Plan Review Details - Permit 19090038
Plan Review Stops For Permit 19090038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By rmcdouga Date 2019-10-01 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2019-10-01 Time 07:48 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-11 Cont ID  
Sent By rmcdouga Date 2019-09-11 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2019-09-11 Time 17:48 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-26 Cont ID  
Sent By jleahy Date 2019-09-26 Time 16:20 Rev Time 0.00
Received By jleahy Date 2019-09-26 Time 16:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 12:33 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 12:33 Sent To  
Notes
2019-09-16 12:35:01FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR PERMIT IS TO LOW
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR THE WORK INVOLVED,
 ELECTRIC, GAS ECT ECT
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By lcrespo Date 2019-10-02 Time 13:26 Rev Time 0.00
Received By lcrespo Date 2019-10-02 Time 13:26 Sent To  
Notes
2019-10-02 13:27:58A GAS AFFIDAVIT SHALL BE AVAILABLE AT THE FINAL
 INSPECTION FOR CITY RECORDS.
2019-10-02 13:26:24 
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By lcrespo Date 2019-09-09 Time 16:41 Rev Time 0.00
Received By lcrespo Date 2019-09-09 Time 16:41 Sent To  
Notes
2019-09-09 16:42:4009/09/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
 2. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
 4. SHOW THE LOCATION OF LP TANK. A LISTED SHUTOFF
 VALVE, UNIONS AND REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
 6. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3
 7. THE CITY RECORDS INDICATE AN EXISTING LP TANK AND
 GENERATOR INSTALLED IN 2005. THE BTU LOAD OF THE
 EXISTING SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD
 ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY
 SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM PER THE 2017
 FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 8. IF APPLICABLE SUBMIT MANUFACTURER?S SPECIFICATIONS
 FOR THE PRESSURE REGULATORS. REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC.
 G2421.1.
 9. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
 10. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 11. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-02 Cont ID  
Sent By lcrespo Date 2019-10-02 Time 13:26 Rev Time 0.00
Received By lcrespo Date 2019-09-19 Time 13:46 Sent To  
Notes
2019-09-20 13:47:01RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 12:35 Rev Time 0.00
Received By jleahy Date 2019-09-05 Time 10:51 Sent To  
Notes
2019-09-06 10:52:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By rfalcone Date 2019-09-20 Time 16:53 Rev Time 0.00
Received By rfalcone Date 2019-09-20 Time 16:53 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By rfalcone Date 2019-09-06 Time 14:57 Rev Time 0.00
Received By rfalcone Date 2019-09-06 Time 14:57 Sent To B
Notes
2019-09-06 15:08:1309/06/19 FAILED.
  
 PURSUANT ZLDR SEC. 94-305(B)(4), MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK.
 WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN
 18 INCHES INTO A REQUIRED SIDE SETBACK. PLEASE INDICATE
 THE SETBACKS FOR THE PROPOSED GENERATOR ON THE PLANS
 THE REQUIRED SETBACKS ARE: FRONT: 20 FT AND SIDE: 5 FT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]