Plan Review Details - Permit 19090272
Plan Review Stops For Permit 19090272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By pvalenti Date 2020-01-17 Time 11:12 Rev Time 0.00
Received By pvalenti Date 2020-01-17 Time 11:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-11-23 Cont ID  
Sent By pvalenti Date 2019-11-23 Time 12:24 Rev Time 0.00
Received By pvalenti Date 2019-11-23 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-01-21 Cont ID  
Sent By jleahy Date 2020-01-21 Time 13:25 Rev Time 0.00
Received By jleahy Date 2020-01-21 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-15 Cont ID  
Sent By jleahy Date 2020-01-15 Time 11:21 Rev Time 0.00
Received By jleahy Date 2020-01-15 Time 11:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-17 Cont ID  
Sent By jleahy Date 2019-12-17 Time 09:26 Rev Time 0.00
Received By jleahy Date 2019-12-17 Time 09:26 Sent To M
Notes
2019-12-17 09:31:48FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) A SIGNED LETTER FROM THE CONTRACTOR IS NOT
 ACCEPTABLE, SIGNED CONTRACT WITH THE OWNER. WE HAVE
 GEN-COM PERMITS WITH VALUES OF $225,000 TO $400,000
  
 THE VALUE AS STATED BELOW SHALL INCLUDE ALL MATERIALS
 TO COMPLETE THE GENERATOR WORK. WIRE, GENERATOR
 TRANSFER SWITCHES, FUEL TANK ECT. ECT.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-21 Cont ID  
Sent By jleahy Date 2019-11-21 Time 17:09 Rev Time 0.00
Received By jleahy Date 2019-11-21 Time 17:09 Sent To  
Notes
2019-11-21 17:12:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE GENERATOR AND LABOR IS TOO LOW.
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR THE INSTALLATION.
  
 PAGE E-4.0.0
  
 2) ATS. #2 AND #4 CHECK WORKING CLEARANCES FROM 110.26
  
 3) F/P CONTROLLER OCP TO EMERGENCY SYSTEM?? WHAT SIZE??
  
 4) GENERATOR RISER SHOWS NO WIRE SIZES FROM GDP TO
 TRANSFER SWITCHES ECT, ECT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By pleduc Date 2020-01-17 Time   Rev Time 0.00
Received By pleduc Date 2020-01-17 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-10-24 Cont ID  
Sent By J.Walker Date 2019-10-24 Time   Rev Time 0.00
Received By jwalker Date 2019-10-24 Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-21 Cont ID  
Sent By cpuell Date 2020-01-21 Time 13:26 Rev Time  
Received By jleahy Date 2020-01-15 Time 11:25 Sent To  
Notes
2020-01-16 11:25:35B07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-24 Cont ID  
Sent By tklarge Date 2019-12-24 Time 14:43 Rev Time 0.00
Received By tklarge Date 2019-12-10 Time 15:25 Sent To  
Notes
2019-12-11 15:25:51RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-11-23 Cont ID  
Sent By pvalenti Date 2019-11-23 Time 12:24 Rev Time 0.00
Received By pvalenti Date 2019-10-18 Time   Sent To  
Notes
2019-10-21 13:34:38ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-01-17 Cont ID  
Sent By ccole Date 2020-01-17 Time 09:54 Rev Time 0.00
Received By ccole Date 2020-01-17 Time 08:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-17 Cont ID  
Sent By ccole Date 2019-12-17 Time 17:48 Rev Time 0.00
Received By ccole Date 2019-12-17 Time 14:52 Sent To P
Notes
2019-12-17 17:50:572ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19090272
 12/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODEWPB- WEST PALM BEACH
 AMENDMENTS TO THE FBC SIXTH EDITION 2017
 NFPA 110- 2018
 NFPA 37- 2018
 NFPA 30- 2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE PLANS ARE NOT VALID FOR REVIEW BECAUSE THEY HAVE
 COPIED ELECTRONIC SEALS AND SIGNATURES. PLEASE PROVIDE
 ORIGINAL RAISED OR INK SEALS AND SIGNATURES- SECTION
 471.025 AND SECTION 61G15.23002 FAC.
  
 PLEASE NOTE THAT THE INSTALLATION IOF THE 660 GALLON
 FUEL TANK REQUIRES APPROVAL BY PALM BEACH COUNTY
 DEPARTMENT OF ENVIRONMENTAL RESOURCES.
  
 COMMENTS BELOW FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS OK OR NOT COMPLIED.
  
 1) OK. NOTE- SHEETS SP1.03 & M1.2.1 REQUIRE ORIGINAL
 SIGNATURES AND SEALS BY THE DESIGN PROFESSIONALS.
  
 2) OK
  
 3) OK
  
 4) NOT COMPLIED. SUBMIT THE SPECS FOR THE ENGINE
 EXHAUST PIPE- SECTION 8.1.1 NFPA 37.
  
 A) INDICATE THE DIAMETER OF THE EXHAUST PIPE AND THE
 TOTAL RUN LENGTH OF THE PIPE ON SHEET M1.2.1A.
  
 B) PROVIDE THE CLEARANCE DISTANCES FROM THE EXHAUST
 PIPE DISCHARGE TO GRADE AND TO THE PROPERTY LINE-
 SECTION 501.3.1(2) FBC M.
  
 C) PROVIDE BACKPRESSURE CALCULATIONS FOR THE EXHAUST
 PIPING AND SILENCER, AND VERIFY THE BACKPRESSURE DOES
 NOT EXCEED THE MAXIMUM 10 KPA ALLOWABLE BACKPRESSURE
 PER THE GENERATOR MANUFACTURER.
  
 IN RESPONSE TO COMMENT #4 THE AOR HAS PROVIDED NOTES IN
 HIS RESPONSE LETTER TO ADDRESS THE COMMENTS, BUT NO
 INFORMATION HAS BEEN PROVIDED ON PLAN SHEET M1.2.1.A.
  
 5) OK
  
 6) OK
  
 7) NOT COMPLIED. SHEET M.1.2.1A: THE RADIATOR EXHAUST
 AIR DISCHARGE SHALL BE DUCTED OUTDOORS OR TO AN
 EXTERIOR OPENING BY A 2-HOUR FIRE-RATED TRANSFER
 SYSTEM- SECTION 7.7.4.2 NFPA 110. PLEASE NOTE THAT THE
 SOUNDLINED DISHARGE PLENUM IS NOT A 2-HOUR FIRE-RATED
 TRANSFER SYSTEM PER THE SUBMITTED DRAWINGS.
  
 8) NOT COMPLIED. REFER TO SECTION 7.7.1 NFPA 110- 2016
 AND VERIFY THAT THE VENTILATION AIRFLOW IN THE
 GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE
 MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR
 MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE
 HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER,
 EXHAUST PIPES,
 AND ALL OTHER HEAT PRODUCING EQUIPMENT- SECTION
 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND
 VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE
 PROVISIONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY,
 LOUVERS, ETC.- SECTION 7.7.7.
  
 9) NOT COMPLIED. M1.2.1A: GENERATOR/FUEL TANK ROOM
 EXHAUST SYSTEM:
  
 A) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 GENERATOR/TANK (EPS) ROOM, AND PROVIDE AN EQUIPMENT
 SCHEDULE FOR EF-2- SECTION 502.4.2 FBC M.
  
 B) THE EF-2 EXHAUST DUCT SHALL RUN INDEPENDENTLY, AND
 SHALL BE ENCLOSED IN 2-HR FIRE-RATED CONSTRUCTION FROM
 THE PENETRATION OF THE WALL TO THE EXHAUST OUTLET-
 SECTIONS 501.3, 510.2, 510.6.7
  
 C) INDICATE THE TYPE AND GAGE OF THE EXHAUST DUCTWORK-
 SECTION 510.9 FBC M.
  
 D) PLEASE NOTE THAT EXHAUST SYSTEM SHALL RUN
 CONTINUOUSLY- SECTIONS 4.1.2.1.3 & 6.3.6.5.1 NFPA 37,
 AND SECTION 502.4.2 FBC.
  
 DEFINITION OF ENVIRONMENTAL AIR DOES NOT INCLUDE
 EXHAUST FROM A GENERATOR/FUEL TANK ROOM. PLEASE REFER
 TO SECTION 510.2 FBC M, SECTION 6.3.6.5.1 NFPA 37, AND
 SECTION 24.10.1 NFPA 30.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By ccole Date 2019-11-04 Time 14:10 Rev Time 0.00
Received By ccole Date 2019-11-04 Time 07:31 Sent To E
Notes
2019-11-04 15:01:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090272
 11/4/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODEWPB- WEST PALM BEACH
 AMENDMENTS TO THE FBC SIXTH EDITION 2017
 NFPA 110- 2018
 NFPA 37- 2018
 NFPA 30- 2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS SP1.0.3 & M1.2.1A: THE SITE PLAN INDICATES BY
 SCALE THAT THE THE EXHAUST PIPE DISCHARGE AND THE
 GENERATOR EXHAUST OUTLET ARE WITHIN THE REQUIRED 10'
 CLEARANCE TO THE PROPERTY LINE. PLEASE REFER TO THE
 MAIN BUILDING PLANS APPROVED UNDER PERMIT #17110075.
 THERE ARE NOTES ON THE GROUND FLOOR MECHANICAL PLANS
 INDICATING ALL OUTSIDE AIR INTAKES AND EXHAUST OUTLETS
 SHALL MEET THE REQUIRED CLEARANCE DISTANCES. IT APPEARS
 THAT MANY AIR INLETS AND EXHAUST OUTLETS WILL BE
 LOCATED TOO CLOSE TO THE PROPERTY LINE.
  
 2) SUBMIT THE SPECS FOR THE FUEL TANK- SECTION 107.2.1
 WPB & SECTION 21.4.2.1.1 NFPA 30. SECTION 8.1.1 NFPA
 37. INDICATE THE DIAMETER OF THE EXHAUST PIPE ON SHEET
 M1.2.1A.
  
 3) SUBMIT THE UL 2200 CERTIFICATE FOR THE GENERATOR-
 SECTION 915.1 FBC M.
  
 4) SUBMIT THE SPECS FOR THE ENGINE EXHAUST PIPE-
 SECTION 8.1.1 NFPA 37.
 A) INDICATE THE DIAMETER OF THE EXHAUST PIPE AND THE
 TOTAL RUN LENGTH OF THE PIPE ON SHEET M1.2.1A.
 B) PROVIDE THE CLEARANCE DISTANCES FROM THE EXHAUST
 PIPE DISCHARGE TO GRADE AND TO THE PROPERTY LINE-
 SECTION 501.3.1(2) FBC M.
 C) PROVIDE BACKPRESSURE CALCULATIONS FOR THE EXHAUST
 PIPING AND SILENCER, AND VERIFY THE BACKPRESSURE DOES
 NOT EXCEED THE MAXIMUM 10 KPA ALLOWABLE BACKPRESSURE
 PER THE GENERATOR MAHNUFACTURER.
  
 5) THE SUBMITTED EPA CERTIFICATE FOR THE GENERATOR
 EMISSIONS EXPIRED ON 12/31/18. PLEASE PROVIDE AN
 UPDATED CERTIFICATE- SECTION 107.2.1 WPB.
  
 6) THE SPECS FOR THE SOUNDLINING INDICATE NOT
 RECOMMENDED FOR EQUIPMENT WITH OPERATING TEMPERATURES
 GREATER THAN 250 DEGREES F, HOWEVER THE GENERATOR SPECS
 SHOW THE EXHAUST TEMPERATURE AT 975 DEGREES F.
  
 7) SHEET M.1.2.1A: THE RADIATOR EXHAUST AIR DISCHARGE
 SHALL BE DUCTED OUTDOORS OR TO AN EXTERIOR OPENING BY A
 2-HOUR FIRE-RATED TRANSFER SYSTEM- SECTION 7.7.4.2 NFPA
 110.
  
 8) REFER TO SECTION 7.7.1 NFPA 110- 2016 AND VERIFY
 THAT THE VENTILATION AIRFLOW IN THE GENERATOR/TANK
 (EPS) ROOM IS DESIGNED TO LIMIT THE MAXIMUM AIR
 TEMPERATURE IN THE ROOM TO THE MAXIMUM AMBIENT AIR
 TEMPERATURE REQUIRED BY THE GENERATOR MANUFACTURER.
 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT EMITTED TO
 THE ROOM BY THE ENERGY CONVERTER, EXHAUST PIPES, AND
 ALL OTHER HEAT PRODUCING EQUIPMENT- SECTION 7.7.1.1.
 DESIGN OF THE HEATING, COOLING, AND VENTILATION SYSTEM
 SHALL AMONG OTHER THINGS, INCLUDE PROVISONS FOR FACTORS
 SUCH AS HEAT, COLD, HUMIDITY, LOUVERS, ETC.- SECTION
 7.7.7.
  
 9) M1.2.1A: GENERATOR/FUEL TANK ROOM EXHAUST SYSTEM:
 A) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 GENERATOR/TANK (EPS) ROOM, AND PROVIDE AN EQUIPMENT
 SCHEDULE FOR EF-2- SECTION 502.4.2 FBC M.
 B) THE EF-2 EXHAUST DUCT SHALL RUN INDEPENDENTLY, AND
 SHALL BE ENCLOSED IN 2-HR FIRE-RATED CONSTUCTION FROM
 THE PENETRATION OF THE WALL TO THE EXHAUST OUTLET-
 SECTIONS 501.3, 510.2, 510.6.7
 C) INDICATE THE TYPE AND GAGE OF THE EXHAUST DUCTWORK-
 SECTION 510.9 FBC M.
 D) PLEASE NOTE THAT EXHAUST SYSTEM SHALL RUN
 CONTINOUSLY- SECTIONS 4.1.2.1.3 & 6.3.6.5.1 NFPA 37,
 AND SECTION 502.4.2 FBC.
  
 10) SHOW THE LOCATION OF THE REMOTE FILL PIPING
 STATION, AND SHOW THE FUEL PIPING RUN TO THE TANK-
 SECTION 1305.6 FBC M & SECTION 6.6.3.3 NFPA 37. A)
 INDCATE THE TYPE AND SIZE OF PIPING- SECTION 1302 FBC
 M.
  
 11) SHOW THE FUEL TANK VENT PIPING RUN AND TERMINATION
 LOCATION- SECTION 1305.7 FBC M & SECTION 6.7.1.1 NFPA
 37.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By tklarge Date 2020-01-17 Time 10:35 Rev Time 0.00
Received By tklarge Date 2020-01-17 Time 10:35 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-12-24 Cont ID  
Sent By tklarge Date 2019-12-24 Time 14:42 Rev Time 0.00
Received By tklarge Date 2019-12-23 Time 06:31 Sent To I
Notes
2019-12-24 06:48:31 
 1) THE PLANS ARE UNACCEPTABLE AS THEY BEAR COPIED
 DIGITAL SEALS AND SIGNATURES. PLEASE PROVIDE ORIGINAL
 RAISED OR INK SEALS AND SIGNATURES PER FL. ADMIN. CODE
 RULE 61G15-23.001 OR SUBMIT THE PLANS ELECTRONICALLY
 PER FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.006,
 FL. STATUTE 471.025.
 2) THE INSTALLATION OF THE 660 GALLON FUEL TANK
 REQUIRES APPROVAL FROM THE PALM BEACH COUNTY DEPARTMENT
 OF ENVIRONMENTAL RESOURCE MANAGEMENT. SUBMIT TWO COPIES
 OF THE APPROVAL FROM THE DEPARTMENT. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
  