Plan Review Details - Permit 19090383
Plan Review Stops For Permit 19090383
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By shill Date 2019-10-22 Time 17:56 Rev Time 0.00
Received By shill Date 2019-10-22 Time 17:56 Sent To FIRE
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 07:05 Rev Time 0.00
Received By shill Date 2019-09-24 Time 07:05 Sent To  
Notes
2019-09-24 07:05:24PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-11-07 Cont ID  
Sent By dbattles Date 2019-11-07 Time 08:33 Rev Time 0.00
Received By dbattles Date 2019-11-07 Time 08:33 Sent To P
Notes
2019-11-07 08:33:302ND REVIEW 11/7/2019
 COMMENT NOT ADDRESSED AND NO COMMENT RESPONSE SHEET.
 IT LOOKS LIKE HISTIRICAL COMMENTS WERE ADDRESSED, BUT
 BUILDING WAS ASKING FOR EXTERIOR ELEMENTS TO BE REMOVED
 FROM INTERIOR DEMO.
 PLEASE CONTACT ME TO DISCUSS OR RE SUBMIT WITH COMMENT
 ADDRESSED.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  
 1ST REVIEW 9/24/2019
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 105.13, PLANS SHOW AND DESCRIBE REMOVAL OF
 EXTERIOR ELEMENTS. THIS IS NOT ALLOWED ON AN INTERIOR
 DEMO PERMIT. EITHER ADVISE VIA EMAIL THAT YOU WOULD
 LIKE THE PLANS REDLINED TO REMOVE THIS FROM SCOPE OF
 WORK OR PROVIDE ADDITIONAL INFORMATION REQUIRED
 (PRODUCT APPROVALS) AND THIS PERMIT WILL BE CONVERTED
 TO A COMMERCIAL REMODEL PERMIT RATHER THAN AN INTERIOR
 DEMO.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 07:10 Rev Time 0.00
Received By shill Date 2019-09-24 Time 07:10 Sent To  
Notes
2019-09-24 07:12:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 105.13, PLANS SHOW AND DESCRIBE REMOVAL OF
 EXTERIOR ELEMENTS. THIS IS NOT ALLOWED ON AN INTERIOR
 DEMO PERMIT. EITHER ADVISE VIA EMAIL THAT YOU WOULD
 LIKE THE PLANS REDLINED TO REMOVE THIS FROM SCOPE OF
 WORK OR PROVIDE ADDITIONAL INFORMATION REQUIRED
 (PRODUCT APPROVALS) AND THIS PERMIT WILL BE CONVERTED
 TO A COMMERCIAL REMODEL PERMIT RATHER THAN AN INTERIOR
 DEMO.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-12 Cont ID  
Sent By jpearson Date 2019-11-12 Time 08:42 Rev Time 0.00
Received By jpearson Date 2019-11-12 Time 08:42 Sent To  
Notes
2019-11-12 08:41:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By jpearson Date 2019-09-24 Time 07:39 Rev Time 0.00
Received By jpearson Date 2019-09-24 Time 07:39 Sent To FIRE
Notes
2019-09-24 07:39:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By pleduc Date 2019-10-23 Time   Rev Time 0.00
Received By pleduc Date 2019-10-23 Time 14:07 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-09-24 Cont ID  
Sent By pleduc Date 2019-09-24 Time   Rev Time 0.00
Received By pleduc Date 2019-09-24 Time 11:23 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By fmittner Date 2019-10-21 Time 15:26 Rev Time 0.00
Received By fmittner Date 2019-10-21 Time 15:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 13:20 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 13:20 Sent To  
Notes
2019-10-03 13:22:33PROPERTY IN HSITORIC DISTRICT. RECESSED ENTRY TO
 REMAIN. NEW DRAWINGS DO NOT MEET DESIGN GUIDELINES.
 OTHER INTERIOR DEMO OK. QUESTIONS CONTACT: FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT (561)
 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-11 Time 13:39 Sent To  
Notes
2019-10-15 13:39:45RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-10-03 Cont ID  
Sent By cpuell Date 2019-10-03 Time 16:33 Rev Time 0.00
Received By cpuell Date 2019-09-12 Time 14:09 Sent To  
Notes
2019-09-24 07:13:25TO JP DESK
  
2019-09-13 14:09:50SHILL

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By tklarge Date 2019-11-12 Time 06:28 Rev Time 0.00
Received By tklarge Date 2019-11-12 Time 06:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-10-02 Cont ID  
Sent By tklarge Date 2019-10-02 Time 13:31 Rev Time 0.00
Received By tklarge Date 2019-10-02 Time 13:31 Sent To  
Notes
***NONE***