
 AND THE CALCULATIONS.
  
 3) ENERGY FORM 405-2017 INDICATES 2079 SF NEW
 CONDITIONED AREA, HOWEVER SHEET A-1 LISTS THE PROPOSED
 NEW AREAS UNDER AIR AT 1297 SF WITH THE FIRST FLOOR
 AREA LISTED AT 188 SF. BASED ON THE PLAN THE ENTIRE
 GARAGE AREA WILL BE CONDITIONED. PLEASE CORRECT THE
 DISCREPANCIES.
  
 4) MP-1: REFER TO SECTION R403.3.6 FBC EC- THE AIR
 HANDLER SHALL NOT BE INSTALLED IN THE ATTIC ONLY IF THE
 FOLLOWING CONDITIONS ARE MET:
  
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 2 .A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT
 DOWN THE UNIT WHEN THE CONDENSATION DRAIN IS NOT
 WORKING PROPERLY.
  
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
  
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 5) MP-1: PLEASE NOTE THAT MAKEUP AIR MAY BE REQUIRED
 FOR THE DRYER IN THE CLOSET. PLEASE REVIEW THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS AND CORRECT THE PLAN IF REQUIRED- SEE
 SECTION M1502.1 FBC R
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-25 Cont ID  
Sent By ccole Date 2020-03-25 Time 11:18 Rev Time 0.00
Received By ccole Date 2020-03-25 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By jgomez Date 2020-03-11 Time 13:58 Rev Time 0.00
Received By jgomez Date 2020-03-11 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-09-26 Cont ID  
Sent By jesmith Date 2019-09-26 Time 15:15 Rev Time 0.00
Received By jesmith Date 2019-09-26 Time 15:15 Sent To  
Notes
2019-09-26 15:15:23PLUMBING COMMEMTS: APPROVED W/PROVISO
 1. SEE PLAN SHEET MP-1. RED LINED PROVISOS ARE AS
 FOLLOW
 A.SANITARY RISER DIAGRAM: HORIZONTAL FIXTURE BRANCH
 BETWEEN CLOTHES WASHER AND VERTICAL SOIL STACK SHALL BE
 3 INCH DIAMETER PER FBC RES 2601.1 AND FBC PL 406.2.
 B.PER FBC RES 2601.1 AND FBC PL 607.1, PROVIDE HOT
 WATER TO PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE. COMPLY WITH FBC PL SECTION 605
 AND 607.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-27 Time 12:37 Rev Time 0.00
Received By jgomez Date 2020-03-27 Time 12:37 Sent To  
Notes
2020-03-27 12:38:37PROVISO:
  
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 B)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jgomez Date 2020-03-12 Time 14:06 Rev Time 0.00
Received By jgomez Date 2020-03-12 Time 13:59 Sent To  
Notes
2020-03-12 14:06:561-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 B)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By jgomez Date 2019-10-03 Time 18:24 Rev Time 0.00
Received By jgomez Date 2019-10-03 Time 18:23 Sent To  
Notes
2019-10-03 18:24:591-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS)
  
 A)ROOF TILE AND CLEARLY MARK ROOF TILE FASTENING METHOD
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS.
 B)ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-03 Cont ID  
Sent By awooten Date 2020-04-03 Time   Rev Time 0.00
Received By awooten Date 2020-04-03 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-02-20 Cont ID  
Sent By awooten Date 2020-02-20 Time   Rev Time 0.00
Received By awooten Date 2020-02-20 Time   Sent To  
Notes
2020-02-20 14:18:03****************************ZONING REVIEW
 FAILED*************************
  
 PROVIDE THE FRONT SETBACKS ON THE SITE PLAN.
  
 THIS PROPERTY IS ZONED SINGLE FAMILY. ONLY ONE
 RESIDENTIAL UNIT IS ALLOWED, SO THERE CAN ONLY BE ONE
 FULL KITCHEN IN THE EXISTING HOUSE AND ON THE PROPERTY.
 REMOVE THE KITCHEN IN THE ADDITION. YOU CAN HAVE A
 SMALL SINK, AN UNDER COUNTER SMALL REFRIDGERATOR, AND
 MICROWAVE.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-20 Cont ID  
Sent By awooten Date 2019-09-20 Time   Rev Time  
Received By awooten Date 2019-09-20 Time   Sent To  
Notes
2019-09-20 13:51:09**************************************ZONING REVIEW
 FAILED***********************************
  
 PROVIDE A SURVEY OF THE PROPERTY SHOWING ALL EXISTING
 SETBACKS.
  
 DIMENSION THE NEW OVERHANG. STRUCTURAL INTRUSIONS.
 STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED TO
 BALCONIES, CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG
 PROJECTIONS SHALL NOT EXTEND FARTHER THAN THREE FEET
 INTO ANY SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]