| 2019-09-05 12:29:17 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| | 805-6724 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1.FBC B 1609. SUBMITTED ENGINEERING EVALUATION RATIONAL |
| | ANALYSIS FOR DESIGN PRESSURE RATING FOR RAISER ROOF |
| | PANEL REFERENCE DESIGN CRITERIA COMPLIANCE WITH 2004 |
| | FBC AND ASCE 7-02 WIND ZONE 150MPH. ROOF PANELS MUST |
| | DEMONSTRATE DESIGN CRITERIA COMPLIANCE WITH 2017 FBC |
| | AND ASCE 7-10 WIND ZONE 170MPH. PROVIDE TWO SETS. |
| | 2. 61G15-23.001. F.A.C. (B). ENGINEERING SPECIFICATIONS |
| | AND CALCULATIONS. AN INDEX SHEET SHALL BE USED AND |
| | SHALL BE SIGNED, DATED AND SEALED BY EACH PROFESSIONAL |
| | ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF |
| | THE ENGINEERING SPECIFICATIONS OR CALCULATIONS. THE |
| | INDEX SHEET MUST BE SIGNED, DATED AND SEALED BY THOSE |
| | PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION AND PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATIONS OR CALCULATIONS, WITH |
| | SUFFICIENT INFORMATION ON THE INDEX SHEET SO THAT THE |
| | USER WILL BE AWARE OF EACH PORTION OF THE |
| | SPECIFICATIONS OR CALCULATIONS FOR WHICH EACH |
| | PROFESSIONAL ENGINEER IS RESPONSIBLE. |
| | 3. CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED. |
| | |