| 2019-09-05 11:25:45 | PERMIT # 19081426 |
| | REVIEW COMMENTS: |
| | |
| | 1.THE DRAWINGS SUBMITTED ARE ONLY FOR THE ELECTRICAL |
| | WORK DONE ON THIS PROJECT. THERE IS NO SPECIFIC |
| | REFERENCE TO THE ACCESS CONTROL AND ITS PLACEMENT FOR |
| | RELOCATED DOORS. PLEASE INDICATE WHERE YOUR SCOPE OF |
| | WORK RELATES TO THE ACCESS CONTROL THAT IS BEING |
| | PROPOSED. IF THE ACCESS CONTROL IS INSTALLED BY |
| | "OTHERS" THAT ENTITY IS THE ONE THAT SHOULD BE APPLYING |
| | FOR THE PERMIT. |
| | |
| | 2.INDICATE ALL NEW OR EXISTING DOORS THAT ARE EQUIPPED |
| | WITH ELECTROMAGNETIC HARDWARE. INTERLOCK WITH THE |
| | SPRINKLER AND FIRE ALARM SYSTEM SHALL BE NOTED ON THE |
| | LIFE SAFETY PLANS, FIRE ALARM PLANS AND ACCESS CONTROL |
| | PLANS. |
| | |
| | 3.ACCESS CONTROLLED EGRESS DOORS SHALL COMPLY WITH ALL |
| | SEVEN REQUIREMENTS LISTED IN SECTION 7.2.1.6.2 OF NFPA |
| | 101 FLORIDA EDITION, 2012. INTERLOCK WITH SPRINKLER AND |
| | FIRE ALARM SYSTEM SHALL BE REFERENCED ON THE LIFE |
| | SAFETY PLANS AND ELECTRICAL FIRE ALARM SYSTEM DRAWINGS. |
| | |
| | 4.PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS |
| | ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING |
| | CRITERIA ARE MET: |
| | |
| | 1). A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| | ARE ARRANGES TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| | DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| | TO THE SENSOR. |
| | 2). LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| | SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS IN THE DIRECTION OF EGRESS. |
| | 3). THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| | WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| | 4). THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | PUSH TO EXIT. |
| | 5). WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| | INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| | AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| | 30 SECONDS. |
| | 6). ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | 7). ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| | SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | |
| | 5. PER SECTION 7.2.1.5.5, ELECTRICALLY CONTROLLED |
| | EGRESS DOOR ASSEMBLIES ARE PERMITTED IF EQUIPPED WITH |
| | APPROVED LISTED HARDWARE THAT INCORPORATES A BUILT-IN |
| | SWITCH AND THE FOLLOWING FIVE CRITERIA ARE MET: |
| | 1). THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | 2). THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | 3). THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | 4). OPERATION OF THE HARDWARE INTERRUPT THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | 5). LOSS OF POWER TO THE HARDWARE AUTOMATICALLY INLOCKS |
| | THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | |
| | 6. PROVIDE MANUFACTURERS SPEC SHEETS FOR PROPOSED |
| | DEVICES TO BE INSTALLED. |
| | |
| | NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE |
| | REQUIREMENTS FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT |
| | SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED ON THE EGRESS |
| | SIDE. |
| | |
| | S. THOMAS |
| | 561-804-4728 |
| | |