Plan Review Details - Permit 19081275
Plan Review Stops For Permit 19081275
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-10-09 Cont ID  
Sent By pvalenti Date 2019-10-09 Time 10:47 Rev Time 0.00
Received By pvalenti Date 2019-10-09 Time 10:47 Sent To  
Notes
2019-10-09 10:50:31PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS LETTER OF ACKNOWLEDGEMENT RECEIVED. PV

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 06:32 Sent To  
Notes
2019-09-17 07:03:24SHOPPING CENTER C. O.ED IN 1977.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 15:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 06:32 Sent To  
Notes
2019-09-17 08:59:022017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081275
 ADD: 5612 S. DIXIE HWY.
 CONT: FLORIDA DEVELOPMENT & CONSTRUCTION
 TEL: 954-707-1309
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 17/2019
 ACTION: DENIED
  
 1) PLEASE CLARIFY THE SCOPE OF WORK. WITHIN THE
 SUBMITTED SET OF PLANS SHEET A.05 HAS NOTES THAT NO
 ROOF WORK IS TO BE COMPLETED. NOTES 2 & 3 INDICATE ROOF
 TOP A/C IS TO BE REPLACED AND DETAILS ARE FOR THE
 FLASHING REPAIRS. ALSO WITH IN THE PERMIT PACKAGE THERE
 IS A SET (2) OF MIAMI-DADE NOA?S FOR GAF CONVENTIONAL
 BUILT-UP-ROOF SYSTEMS OVER RECOVER DECKS. PLEASE NOTE
 THE DESIGNER OF RECORD HAS NOT REVIEWED THIS PRODUCT
 APPROVAL, NOR SELECTED ONE OF THE SUB-SYSTEMS FOR
 INSTALLATION.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: W. P. B.
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 2) THE 2017 EXISTING BUILDING CODE SECTION 706.3 DEALS
 WITH RECOVERING OF ROOF DECKS.
 706.3 RECOVERING VERSUS REPLACEMENT. NEW ROOF COVERINGS
 SHALL NOT BE INSTALLED WITHOUT FIRST REMOVING ALL
 EXISTING LAYERS OF ROOF COVERINGS DOWN TO THE ROOF DECK
 WHERE ANY OF THE FOLLOWING CONDITIONS OCCUR:
  
 2.1. WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER
 SOAKED OR HAS DETERIORATED TO THE POINT THAT THE
 EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A
 BASE FOR ADDITIONAL ROOFING.
  
 2.2. WHERE THE EXISTING ROOF COVERING IS WOOD SHAKE,
 SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT TILE.
  
 2.3. WHERE THE EXISTING ROOF HAS TWO OR MORE
 APPLICATIONS OF ANY TYPE OF ROOF COVERING.
  
 2.4. WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS
 BLISTERS ARE CUT OR SCRAPED OPEN AND REMAINING
 MATERIALS SECURED DOWN BEFORE APPLYING ADDITIONAL
 ROOFING.
  
 2.5. WHERE THE EXISTING ROOF IS TO BE USED FOR
 ATTACHMENT FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH
 THE SECUREMENT PROVISIONS OF SECTION 1504.1 OF THE
 FLORIDA BUILDING CODE, BUILDING CANNOT BE MET.
  
 IN THE 2017 FBC-B SECTION 1504.1. FBC-B 1504.1 WIND
 RESISTANCE OF ROOFS. ROOF DECKS AND ROOF COVERINGS
 SHALL BE DESIGNED FOR WIND LOADS IN ACCORDANCE WITH
 CHAPTER 16 AND SECTIONS 1504.2, 1504.3 AND 1504.4.
 A PULL TEST IS NECESSARY. 1504.3.1 OTHER ROOF SYSTEMS.
 BUILT-UP, MODIFIED BITUMEN, FULLY ADHERED OR
 MECHANICALLY ATTACHED SINGLE-PLY ROOF SYSTEMS, METAL
 PANEL ROOF SYSTEMS APPLIED TO A SOLID OR CLOSELY FITTED
 DECK AND OTHER TYPES OF MEMBRANE ROOF COVERINGS SHALL
 BE TESTED IN ACCORDANCE WITH FM 4474, UL 580 OR UL
 1897.
  
 3) THE CGC STEPHEN CIRIACO IS NOT LICENSED AS A
 CERTIFIED ROOFING CONTRACTOR AND THE RESTRICTIONS FOR
 THE CGC LICENSE UNDER F. S. 489.113(3)(B) ONLY ALLOWS
 FOR: (B) A GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR
 SHALL NOT BE REQUIRED TO SUBCONTRACT THE INSTALLATION,
 OR REPAIR MADE UNDER WARRANTY, OF WOOD SHINGLES, WOOD
 SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE ROOFING
 MATERIALS ON A NEW BUILDING OF HIS OR HER OWN
 CONSTRUCTION.
  
 4) SHEET A.03 PLEASE REVIEW THE FLOAT TANKS, OPEN FLOAT
 TUB, SHOWERS AND BATHROOM # 1 WITH SHOWER.
 PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE 213.2
 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE
 PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE
 BATHING ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL
 COMPLY WITH 603. PLEASE REVIEW THE PLUMBING PLAN
 REVIEWER?S COMMENTS THAT DEAL WITH ALL OF THE
 ACCESSIBLE ELEMENTS THAT NEED TO SHOW CODE COMPLIANCE.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By jleahy Date 2019-10-25 Time 14:26 Rev Time 0.00
Received By jleahy Date 2019-10-25 Time 14:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By jpearson Date 2019-09-19 Time 09:05 Rev Time 0.00
Received By jpearson Date 2019-09-19 Time 08:07 Sent To  
Notes
2019-09-19 09:05:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE LIGHT FIXTURE SCHEDULE. LIGHTING IN BATHTUB
 OR SHOWER AREAS SHALL BE SUITABLE FOR DAMP LOCATIONS.
 PROVIDE CORRECTION. NEC 410.10(D)
 3. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS PER CODE. NEC
 210.62
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE CONTROL FOR SIGN PER ENERGY CODE. FBC EC
 405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By pleduc Date 2019-10-21 Time   Rev Time 0.00
Received By pleduc Date 2019-10-21 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-29 Cont ID  
Sent By pleduc Date 2019-08-29 Time   Rev Time 0.00
Received By pleduc Date 2019-08-29 Time 12:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By jesmith Date 2019-10-24 Time 14:20 Rev Time 0.00
Received By jesmith Date 2019-10-24 Time 14:20 Sent To  
Notes
2019-10-24 14:20:35GAS COMMENTS: APPROVED W/PROVISO
  
 1. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE
 TANKLESS GAS WATER HEATER. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO THE FIRST GAS
 ROUGH INSPECTION.
 3. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-09-16 Cont ID  
Sent By jesmith Date 2019-09-16 Time 14:40 Rev Time 0.00
Received By jesmith Date 2019-09-16 Time 13:45 Sent To  
Notes
2019-09-16 14:40:29GAS COMMENTS: APPROVED W/PROVISO
  
 1. CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, THE MANUFACTURER?S DATA
 SHEETS/SPECIFICATION/INSTALLATION GUIDE FOR THE
 TANKLESS GAS WATER HEATER. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO THE FIRST GAS
 ROUGH INSPECTION.
 3. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-25 Cont ID  
Sent By cpuell Date 2019-10-25 Time 14:56 Rev Time 0.00
Received By cpuell Date 2019-10-15 Time 14:26 Sent To  
Notes
2019-10-16 14:26:46B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-26 Time 15:30 Sent To  
Notes
2019-08-26 15:30:28B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 06:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By ccole Date 2019-10-23 Time 11:51 Rev Time 0.00
Received By ccole Date 2019-10-23 Time 10:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By ccole Date 2019-09-17 Time 15:26 Rev Time 0.00
Received By ccole Date 2019-09-17 Time 12:53 Sent To  
Notes
2019-09-17 15:31:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081275
 9/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE A MINIMUM 50 CFM OF EXHAUST
 VENTILATION AT EACH SHOWER HEAD LOCATION PER TABLE
 403.3.1.1 FBC M.
  
 2) M-1: SUBMIT MANNUFACTURER'S SPECIFICATIONS FOR THE
 FLOAT TUBS AND THE INFRARED HEATERS- SECION 304.1 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-24 Cont ID  
Sent By jesmith Date 2019-10-24 Time 14:23 Rev Time 0.00
Received By jesmith Date 2019-10-22 Time 14:44 Sent To  
Notes
2019-10-24 14:23:15PLUMBING COMMENTS: APPROVED
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jesmith Date 2019-09-16 Time 15:54 Rev Time 0.00
Received By jesmith Date 2019-09-16 Time 15:52 Sent To  
Notes
2019-09-16 15:52:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A. PER FBC ACC 213.3.6, THE BATHROOM SHOWER, ONE OF THE
 TWO FOAT TANK ROOMS AND THE OPEN FLOAT TUB ROOM SHALL
 COMPLY WITH FBC ACC 608.
  
 1) PROVIDE CLEAR FLOOR SPACE ON PLAN VIEW SHOWING
 COMPLIANCE WITH FBC ACC SECTION 305.
 2) PROVIDE A DETAIL (ELEVATION) OF THE SHOWER SHOWING
 COMPLIANCE WITH FBC ACC SECTION 608.
  
 B. WATER CLOSET SHALL BE 16" MINIMUM AND 18" MAXIMUM,
 CENTERLINE TO SIDE WALL PER FBC ACC 604.2 AND THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM TO THE WALL SIDE AND 24 INCHES
 (610 MM) MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2.
 C. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW PER FBC ACC 604.7.
  
 2. WHAT IS THE OPEN FLOAT TUB AND HOW IS WATER SUPPLIED
 TO IT?
 3. HOW ARE THE FLOAT TANKS DRAINED? DO THE HOSE BIBS
 PROVIDE WATER FOR THE FLOAT TANKS?
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION/CUT SHEETS FOR FLOAT TANKS AND OPEN FLOAT
 TUB.
 5. RE: SANITARY ISOMETRIC; A SHOWER IS INDICATED WHERE
 THE OPEN FLOAT TUB SHOULD BE. PLEASE CLARIFY.
 6. SHOW LOCATION OF SHUT OFF VALVES FOR STACKABLE
 WASHER/DRYER COMBO TO SHOW COMPLIANCE WITH FBC PL
 606.3..
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19081275 5612 S DIXIE HWY
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By rfalcone Date 2019-10-25 Time 14:45 Rev Time 0.00
Received By rfalcone Date 2019-10-25 Time 14:45 Sent To  
Notes
2019-10-25 14:48:4510/25/19 PASSED.
  
 NO MODIFICATIONS BEING MADE TO THE FOOTPRINT OF THE
 STRUCTURE. APPLICANT BROUGHT PLAN SET UP TO PZ FOR
 REVIEW AND TOOK THE PLAN SET BACK DOWN TO THE BUILDING
 DEPARTMENT.
  
 RACHEL FALCONE
 [email protected]
 561-822-1442

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-09-06 Time   Rev Time 0.00
Received By pgreilic Date 2019-09-06 Time 10:51 Sent To  
Notes
2019-09-06 10:51:531.) PROVIDE A SURVEY AND OR ADD A NOTE INDICATING THE
 EXISTING BUILDING FOOTPRINT WILL NOT BE ALTERED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]