Plan Review Details - Permit 19090103
Plan Review Stops For Permit 19090103
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By shill Date 2019-09-18 Time 11:51 Rev Time 0.00
Received By shill Date 2019-09-18 Time 11:51 Sent To  
Notes
2019-09-18 11:51:44CONTRACTOR ACKNOWLEDGMENT RECEIVED; ROUTED TO RECORDS
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By pvalenti Date 2019-09-10 Time 13:00 Rev Time 0.00
Received By pvalenti Date 2019-09-10 Time 13:00 Sent To  
Notes
2019-09-10 13:02:01ASBESTOS COMMENTS:
  
 FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By pvalenti Date 2019-10-01 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2019-10-01 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By pvalenti Date 2019-09-10 Time 13:09 Rev Time 0.00
Received By pvalenti Date 2019-09-10 Time 13:02 Sent To  
Notes
2019-09-10 13:09:09***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1. PROVIDE DETAILS ON DRYWALL REPLACEMENT INCLUDING
 THICKNESS, FASTENER SPACING, AND MAINTAINING FIRE
 RATING AT TENANT AND OR CORRIDOR SEPERATION WALLS.
 2. PROVIDE FLAME SPREAD SPECIFICATIONS FOR NEW
 FLOORING.
 3. PROVIDE DETAILS FOR CEILING TILE REPLACEMENT
 INCLUDING FASTENING AND SUPPORTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-01 Cont ID  
Sent By pvalenti Date 2019-10-01 Time 16:33 Rev Time 0.00
Received By pvalenti Date 2019-09-20 Time 14:14 Sent To  
Notes
2019-09-23 14:15:01RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-10 Cont ID  
Sent By pvalenti Date 2019-09-10 Time 13:09 Rev Time 0.00
Received By pvalenti Date 2019-09-06 Time 10:11 Sent To B
Notes
***NONE***