| 2019-08-28 18:05:20 | 08/28/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS. |
| | |
| | NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE |
| | ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE |
| | SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED |
| | ON THE RESUBMITTAL REVIEW. |
| | |
| | 1. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO |
| | 10.0 WC. PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | FOR THE PRESSURE REGULATORS. REGULATORS INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| | OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC. G2421. |
| | |
| | 2. GAS RISER DIAGRAM REQUIRED, SUBMIT AN ISOMETRIC |
| | DRAWING THAT CLEARLY SHOWS, UNIONS, SHUTOFF VALVES ON |
| | SYSTEM, SEDIMENT TRAP AND REGULATOR PER THE 2017 FBC |
| | RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. TYPE OF GAS LABELED ON PLANS AND METER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 5. ONLY PAGE ONE OF THE MANUAL WAS SUBMITTED ON |
| | MANUFACTURER?S SPECIFICATION SHEETS/INSTALLATION MANUAL |
| | FOR POOL HEATER EQUIPMENT WE WILL NEED TO VERIFY |
| | COMPLIANCE WITH 2017 FBC FG RES. SEC. G2408.1. THE POOL |
| | HEATER SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82% |
| | PER THE 2017 FBC-ENERGY SEC. R403.10.4. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR POOL HEATER EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FG RES. SEC. G2408.1. |
| | THE POOL HEATER SHALL HAVE A MINIMUM THERMAL EFFICIENCY |
| | OF 82% PER THE 2017 FBC-ENERGY SEC. R403.10.4. |
| | |
| | 7. MANUFACTURER?S SPECIFICATION SHEETS/INSTALLATION |
| | MANUAL FOR HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | 2017 FBC FG SEC.305.1 OR 2017 FBC RES. SEC. G2408.1. |
| | |
| | 8. A SOLAR COVER OR A LIQUID COVER REQUIRED PER 2017 |
| | FBC EC404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND |
| | OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A |
| | VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| | LIQUID COVER OR OTHER MEANS PROVING TO REDUCE HEAT |
| | LOSS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |