| 2019-09-13 16:05:39 | 09/13/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE |
| | ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE |
| | SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED |
| | ON THE RESUBMITTAL REVIEW. |
| | |
| | 1. PLAN ARE TO SMALL TO READ NOTES, PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE PER THE WPB AMENDMENT |
| | TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING PLANS. |
| | 2. PLEASE SHOW THE LOCATION OF RAIN SENSOR AND TIME |
| | CLOCK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 3. THE PLANS INDICATE ON THE IRRIGATION NOTES THAT |
| | THERE IS RECLAIMED WATER AND A BACKFLOW PREVENTER FOR |
| | THAT SOURCE. PLEASE CLARIFY IF WATER IS COMING FROM |
| | RECLAIM AND GIVE LOCATION OF CONNECTION. IF USING THE |
| | CITY WATER A BACKFLOW DEVICE LIKE AN RPZ IS REQUIRED AT |
| | METER AND SEPARATE PERMIT FOR BACKFLOW DEVICE FROM A |
| | LICENSED CONTRACTOR, CERTIFICATION OF THE BACKFLOW IS |
| | ALSO REQUIRED AND IF IT IS AN ISOLATION DEVICE THE |
| | CERTIFICATION IS DONE BY CONTRACTOR AND IF IT IS |
| | CONTAINMENT IT WILL NEED TO BE DONE BY THE CITY OF WEST |
| | PALM BEACH UTILITIES DEPARTMENT. TO MAKE SURE THAT |
| | THERE IS NO CROSS CONNECTION PLEASE REFER TO THE CITY |
| | OF WEST PALM BEACH CROSS CONNECTION MANUAL OR CALL |
| | 561-822-2240 FOR MORE INFORMATION. |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |