Plan Review Details - Permit 19090077
Plan Review Stops For Permit 19090077
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-10 Cont ID  
Sent By jbrooks Date 2019-10-10 Time 09:47 Rev Time 0.00
Received By jbrooks Date 2019-10-10 Time 09:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By jbrooks Date 2019-09-12 Time 13:12 Rev Time 0.00
Received By jbrooks Date 2019-09-12 Time 13:11 Sent To P
Notes
2019-09-12 13:12:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 2. FBC EB 504.1. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
 3.FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS DESCRIBED
 IN SECTION 504 SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 8. IN ADDITION TO THE REQUIREMENTS OF THIS
 CHAPTER, ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 7. PROVIDE FLOOR PLAN OF EXISTING RESIDENCE
 SHOWING COMPLIANCE.
 4. FBC B 107.2.1 PROVIDE FRAMING DETAILS SUPPLIED FOR
 ALL NEW WALLS/CEILINGS/INFILL/SOFFITS. SHOW ANCHORAGE,
 BRACING AND BLOCKING.
 5.FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING
 CONSTRUCTION METHOD OF PROPOSED NEW SHOWER WALLS AND
 SHOWING COMPLIANCE WITH R307.2 AND R702.4.2.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-10 Cont ID  
Sent By jbrooks Date 2019-10-10 Time 09:47 Rev Time 0.00
Received By jbrooks Date 2019-10-08 Time 14:00 Sent To  
Notes
2019-10-09 14:00:21RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-16 Cont ID  
Sent By jbrooks Date 2019-09-16 Time 16:48 Rev Time  
Received By lcrespo Date 2019-09-05 Time 11:17 Sent To  
Notes
2019-09-06 11:17:38BLDG MISC 2

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-09 Cont ID  
Sent By lcrespo Date 2019-10-09 Time 15:54 Rev Time 0.00
Received By lcrespo Date 2019-10-09 Time 15:44 Sent To B
Notes
2019-10-09 15:55:4110/09/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By lcrespo Date 2019-09-16 Time 16:45 Rev Time 0.00
Received By lcrespo Date 2019-09-16 Time 16:45 Sent To  
Notes
2019-09-16 16:48:4409/16/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN (BATHROOM LAYOUT). WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ONE OF THE DRAWING PLANS THAT HAS BEEN SUBMITTED IS
 DRAWN IN PENCIL (BATHROOM LAYOUT). PLANS DONE IN PENCIL
 ARE UNACCEPTABLE AS THE DRAWING CAN BE
 MODIFIED/CHANGED. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 3. A SUB PLUMBING PERMIT IS REQUIRED BY A LICSENED FOR
 THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 4. SHOW DIMENSIONS OF SHOWER PAN, DETAIL ON BENCH,
 DISTANCE FROM LAV TO TOILET AND THEN TO WALL AND ANY
 INFORMATION, OF THE DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENT TO FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. SHOW DETAILS ON SHOWER PAN AND PITCH TO COMPLY
 ACCORDING TO 2017 FBC SEC R2709.1.
  
 6. SEE REMODELING PAGE AND CHANGE SCOPE OF WORK
 VERBIAGE, THE WAY IT IS, IT SEEMS LIKE YOU ARE BUILDING
 WALL AND BUILDING DEPARTMENT WILL REQUIRE A FULL SET OF
 PLANS FROM ENGINEER OR ARCHITECT, FYI
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  