Plan Review Details - Permit 19090477
Plan Review Stops For Permit 19090477
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-01-21 Cont ID  
Sent By cthroop Date 2020-01-21 Time 09:05 Rev Time 0.00
Received By cthroop Date 2020-01-21 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-25 Cont ID  
Sent By cthroop Date 2019-10-25 Time 09:59 Rev Time 0.00
Received By cthroop Date 2019-10-21 Time 15:57 Sent To  
Notes
2019-10-25 10:21:45PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 2. PROVIDE 2ND COPY OF WINDOW NOA.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 08:56 Rev Time 0.00
Received By cthroop Date 2019-09-26 Time 15:40 Sent To  
Notes
2019-09-27 09:03:49BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SOW ON PAGE A1 IS TO RENOVATE THE EXISTING KITCHEN
 BY REMOVING AND REPLACING APPLIANCES, CABINETS AND
 COUNTERTOPS.
 2. PLANS SUBMITTED ARE FOR A FULL RES REMODEL INCLUDING
 THE RE-LOCATION OF THE EXTERIOR STAIRS TO THE INTERIOR
 OF THE BUILDING, RE-CONFIGURING INTERIOR SPACE AND THE
 REPLACEMENT OF MECH., ELEC., & PLUMBING SYSTEMS.
 3. APPLCANT SHALL INCREASE SOW TO INCLUDE ALL
 REFERENCED WORK ON PLANS OR REMOVE ANY WORK ON PLANS
 THAT IS NOT INCLUDED IN SOW.
 4. IF SOW IS INCREASED, ADJUST VALUE AND PROVIDE A
 SIGNED COPY OF CONTRACT WITH OWNER.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-07 Cont ID  
Sent By jpearson Date 2020-01-07 Time 15:43 Rev Time 0.00
Received By jpearson Date 2020-01-07 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-31 Cont ID  
Sent By jpearson Date 2019-10-31 Time 09:41 Rev Time 0.00
Received By jpearson Date 2019-10-31 Time 06:37 Sent To  
Notes
2019-10-31 09:35:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PANEL SCHEDULE STATES THAT THE PANEL IS RATED FOR
 125 AMPS. LOAD CALCULATION STATES THE LOAD IS 141 AMPS,
 SO THE PANEL IS NOT RATED FOR THE LOAD. PROVIDE
 CORRECTION. NEC 408.30 (NOT CORRECTED. RISER DIAGRAM
 SHOWS A 125 AMP DISCONNECT WITH #1 WIRE FEEDING PANEL
 A. BASED ON LOAD CALCULATION PROVIDED, THIS DISCONNECT
 AND WIRE WOULD BE OVERLOADED AND IS NOT SIZED PROPERLY.
 PROVIDE CORRECTION.)
 2. CORRECTED.
 3. IS THIS A NEW SERVICE? PROVIDE CLARIFICATION. WPB
 FBC 107.2.1 (NOT CLARIFIED.)
 4. IF SERVICE IS NEW OR BEING REBUILT, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE
 E3606.3 (NOT CLARIFIED, NOT PROVIDED.)
 5. CORRECTED.
 6. CORRECTED.
  
 NEW COMMENT:
  
 7. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS (PANEL A AND PANEL B) TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 13:59 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 07:56 Sent To  
Notes
2019-09-24 13:59:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE STATES THAT THE PANEL IS RATED FOR
 125 AMPS. LOAD CALCULATION STATES THE LOAD IS 141 AMPS,
 SO THE PANEL IS NOT RATED FOR THE LOAD. PROVIDE
 CORRECTION. NEC 408.30
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. IS THIS A NEW SERVICE? PROVIDE CLARIFICATION. WPB
 FBC 107.2.1
 4. IF SERVICE IS NEW OR BEING REBUILT, PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE
 E3606.3
 5. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB
 FBC 107.2.1; NEC 230.2; FBC RE E3601.2
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-21 Cont ID  
Sent By cthroop Date 2020-01-21 Time 09:05 Rev Time 0.00
Received By cthroop Date 2019-12-31 Time 16:22 Sent To  
Notes
2020-01-02 16:23:06R08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-20 Cont ID  
Sent By cpuell Date 2019-11-20 Time 15:02 Rev Time 0.00
Received By cpuell Date 2019-10-08 Time 14:08 Sent To  
Notes
2019-10-09 14:08:15R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 09:03 Rev Time 0.00
Received By cthroop Date 2019-09-13 Time 14:21 Sent To  
Notes
2019-09-16 14:21:24R01

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-01-21 Cont ID  
Sent By cthroop Date 2020-01-21 Time 09:05 Rev Time 0.00
Received By cthroop Date 2020-01-21 Time 08:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By cthroop Date 2019-10-25 Time 09:59 Rev Time 0.00
Received By cthroop Date 2019-10-21 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 08:53 Rev Time 0.00
Received By cthroop Date 2019-09-26 Time 15:40 Sent To  
Notes
2019-09-27 08:54:19MECHANICAL SYSTEM IS NOT PART OF SOW AS STATED ON PLAN
 PAGE A1. IF MECHANICAL SYSTEM WILL BE INCLUDED IN THE
 SOW, INCLUDE IN NARRATIVE ON PG A1 AND ADJUST VALUE
 ACCORDINGLY. PROVIDE A SIGNED COPY OF CONTRACT WITH
 OWNER.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 09:05 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 09:05 Sent To  
Notes
2019-09-27 09:06:27PROPERTY IS LOCATED IN A FLOOD ZONE X. AN ELEVATION
 CERTIFICATE IS NOT REQUIRED. CT

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By gjohnson Date 2019-10-21 Time 11:34 Rev Time 0.00
Received By gjohnson Date 2019-10-18 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-20 Cont ID  
Sent By tklarge Date 2019-09-20 Time 11:05 Rev Time 0.00
Received By tklarge Date 2019-09-20 Time 10:13 Sent To  
Notes
2019-09-20 11:04:361) THE ENERGY CALCULATIONS SHOW THE EF OF THE WATER
 HEATER AS .92. AS OF 4/16/2015, THE MINIMUM EF OF WATER
 HEATERS SHALL BE .96 PER 10 CFR SEC.430.32.
 2) THE SUBMITTED SANITARY RISER SHOWS NO FIXTURES. SHOW
 PROPOSED CHANGES TO THE SANITARY SYSTEM ON THE SANITARY
 RISER DIAGRAM. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE PLANS SHOW A STACKED WASHER AND DRYER. THE WATER
 SUPPLY VALVES FOR THE WASHER SHALL BE ACCESSIBLE PER
 2017 FBC-PLUMBING SEC.606.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-11-20 Cont ID  
Sent By awooten Date 2019-11-20 Time   Rev Time 0.00
Received By awooten Date 2019-11-20 Time   Sent To  
Notes
***NONE***