Plan Review Details - Permit 19081501
Plan Review Stops For Permit 19081501
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-12-10 Cont ID  
Sent By dbattles Date 2019-12-10 Time 09:58 Rev Time 0.00
Received By dbattles Date 2019-12-10 Time 09:58 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By jpearson Date 2019-12-10 Time 06:59 Rev Time 0.00
Received By jpearson Date 2019-12-10 Time 06:59 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jpearson Date 2019-09-16 Time 15:38 Rev Time 0.00
Received By jpearson Date 2019-09-16 Time 15:38 Sent To I
Notes
2019-09-16 15:38:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
2019-09-13 14:16:53SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-17 Cont ID  
Sent By cpuell Date 2019-12-17 Time 10:37 Rev Time 0.00
Received By cpuell Date 2019-11-26 Time 13:00 Sent To  
Notes
2019-11-27 13:00:33RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-29 Time 14:48 Sent To  
Notes
2019-08-29 14:48:07ELEC <5K

Review Stop Z ZONING
Rev No 2 Status P Date 2019-12-17 Cont ID  
Sent By eschneid Date 2019-12-17 Time 09:51 Rev Time 0.25
Received By eschneid Date 2019-12-17 Time 09:51 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By eschneid Date 2019-09-16 Time 14:49 Rev Time 0.25
Received By eschneid Date 2019-09-16 Time 14:49 Sent To  
Notes
2019-09-16 14:57:52FAILED
  
 THE PROPOSED POLE DOES NOT MEET THE CITY OF WEST PALM
 BEACH CONCEALMENT (STEALTH), STYLE OR HEIGHT
 REQUIREMENTS LISTED IN SECTIONS 78-411(E), 78-411(F)
 AND 78-411(G) OF THE CITY CODE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]