Plan Review Details - Permit 19081237
Plan Review Stops For Permit 19081237
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-29 Cont ID  
Sent By rmcdouga Date 2019-08-29 Time 11:47 Rev Time 0.00
Received By rmcdouga Date 2019-08-29 Time 11:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By rmcdouga Date 2019-08-27 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2019-08-27 Time 18:52 Sent To HIST
Notes
2019-08-27 19:01:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MAXIMUM DESIGN PRESSURE OF -52.5 PSF THAT IS
 SPECIFIED FOR FASTENING OPTION #3 ON PAGE 51 OF NOA
 NO.18-0919.12 FOR THE GAF MODIFIED ROOF SYSTEM IS NOT
 ADEQUATE FOR THE CORNER AND PERIMETER AREAS. SUBMIT TWO
 SETS OF SIGNED AND SEALED RAS117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON PAGE 67.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By fmittner Date 2019-08-28 Time 09:31 Rev Time 0.00
Received By fmittner Date 2019-08-28 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-28 Cont ID  
Sent By skennedy Date 2019-08-28 Time 10:59 Rev Time 0.00
Received By skennedy Date 2019-08-23 Time 14:02 Sent To  
Notes
***NONE***