Plan Review Details - Permit 19081361
Plan Review Stops For Permit 19081361
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 06:03 Sent To  
Notes
2019-09-23 12:35:432017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081361
 ADD: 2058 PINEHURST DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-287-0305
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 23/ 2019
 ACTION: DENIED
  
 1A) PLEASE NOTE THIS PERMIT APPLICATION CAME IN AS AN
 OWNER/ BUILDER PERMIT. THE PALM BEACH COUNTY PROPERTY
 APPRAISERS SITE SHOWS THIS PROPERTY IS OWNED BY SIMON
 2014 LLC. PLEASE NOTE TO TAKE EXCEPTION TO F. S.
 489.103 OWNER/ BUILDER EXEMPTION, AN OWNER MUST
 PERSONALLY APPEAR AND SIGN THE BUILDING APPLICATION AND
 EXEMPTION FORMS. IF THE PROPERTY IS IN AN LLC A LLC
 CANNOT APPEAR TO SIGN THE PERMIT APPLICATION NOR
 EXEMPTION FORM.
  
 1B) THE 2ND ISSUE IS THE ROOMS FOR LEASE, NOT THE
 OWNERS OWN USE, SOME TYPE OF GROUP HOME IF THE INTENDED
 USE IS AS INDICATED A R-4 USE ON THE PERMIT
 APPLICATION. THIS WOULD TAKE A CONTRACTOR TO COMPLETE
 THE WORK.
 F. S. 489. (7)(A)(1) WHEN BUILDING OR IMPROVING FARM
 OUTBUILDINGS OR ONE-FAMILY OR TWO-FAMILY RESIDENCES ON
 SUCH PROPERTY FOR THE OCCUPANCY OR USE OF SUCH OWNERS
 AND NOT OFFERED FOR SALE OR LEASE, OR BUILDING OR
 IMPROVING COMMERCIAL BUILDINGS, AT A COST NOT TO EXCEED
 $75,000, ON SUCH PROPERTY FOR THE OCCUPANCY OR USE OF
 SUCH OWNERS AND NOT OFFERED FOR SALE OR LEASE. IN AN
 ACTION BROUGHT UNDER THIS PART, PROOF OF THE SALE OR
 LEASE, OR OFFERING FOR SALE OR LEASE, OF ANY SUCH
 STRUCTURE BY THE OWNER-BUILDER WITHIN 1 YEAR AFTER
 COMPLETION OF SAME CREATES A PRESUMPTION THAT THE
 CONSTRUCTION WAS UNDERTAKEN FOR PURPOSES OF SALE OR
 LEASE.
  
 2) PLEASE NOTE ONLY FIRE SPRINKLER FLOOR PLAN WAS
 SUBMITTED, PLEASE NOTE THIS PLAN AND PERMIT APPLICATION
 WOULD NEED TO BE SUBMITTED SEPARATELY UNDER THE FIRE
 SPRINKLER PERMIT. SEPARATE REVIEWS AND FEES. 2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATIVE CODE SECTION 105.1.
  
 3) THIS REVIEW NO PLANS WERE SUBMITTED FOR A CHANGE OF
 OCCUPANCY FROM A R3 TO AN R4 OCCUPANCY TYPE. 2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATIVE CODE 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SITE REQUIREMENTS:
 PARKING
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 BUILDING FLOOR PLAN
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 OCCUPANCY GROUP SHALL BE DETERMINED, INDICATE THE
 USAGE:
  
  
 4) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 506.2).
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 BUILDINGS OF GROUP R-4 SHALL BE CLASSIFIED AS ONE OF
 THE OCCUPANCY CONDITIONS SPECIFIED IN SECTION 310.6.1
 OR 310.6.2. THIS GROUP SHALL INCLUDE, BUT NOT BE
 LIMITED TO, THE FOLLOWING:
 ALCOHOL AND DRUG CENTERS
 ASSISTED LIVING FACILITIES
 CONGREGATE CARE FACILITIES
 GROUP HOMES
 HALFWAY HOUSES
 RESIDENTIAL BOARD AND CUSTODIAL CARE FACILITIES
 SOCIAL REHABILITATION FACILITIES
  
 PLEASE INDICATE COMPLIANCE WITH 310.6.1 OR 310.6.2.
  
 310.6.1 CONDITION 1. THIS OCCUPANCY CONDITION SHALL
 INCLUDE BUILDINGS IN WHICH ALL PERSONS RECEIVING
 CUSTODIAL CARE, WITHOUT ANY ASSISTANCE, ARE CAPABLE OF
 RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE
 BUILDING EVACUATION. 310.6.2 CONDITION 2. THIS
 OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN WHICH
 THERE ARE ANY PERSONS RECEIVING CUSTODIAL CARE WHO
 REQUIRE LIMITED VERBAL OR PHYSICAL ASSISTANCE WHILE
 RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE
 BUILDING EVACUATION.
  
  
 310.6.2 CONDITION 2. THIS OCCUPANCY CONDITION SHALL
 INCLUDE BUILDINGS IN WHICH THERE ARE ANY PERSONS
 RECEIVING CUSTODIAL CARE WHO REQUIRE LIMITED VERBAL OR
 PHYSICAL ASSISTANCE WHILE RESPONDING TO AN EMERGENCY
 SITUATION TO COMPLETE BUILDING EVACUATION.
  
 5) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS 2017 FBC-B SECTION 420
 / EMERGENCY ESCAPE AND RESCUE WINDOWS/ BEDROOMS
  
 6) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE & ENTRY
 TOILET AND BATHING FACILITIES
  
 7) WITH THE CODE REQUIRED REQUIREMENTS THERE WILL BE A
 VALUE FOR THE WORK REQUIRED TO MAKE THE OCCUPANCY
 CHANGE INTO AN R4. 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
  
  
  
 8) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-10-01 Cont ID  
Sent By jpearson Date 2019-10-01 Time 09:10 Rev Time  
Received By jpearson Date   Time   Sent To I
Notes
2019-10-01 09:10:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. PROVIDE MULTIPLE POWER SOURCE FOR FIRE SPRINKLER
 SYSTEM. NEC 695.3(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-29 Cont ID  
Sent By pleduc Date 2019-08-29 Time   Rev Time 0.00
Received By pleduc Date 2019-08-29 Time 11:58 Sent To  
Notes
2019-08-29 12:17:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS PERMIT HAS TWO SEPARATE DESCRIPTION; CHANGE OF
 OCCUPANCY/ FIRE SSPRINKLER.
  
 THESE CANNOT BE UNDER THE SAME PERMIT.
  
 PLEASE SEPARATE AND RESUBMIT.
  
  
  
 2) FOR CHANGE OF OCCUPANCY, PLEASE PROVIDE DETAILS OF
 WHAT IS BEING PROVIDED IN THIS OCCUPANCY?
  
 WHAT OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE
 PREVENTION CODE WILL IT BE REQUIRED TO COMPLY WITH?
  
 PROVIDE A LIFE SAFETY PLAN INCLUDING FLOOR PLAN
 DETAILS/DIMENSIONS, DOOR SIZES, EXIT HARDWARE, SMOKE
 DETECTOR LOCATIONS, ETC,
  
 PLEASE PROVIDE
  
  
  
 3) IT APPEARS THAT A WELL IS PROPOSED FOR THE FIRE
 SPRINKLER; PER NFPA 13D AS PROPOSED.
  
 THE PUMP FOR THE WELL IS ELECTRIC, HOW WILL THIS BE
 POWERED IN THE EVENT OF POWER FAILURE?
  
 HOW DO YOU PROPOSE TO VERIFY AND CONFIRM THE WATER
 FLOW?
  
  
 4) ANY UNDERGROUND FIRE LINE SHALL BE INSTALLED PER
 NFPA 24 BY A LICENSED UNDERGROUND CONTRACTOR PER THE
 STATE OF FLORIDA.
  
 PLEAE ENSURE COMPLIANCE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-10-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-27 Time 15:00 Sent To  
Notes
2019-08-27 15:00:32C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-23 Cont ID  
Sent By jwitmer Date 2019-09-23 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2019-09-23 Time 06:03 Sent To  
Notes
2019-09-23 12:32:46IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By ccole Date 2019-09-24 Time 14:59 Rev Time 0.00
Received By ccole Date 2019-09-24 Time 14:56 Sent To  
Notes
2019-09-24 15:55:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081361
 9/24/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DUE TO THE CHANGE OF OCCUPANCY FROM R-3 TO R-4
 (RESIDENTIAL TO COMMERCIAL), PLEASE VERIFY THAT
 ADEQUATE VENTILATION FOR ALL ROOM AND SPACES IS BEING
 PROVIDED EITHER BY NATURAL OR MECHANICAL MEANS IN
 ACCORDANCE WITH SECTION 401.2 FBC M. TO COMPLY WITH THE
 NATURAL VENTILATION REQUIREMENT, ALL OCCUPIED SPACES
 MUST HAVE MUST HAVE WINDOWS, DOOR, LOUVERS, OR OTHER
 OPENINGS TO THE OUTDOORS. THE MINIMUM OPENABLE AREA OF
 THOSE OPENINGS SHALL BE 4 PERCENT OF THE FLOOR AREA
 BEING VENTILATED. FOR EXAMPLE, BEDROOM #1 ON THE PLAN
 IS APPROXIMATELY 224 SQ. FT., THEREFORE THE TWO WINDOWS
 IN THE ROOM COMBINED MUST HAVE A MINIMUM OF 9 SQ, FT,
 OPENINGS TO THE OUTDOORS. TO COMPLY MECHANICALLY,
 OUTSIDE AIR MUST BE DRAWN INTO THE SPACES USING EITHER
 AN OUTSIDE AIR DUCT CONNECTED TO THE RETURN AIR SYSTEM
 OF THE AC AIR HANDLER, OR BY USING A FAN TO DRAW AIR
 DIRECTLY INTO THE SPACE THROUGH THE EXTERIOR WALL OR
 ROOF. THE REQUIRED VENTILATION RATE PER TABLE 403.3.1.1
 FBC M IS 0.35 ACH (AIR CHANGES PER HOUR) BUT NOT LESS
 THAN 15 CFMS PER PERSON.
  
 2) DUE TO THE CHANGE OF OCCUPANCY FROM R-3 AND R-4, THE
 BATHROOMS SHALL BE MECHANICALLY VENTILATED- SECTION
 1203.5.2.1 FBC B. MOST TYPICALLY, MINIMUM 50 CFM BATH
 EXHAUST FANS AND EXHAUST DUCTS ARE INSTALLED TO MEET
 COMPLIANCE- SEE TABLE 403.3.1.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-21 Cont ID  
Sent By gjohnson Date 2019-09-21 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2019-09-21 Time 09:40 Sent To  
Notes
2019-09-21 16:27:241ST REVIEW: 19081361
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PROVIDE PROPERTY ADDRESS INFORMATION, OWNER
 INFORMATION AND VALUATION OF JOB ON PERMIT APPLICATION
 FORM.PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE FLOOR PLAN SHOWING THE LOCATION OF THE
 PLUMBING FIXTURES. PER WPB AMEND TO FBC 107.2.1
  
 3. DOES THE WATER SERVICE HAVE A BACKFLOW , ONE IS
 REQUIRED BECAUSE OF THE ALTERNATE SOURCE OF WATER PER
 WPB CROSS CONNECTION MANUAL.SHOW ON SITE PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By llouie Date 2019-09-24 Time   Rev Time 0.00
Received By llouie Date 2019-09-24 Time   Sent To  
Notes
2019-09-24 10:53:06SPOKE TO ROBERT BROWN, BUILDING OFFICIAL ON 9/24/19 -
 INFORMED THAT THE SCOPE OF WORK IS ONLY FOR THE UPGRADE
 OF FIRE SPRINKLER SYSTEM DUE TO THE INCREASE IN
 OCCUPANTS FROM 5 TO 6 (PANSYS PLACE).

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-05 Cont ID  
Sent By llouie Date 2019-09-05 Time   Rev Time  
Received By llouie Date 2019-09-05 Time   Sent To  
Notes
2019-09-05 11:38:27** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED, DATED AND SEALED SURVEY OF THE PROPERTY IS
 MISSING FROM THE PERMIT APPLICATION. PLEASE PROVIDE.
  
 2.) PLEASE SHOW EXISTING AND PROPOSED FLOOR PLAN.
  
 3.) WHAT IS THE VALUE OF THE SCOPE OF WORK? PLEASE NOTE
 THAT IF THE VALUE OF THE SCOPE OF WORK EXCEEDS 50% OF
 THE VALUE OF THE STRUCTURE, THE LANDSCAPING ON THE
 PROPERTY WILL BE REQUIRED TO BE UPGRADED TO MEET THE
 MINIMUM REQUIREMENTS OF THE CITY'S LANDSCAPE CODE.
 [ZLDR S.94-441(C)]
  
  
 NOTES:
  
 * PROPOSED USE: GROUP HOME - TYPE I: <6 PERSONS.
  
 * REFERENCE BTR APPLICATION: PANSYS PLACE, INC.
 (#0000051830); TEMPORARY APPROVAL EXPIRES 10/17/19.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  