Plan Review Details - Permit 19081524
Plan Review Stops For Permit 19081524
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-24 Cont ID  
Sent By cthroop Date 2019-09-24 Time 12:33 Rev Time 0.00
Received By cthroop Date 2019-09-24 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By fgiaquin Date 2019-10-17 Time 22:40 Rev Time 0.00
Received By fgiaquin Date 2019-10-17 Time 21:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-21 Cont ID  
Sent By fgiaquin Date 2019-09-21 Time 08:45 Rev Time 0.00
Received By fgiaquin Date 2019-09-20 Time 09:37 Sent To  
Notes
2019-09-21 10:34:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 1. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI/AFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.12, 210.8(A)(9); FBC RE E3902.9
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 8. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 9. INTERIOR PANEL IN LAUNDRY ROOM HAS NO WORKING
 CLEARANCE AS PER NEC 110.26(A1)&(A2)
 10. RECEPTACLE REQUIRED OUTSIDE AT BOTH FRONT AND REAR
 OF DWELLING. NEC 210.52E1
 11. PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED
 LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC
 MECHANICAL CODE M306.3.1
 12. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN, IN
 BATHROOMS. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 13. LIGHT REQUIRED AT EXTERNAL SIDE OF EACH DOOR TO
 DWELLING THAT PROVIDES GRADE LEVEL ACCESS. (FRONT DOOR)
 NEC 210.70(A)(2)(B)
 14. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1
  
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-18 Cont ID  
Sent By lmarchan Date 2019-10-18 Time 07:46 Rev Time 0.00
Received By lmarchan Date 2019-10-15 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-24 Cont ID  
Sent By cthroop Date 2019-09-24 Time 12:34 Rev Time 0.00
Received By cthroop Date 2019-09-13 Time 15:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-09-16 Cont ID  
Sent By cmontell Date 2019-09-16 Time 14:06 Rev Time 0.00
Received By cmontell Date 2019-09-16 Time 14:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-09-20 Cont ID  
Sent By tklarge Date 2019-09-20 Time 11:38 Rev Time 0.00
Received By tklarge Date 2019-09-20 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-17 Cont ID  
Sent By fgiaquin Date 2019-10-17 Time 22:41 Rev Time 0.00
Received By fgiaquin Date 2019-10-17 Time 22:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-09-24 Cont ID  
Sent By cthroop Date 2019-09-24 Time 12:33 Rev Time 0.00
Received By cthroop Date 2019-09-24 Time 10:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved