Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By jwitmer Date 2020-01-13 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2020-01-13 Time 06:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-11-19 Cont ID  
Sent By jwitmer Date 2019-11-19 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2019-11-19 Time 07:01 Sent To  
Notes
2019-11-19 10:04:54PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 09:04 Sent To  
Notes
2019-09-17 09:09:42PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-01-13 Cont ID  
Sent By jwitmer Date 2020-01-13 Time 07:39 Rev Time 0.00
Received By jwitmer Date 2020-01-13 Time 06:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-11-19 Cont ID  
Sent By jwitmer Date 2019-11-19 Time 10:03 Rev Time 0.00
Received By jwitmer Date 2019-11-19 Time 07:01 Sent To  
Notes
2019-11-19 10:03:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081206
 ADD: 1920 PALM BEACH LAKES SUITE: 214-215
 CONT: OCTAGON CONSTRUCTION GROUP INC.
 TEL: 561-676-4543
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 19/2019
 ACTION: DENIED
  
 1) COMPLETE.
  
 2) SHEET A-1:
 2A-B) COMPLIED.
  
 2C) IN EACH OF THE 2 ACCESSIBLE BATHROOMS THERE ARE
 NOTES FOR A HAND HELD SHOWER AND SHOWER DRAIN. PLEASE
 SHOW COMPLIANCE FOR AN ACCESSIBLE ROLL-IN SHOWER AND
 COMPLIANCE WITH 608.5.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 3A) COMPLIED, DUROCK TO CEILING.
  
 3B) 2ND REQUEST. NEW DETAIL DOES NOT GIVE ANY CEILING
 DETAIL. RESPONSE INDICATES S SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK IS ATTACHED.
 1ST ROUND COMMENT. SHEET A2 DETAIL 8 SHOWS THE USE OF
 AN ACOUSTICAL DROPPED CEILING FOR IN THE SHOWER
 COMPARTMENT. PLEASE REVIEW SECTION FBC-B 2509.3 WHERE
 WATER RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED.
  
 3C) 2ND REQUEST. NO RESPONSE COMMENT TO THIS CODE
 ISSUE.
  
 3C)(1) THE PLANS ARE SILENT AS TO HOW THE JOINT FROM
 THE BACKER BOARD FOR TILE WILL BE SEALED TO THE FLOOR.
 THE 2017 FBC-B SECTION 1210.2.1 INDICATES THE
 INTERSECTIONS OF SUCH FLOORS WITH WALLS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT VERTICAL BASE THAT EXTENDS
 UPWARD ONTO THE WALLS NOT LESS THAN 4 INCHES.
  
 3C)(2) 2ND REQUEST. THE WHOLE ROOM NEEDS TO BE DESIGNED
 AS A SHOWER. PLEASE PROVIDE A BLOWN UP DETAIL FOR
 COMPLIANCE WITH THE SHOWER PLAN INTERSECTS WITH THE
 WALL AND TO WHAT HEIGHT THE SHOWER PAN NEEDS TO BE IN
 THE VERTICAL PLANE AND THE LAP OF THE DUROROCK BOARD.
 1ST ROUND OF COMMENTS. NOR HOW THE FLOOR WILL BE
 SEALED, PITCHED TO THE DRAIN NOR THE REQUIREMENTS UNDER
 THE PLUMBING CODE FOR A SHOWER LINING. FBC-P 417.2. /
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3D) SEMI-COMPLIED. SHEET A-2 DETAIL # 4 NOW SHOWS THE
 MIRROR WITH A TRIM SURROUND. THE VERTICAL MEASUREMENT
 IS TAKEN FROM FINISH FLOOR TO THE BOTTOM EDGE OF THE
 MIRROR, NOT THE BOTTOM OF THE
 REFLECTIVE SURFACE.
 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3E) NEW COMMENT. SHEET A-2 DETAIL 3 IS A CODE COMPLIANT
 FOR THE WATER CLOSET PAPER DISPENSER. THE ISSUE
 IS WITH DETAIL # 7 AND THE UPPER LEFT NOMENCLATURE (A)
 FOR THE WATER CLOSET PAPER DISPENSER ARE NOT IN THE
 CORRECT LOCATION.
 TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 3F) NEW COMMENT. SHEET A2 DETAILS 2 & 3 BOTH SHOW THE
 GRAB BAR BEING MEASURED FROM FINISH FLOOR TO THE CENTER
 OF THE GRAB BAR. PLEASE SHOW COMPLIANCE WITH:
 GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1ST ROUND OF COMMENTS. IN THE OLD LAYOUT OF THE
 RESTROOMS THERE WERE NO WINDOWS ON THE EXTERIOR WALL.
 ON THE NEW LAYOUT THE ADA RESTROOM # 2 HAS THE LAVATORY
 IN THE WINDOW. THE PLANS DO NOT HAVE A DETAIL FOR THIS
 CONFIGURATION, THE SUBMITTED ADA DETAIL 4 ON SHEET A-2
 HAS A MIRROR LOCATED BEHIND THE LAV. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED, CODE COMPLIANCE
 CANNOT BE DETERMINED AT THIS TIME.
  
 4) 2ND REQUEST. THIS IS A CONDO BUILDING. WITH THE
 UNIFYING 2 UNITS YOU NEED TO COMPLETE A UNITY OF TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 09:04 Sent To  
Notes
2019-09-17 10:57:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081206
 ADD: 1920 PALM BEACH LAKES SUITE: 214-215
 CONT: OCTAGON CONSTRUCTION GROUP INC.
 TEL: 561-676-4543
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 17/2019
 ACTION: DENIED
  
 1) THE COVERSHEET:
 1A) CODE RESEARCH INDICATES THE MINIMUM BUILDING TYPE
 AS TYPE III. THERE IS A QUESTION AS TO WHICH CODE YOU
 ARE REFERENCING. THIS BUILDING WAS BUILT IN 1976, ARE
 YOU REFERENCING THE CODE AT TIME THE BUILDING WAS
 BUILT? THE CONSTRUCTION TYPE ALSO CHANGED FROM THE 2001
 FBC-B TYPE III CONSTRUCTION TO IN THE 2004 FBC TO IV
 HEAVY TIMBER. TODAYS CODE THE 2017 FBC-B THE
 TERMINOLOGY WOULD BE:
 TYPE III-A 1-HOUR PROTECTED
 TYPE III-B NON-PROTECTED
 PLEASE INDICATE THE CURRENT CONSTRUCTION TYPE.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE COVERSHEET UNDER THE HEADING CODE RESEARCH,
 LIST FIRE WALLS EXISTING 2- HOUR TENANT SEPARATION
 WALLS. THE TERM FIRE WALLS IS A TERM USED TO SEPARATE A
 BUILDING INTO SEPARATE FIRE AREAS IN ORDER TO NOT FIRE
 SPRINKLER A BUILDING, SEE FBC-B 706.1. FIRE BARRIER
 WALLS SEPARATE OCCUPANCIES, SHAFT, INTERIOR EXIT
 STAIRWAYS EXIT ENCLOSURES, EXIT PASSAGEWAYS AND ATRIUMS
 SEE FBC-B 707.1. FIRE PARTITIONS SEPARATE TENANT SPACES
 THAT ARE THE SAME OCCUPANCY TYPE SEE FBC-B 708.1.
 PLEASE CORRECT TERMINOLOGY.
  
 1C) THE COVERSHEET UNDER THE HEADING CODE RESEARCH,
 LIST FIRE WALLS EXISTING 2- HOUR TENANT SEPARATION
 WALLS (FIRE PARTITION) WHEREAS SHEET D-1 & A-1 BOTH
 INDICATE THE SAME TENANT SEPARATION WALL(DEMISING WALL)
 AS A ONE HOUR WALL. PLEASE UPDATE THE PLANS TO SHOW
 CONSISTENCY. 107.2.1.2.
  
 2) SHEET A-1:
 2A) SHEET A-1 INDICATES CHAIRS NEXT TO THE INSWING
 DOORWAY IN THE WAITING ROOM AND THE INFUSION ROOM.
 TO SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 404.2.4, TABLE 404.2.4.1 & FIGURE 404.2.4.1(A).
  
 2B) THE DEMO PLAN SHOWS ALL OF THE WALLS OF THE
 EXISTING BATHROOMS REMOVED. THE PROPOSED FLOOR PLAN
 INDICATES A BACKWALL MEASUREMENT OF 6 FEET 9 INCHES.
 THIS MEASUREMENT IS TOO SMALL TO SHOW COMPLIANCE WITH
 THE ACCESS. CODE SECTION 604.3.1 SIZE AND 604.3.2
 OVERLAP. THE MINIMUM MEASUREMENT FINISH TO FINISH IS 7
 FEET 1 INCH.
  
 2C) IN EACH OF THE 2 ACCESSIBLE BATHROOMS THERE ARE
 NOTES FOR A HAND HELD SHOWER AND SHOWER DRAIN. PLEASE
 SHOW COMPLIANCE FOR AN ACCESSIBLE ROLL-IN SHOWER AND
 COMPLIANCE WITH 608.5.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.
  
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 3A) SHEET A2 DETAIL 8 HAS NOTES DEALING WITH THE SHOWER
 WALLS IN THE ACCESSIBLE RESTROOMS. THE NOTE INDICATES
 THE USE OF DUROCK UP 4 FEET AND MR BOARD ABOVE. ALL
 WALLS TO BE CERAMIC TILE FULL HEIGHT.
 PLEASE REVIEW THE 2017 FBC-B SECTION 2509.2 ACCEPTABLE
 MATERIALS TO BE USED FOR TILE BASE IN SHOWERS.
  
 3B) SHEET A2 DETAIL 8 SHOWS THE USE OF AN ACOUSTICAL
 DROPPED CEILING FOR IN THE SHOWER COMPARTMENT. PLEASE
 REVIEW SECTION FBC-B 2509.3 WHERE WATER RESISTANT
 GYPSUM BACKING BOARD SHALL NOT BE USED.
 (1) OVER A VAPOR RETARDER IN A SHOWER COMPARTMENT.
  
 3E) THE PLANS ARE SILENT AS TO HOW THE JOINT FROM THE
 BACKER BOARD FOR TILE WILL BE SEALED TO THE FLOOR NOR
 HOW THE FLOOR WILL BE SEALED, PITCHED TO THE DRAIN NOR
 THE REQUIREMENTS UNDER THE PLUMBING CODE FOR A SHOWER
 LINING. FBC-P 417.2. / 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3C) IN THE OLD LAYOUT OF THE RESTROOMS THERE WERE NO
 WINDOWS ON THE EXTERIOR WALL. ON THE NEW LAYOUT THE ADA
 RESTROOM # 2 HAS THE LAVATORY IN THE WINDOW. THE PLANS
 DO NOT HAVE A DETAIL FOR THIS CONFIGURATION, THE
 SUBMITTED ADA DETAIL 4 ON SHEET A-2 HAS A MIRROR
 LOCATED BEHIND THE LAV. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, CODE COMPLIANCE CANNOT BE
 DETERMINED AT THIS TIME.
  
 4) THIS IS A CONDO BUILDING. WITH THE UNIFYING 2 UNITS
 YOU NEED TO COMPLETE A UNITY OF TITLE.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-01-10 Cont ID  
Sent By jpearson Date 2020-01-10 Time 15:46 Rev Time 0.00
Received By jpearson Date 2020-01-10 Time 15:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-21 Cont ID  
Sent By jpearson Date 2019-11-21 Time 14:34 Rev Time 0.00
Received By jpearson Date 2019-11-21 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-18 Cont ID  
Sent By jpearson Date 2019-09-18 Time 14:32 Rev Time 0.00
Received By jpearson Date 2019-09-18 Time 07:43 Sent To  
Notes
2019-09-18 13:21:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8
 2. DESIGNATE AREAS ON PLAN THAT WILL BE WIRED PER NEC
 517.13.
 3. PROVIDE ACCURATE LOAD CALCULATION. THE LOAD
 CALCULATION PROVIDED SHOWS A DEMAND FACTOR OF 60% FOR
 LOADS OVER10000 VA, WHICH IS A CODE VIOLATION. PROVIDE
 CORRECTION. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-01-21 Cont ID  
Sent By pleduc Date 2020-01-21 Time   Rev Time 0.00
Received By pleduc Date 2020-01-21 Time 12:03 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-11-26 Cont ID  
Sent By pleduc Date 2019-11-26 Time   Rev Time 0.00
Received By pleduc Date 2019-11-26 Time 11:13 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By sathomas Date 2019-08-28 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-08-28 Time 00:00 Sent To M
Notes
2019-08-28 12:31:23NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 1 & 101-THE LIFE SAFETY
 CODE (2015 EDITION WITH FLORIDA AMENDMENTS.)
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PER SECTION 7.5.2.1, ACCESS TO AN EXIT SHALL NOT BE
 THROUGH KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN
 CHAPTERS 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS,
 BEDROOMS OR SIMILAR SPACES, OR OTHER ROOMS OR SPACES
 SUBJECT TO LOCKING.
  
 ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE
 PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN
 EXIT."
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 16:36 Rev Time 0.00
Received By gjohnson Date 2020-01-30 Time 13:59 Sent To  
Notes
2020-01-31 13:59:25RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-31 Cont ID  
Sent By lmarchan Date 2020-01-31 Time 13:59 Rev Time 0.00
Received By lmarchan Date 2020-01-08 Time 14:20 Sent To  
Notes
2020-01-09 14:20:58B20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-26 Cont ID  
Sent By cpuell Date 2019-11-26 Time 11:27 Rev Time 0.00
Received By cpuell Date 2019-11-12 Time 14:39 Sent To  
Notes
2019-11-13 14:39:18B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-23 Time 14:27 Sent To  
Notes
2019-08-23 14:27:36B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-02-03 Cont ID  
Sent By ccole Date 2020-02-03 Time 10:43 Rev Time 0.00
Received By ccole Date 2020-02-03 Time 10:21 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-01-15 Cont ID  
Sent By ccole Date 2020-01-15 Time 08:48 Rev Time 0.00
Received By ccole Date 2020-01-14 Time 17:37 Sent To  
Notes
2020-01-15 09:20:442ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19081206
 1/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE REVISED AC EQUIPMENT SCHEDULE
 INDICATES AN EXISTING 2.5 TON SYSTEM, HOWEVER THE MODEL
 NUMBER OF THE AIR HANDLER, THE TOTAL COOLING CAPACITY,
 AND THE TOTAL CFMS OF THE UNIT INDICATE IT IS A 3-TON
 SYSTEM- PLEASE CORRECT.
  
 2) M1: THE MECHANICAL DUCT LAYOUT PLAN INDICATES A
 TOTAL OF 657 CFMS TO BE DISTRIBUTED IN THE TENANT SPACE
 WHICH DOES NOT APPEAR TO BE CONSISTENT WITH THE 1200
 CFM TOTAL CAPACITY OF THE SYSTEM. IT MAY BE HELPFUL TO
 PERFORM A HEAT LOAD CALACULATION FOR THE SPACE USING
 MANUAL N- SECTION C403.2.1 FBC EC.
  
 3) M1: THE BOXED NOTE SHOWN BY THE AIR CALCULATIONS
 INDICATES AN ERV WILL BE INSTALLED, HOWEVER THERE IS NO
 ERV SYSTEM SHOWN ON THE PLANS- PLEASE CLARIFY AND REFER
 TO SECTION C403.2.7 FBC EC FOR MORE INFORMATION. PLEASE
 NOTE THE CALCULATIONS IN THE BOX INDICATE AN RTU AT
 1200 CFMS AND 507 CFMS OF EXHAUST IN THE SPACE WHICH
 DOES NOT APPEAR TO CORRECT- THE PLANS ARE SHOWING AN
 AHU IN THE CLOSET, AND TWO BATH EXHAUST FANS. PLEASE
 PROVIDE EXHAUST FAN SCHEDULES TO VERIFY NTHE 507 CFMS
 OF EXHAUST.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-11-18 Cont ID  
Sent By ccole Date 2019-11-18 Time 13:22 Rev Time 0.00
Received By ccole Date 2019-11-18 Time 13:21 Sent To  
Notes
2019-11-18 13:34:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081206
 11/1819
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.THE COMMENTS LISTED BELOW
 FROM THE 1ST REVIEW STILL EXIST. PLEASE COMPLY.
  
 1) SHEET M-1: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW SYSTEM IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC, AND SECTION 312.1 FBC M.
 THE ARCHITECT'S NARRATIVE RESP0ONSE INDICATES BY
 OTHERS.
  
 2) M-1: REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-M. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
 ARCHITECT INDICATES BY OTHERS
  
 4) M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED FOR THE
 OCCUPANTS. IF AN O/A DUCT IS TO BE USED, PLEASE SHOW
 THE LOCATION OF THE DUCT, THE TYPE AND SIZE OF DUCT,
 AND THE LOCATION OF THE AIR INLET- SECTION 401.4 FBC M.
 NO CORRECTIONS TO THE PLANS WERE MADE
  
 5) M-1: IF AN O/A DUCT IS TO BE PROVIDED PLEASE PROVIDE
 AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER- SECTION
 C403.2.4.3 FBC- EC.
 NO CORRECTIONS TO THE PLANS WERE MADE.
  
 7) M-1: THE AC CLOSET AND DOORS SHALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION- SECTION C403.2.9.2 FBC
 EC, AND SECTION 602.1 FBC M.
 NO CORRECTIONS TO THE PLANS WERE MADE
  
 8) NEW COMMENT- M-1: THE 4" ROUND DUCT SUPPLYING 100
 CFMS OF AIR ARE UNDERSIZED PER TRANE DUCTULATER SIZING.
 PLEASE INCREASE THE DUCT SIZES TO 6" .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By ccole Date 2019-09-16 Time 14:51 Rev Time 0.00
Received By ccole Date 2019-09-16 Time 13:15 Sent To  
Notes
2019-09-17 08:16:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081206
 9/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE AC COOLING AND HEATING
 CALCULATIONS FOR THE NEW SYSTEM IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC, AND SECTION 312.1 FBC M.
  
 2) M-1: REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-M. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 3) M-1: THE CORRIDOR SHALL NOT BE USED TO CONVEY RETURN
 AIR FROM THE ROOMS TO THE AIR HANDLER- SECTION 601.2
 FBC M. DUCTED RETRUNS FROM THE ROOMS ARE REQUIRED.
  
 4) M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED FOR THE
 OCCUPANTS. IF AN O/A DUCT IS TO BE USED, PLEASE SHOW
 THE LOCATION OF THE DUCT, THE TYPE AND SIZE OF DUCT,
 AND THE LOCATION OF THE AIR INLET- SECTION 401.4 FBC M.
  
 5) M-1: IF AN O/A DUCT IS TO BE PROVIDED PLEASE PROVIDE
 AN AUTOMATICALLY CONTROLLED SHUTOFF DAMPER- SECTION
 C403.2.4.3 FBC- EC.
  
 6) M-1: THERE IS A NOTE INDICATING A DUCT SMOKE
 DETECTOR WILL BE INSTALLED IN THE RETRUN AIR SYSTEM OF
 THE NEW AIR HANDLER. PLEASE NOTE THAT DUCT SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY AIR SYSTEMS OF AIR
 HANDLERS WITH THE CAPACITIES EXCEEDING 2000 CFMS-
 SECTION 606.2.1 FBC M.
  
 7) M-1: THE AC CLOSET AND DOORS SHALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION- SECTION C403.2.9.2 FBC
 EC, AND SECTION 602.1 FBC M.
  
 8) M-1: MECHANICAL EXHAUST VENTILATION REQUIRED FOR THE
 TOILET ROOMS- SECTION 1203.5.2.1 FBC B AND TABLE
 403.3.1.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-02-07 Cont ID  
Sent By gjohnson Date 2020-02-07 Time 16:35 Rev Time 0.00
Received By gjohnson Date 2020-02-07 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-01-15 Cont ID  
Sent By gjohnson Date 2020-01-15 Time 11:30 Rev Time 0.00
Received By gjohnson Date 2020-01-14 Time 09:29 Sent To  
Notes
2020-01-14 15:54:083RD REVIEW:19081206
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING
 FIXTURE COUNT STATES SEPARATE FACILITIES SHALL NOT BE
 REQUIRED IN BUSINESS AND MERCANTILE OCCUPANCIES WITH A
 TOTAL FLOOR AREA OF 3000SQFT OR LESS THIS IS NOT
 CORRECT THE CODE DOES NOT PROVIDE A EXCEPTIONS USING
 SQFT. PLEASE SEE FBC PL 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 EXCEPTIONS:
  
 1)SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
  
 2)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 STRUCTURES OR TENANT SPACES WITH A TOTAL OCCUPANT LOAD,
 INCLUDING BOTH EMPLOYEES AND CUSTOMERS, OF 15 OR FEWER.
  
 3)SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 MERCANTILE OCCUPANCIES IN WHICH THE MAXIMUM OCCUPANT
 LOAD IS 100 OR FEWER.
  
 2. ON THE COVER SHEET THE NOTE UNDER THE PLUMBING
 FIXTURE COUNT STATES BUSINESS 1 WATER CLOSET PER 50
 THIS IS INCORRECT THE CODE IS 1 PER 25 FOR THE FIRST 50
 AND 1
 PER 50 FOR THE REMAINDER EXCEEDING 50 AND THE PLAN
 STATES 1 LAVATORY PER 80 THAT IS INCORRECT THE CODE IS
 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE
 REMAINDER EXCEEDING 80
 PER FBC PL TABLE 403.1
  
 3. SHT. P-1 SANITARY ISOMETRIC DRAWING THE SINKS IN THE
 BREAK ROOM AND EXAM ROOMS 1,2,3 ARE NOT VENTED THEY
 SHALL EACH BE INDIVIDUAL VENTED PER FBC PL 901.2.1
 910.1
  
 4.SHT. P-1 GENERAL EQUIPMENT NOTES DO NOT APPEAR TO
 PERTAIN TO THIS JOB PLEASE REMOVE ANY NOTES FOR KITCHEN
 EQUIPMENT GAS EQUIPMENT AND WALK IN FREEZERS OR ANY
 OTHER NOTE NOT FOR THIS JOB PER WPB AMEND TO FBC
 107.2.1
  
 5. PLEASE SHOW SIZE MANUFACTURE AND MODEL OF THE
 THERMAL EXPANSION TANK ON THE WATER HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 6. SHEET P-2 DETAIL #3 SHOWS 2 DIFFERENT HOT WATER
 RECIRCULATION PUMPS NONE IS SHOWN ON THE ISOMETRIC
 DRAWING OR FLOOR PLAN PLEASE CLARIFY IF A RECIRCULATION
 SYSTEM IS BEING USED SHOW IT ON ALL DRAWING AND PROVIDE
 MANUFACTURE MODEL NUMBER AND INSTILLATION GUIDE AND
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 AND FBC PL
 607.2,607.2.1,
  
 7. THE EXISTING COLD WATER SERVICE FOR THIS UNIT IS NOT
 CLEARLY SHOWN PLEASE CLEARLY SHOW SIZE LOCATION AND
 BACKFLOW DEVISE ONE WILL BE REQUIRED FOR THIS UNIT TO
 SEPARATE IT IF THERE ARE OTHER UNITS ON THE SAME
 SERVICE FROM METER. PER WPB UTILITIES CROSS CONNECTION
 MANUAL
  
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-21 Cont ID  
Sent By jesmith Date 2019-11-21 Time 14:01 Rev Time 0.00
Received By jesmith Date 2019-11-21 Time 08:27 Sent To  
Notes
2019-11-21 13:57:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW: 19081206
 PLUMBING COMMENTS: DENIED
 NOTE: A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS
 AS REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 1. RE: PLAN SHEET A-1; NOTE AT INFUSION ROOM, EXAM ROOM
 #1 AND BREAK ROOM SINK LOCATIONS READS ADA 36 " H
 COUNTER. TO BE CLEAR, PER FBC ACC 606.3 STATES THAT
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 WPB FBC 107.2.1, REMOVE THE NOTE AT THE THREE SINKS AND
 PROVIDE A NOTE REFLECTING THE REQUIREMENTS OF 606.3,
 REFERENCING THE THREE SINKS. ADDITIONALLY, THE EXISTING
 ADDED NOTE PERTAINING TO THE THREE SINKS AND FBC ACC
 SECTIONS HAS AN APPARENT TYPO; 21202 SHOULD BE 212.2.
 PLEASE CORRECT.
 2. RE: PLAN SHEET A-2, DETAILS 6 AND 7; REGARDING THE
 SHOWER,
 A. THE LAYOUT AS SHOWN DOES NOT FIT THE
 NARRATIVE/REQUIREMENTS OF FBC ACC SECTION 608; IT IS
 SUGGESTED THAT THE DESIGNERS MEET WITH THE BUILDING
 DEPARTMENT TO CONFIRM AN ACCEPTABLE DESIGN THAT WOULD
 PROVIDE COMPLIANCE. PLEASE SEE ADDITIONAL COMMENTS
 BELOW. PLEASE NOTE THAT THE COMMENTS ARE OBSERVATIONS
 AND SHALL NOT BE TAKEN AS CORRECTIONS THAT IF MADE
 WOULD LEAD TO A SATISFACTORY REVIEW FOR COMPLIANCE. IT
 IS THE DESIGNER'S RESPONSIBILITY TO PROVIDE A COMPLIANT
 DESIGN FOR THE SHOWER.
 B. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE.
 C. IT IS NOTED THAT THE SIDE WALL OF THE WATER CLOSET
 WOULD BE THE BACK WALL OF THE SHOWER IF CONSIDERED A
 ROLL-IN SHOWER. THERE IS A MINIMUM SIXTY (60) INCH
 CLEAR SPACE REQUIRED FOR THE LENGTH OF THE SAID BACK
 WALL. PER FBC ACC 608.2.2.1, A 30 INCH (760 MM) WIDE
 MINIMUM BY 60 INCH (1525 MM) LONG MINIMUM CLEARANCE
 (CLEAR FLOOR SPACE) SHALL BE PROVIDED ADJACENT TO THE
 OPEN FACE OF THE SHOWER COMPARTMENT.
 D. A CONTINUOUS GRAB BAR ON THE SAID BACK WALL SHALL BE
 A MAXIMUM OF 6 INCHES FROM THE TWO SIDE WALLS, AS
 PERTAINS TO THE SHOWER.
 E. GRAB BARS ON THE SAID SIDE WALLS SHALL BE A MAXIMUM
 OF 6 INCHES FROM THE SAID BACK WALL, AS PERTAINS TO THE
 SHOWER.
 F. THE ISSUE HERE IS THE WATER CLOSET AT THE FAR END OF
 THE SHOWER SPACE. THE SPACE IN ACCORDANCE WITH THE
 REQUIREMENTS OF FBC ACC 608.2.1 IS SUPPOSED TO BE CLEAR
 FROM SIDE WALL TO SIDE WALL OR IT MAY HAVE A SEAT ON A
 SIDE WALL. IF, THE THOUGHT IS THAT IT COULD DOUBLE AS A
 SEAT, THEN IT WOULD HAVE TO BE SHOWN TO MEET THE
 REQUIREMENTS OF FBC ACC 610.3, 610.3.1, 610.3.2.1 AND
 610.4. NOTE IT SHALL BE ADJACENT TO THE SHOWER
 CONTROLS.
 3. RE: PLAN SHEET A-2, DETAIL 1. PER WPB FBC 107.2.1,
 WATER CLOSET SPACE SHALL COMPLY WITH FBC 2017, NOT
 2010, 604.3.1 ACCESSIBILITY.
 4. RE: PLAN SHEET A-2, DETAILS 2 AND 3; PER FBC ACC
 609.4, GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, NOT TO THE CENTER. THIS IS A
 SECOND REQUEST.
 5. RE: PLAN SHEET A-2, DETAIL 4; PER FBC ACC 606.3, THE
 DRAWING ON THE RIGHT OF THE LAVATORY HAS A DIMENSION OF
 34 INCHES MINIMUM TO THE LIP OF THE LAVATORY; IT SHALL
 BE A MAXIMUM OF 34".
 6. RE: PLAN SHEET A-2, DETAIL 6 AND 7; PER FBC ACC
 604.7, TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES
 (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED
 TO THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
 7. RE: PLAN SHEET A-2, DETAIL 8; PER WPB FBC 107.2.1,
 PROVIDE IN THE DETAIL HOW THE ENTIRE ROOM WILL BE
 SEALED TO COMPLY WITH FBC PL 417.5.2 SHOWER LINING;
 INCLUDE DETAIL FOR SEALING THE WATER CLOSET VERTICAL
 DRAIN PIPE THROUGH THE FLOOR, INTEGRATING IT WITH THE
 LINER.
 8. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOM
 WITH 3" VENT THROUGH THE ROOF. EACH BATHROOM GROUP
 FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE WET
 VENT IN ACCORDANCE WITH FBC PL 912.1. CONNECT WET VENT
 BETWEEN THE WATER CLOSET AND THE SHOWER TO COMPLY.
 9. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOMS #1
 AND #2. WATER CLOSETS ARE INTEGRALLY TRAPPED FIXTURES.
 PROVIDING A TRAP IN THE ROUGH DRAIN PIPING AS SHOWN ON
 THE ISOMETRIC CONSTITUTES A DOUBLE TRAP AND AS SUCH
 DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC PL909.1.
 PER FBC 107.2.1, ELIMINATE THE TRAP AND PROVIDE A
 VERTICAL WASTE PIPE EXTENDING FROM THE HORIZONTAL
 PIPING TO THE FLOOR FLANGE POINT OF CONNECTION.
 10. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; BATHROOMS
 #1 AND #2. SHOWER DRAINS IN BATHROOMS SHALL BE PROVIDED
 WITH TRAP SEAL PROTECTION IN ACCORDANCE WITH THE
 REQUIREMENTS OF FBC PL 1002.4.1.
 11. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; PER WPB FBC
 107.2.1, NOTE THAT 3 INCH PIPE DOWN TO FIRST FLOOR
 SANITARY SHALL NOT DISCHARGE THROUGH A FIRST FLOOR VENT
 TO SHOW COMPLIANCE WITH THE REQUIREMENTS OF FBC PL
 CHAPTER 9.
 12. RE: PLAN SHEET P-1, SANITARY ISOMETRIC; ALL SINKS.
 WASTE FOR SINKS SHALL RISE VERTICALLY TO A POINT ABOVE
 THE FLOOR BEFORE THE INDIVIDUAL FIXTURE DRAIN SHALL BE
 ALLOWED TO CONNECT TO IT TO INSURE COMPLIANCE WITH FBC
 PL 1002.1. THE FIXTURE DRAINS SHALL BE INDIVIDUALLY OR
 COMMON VENTED IN ACCORDANCE WITH FBC PL SECTIONS 910
 AND 911. COMMON VENTS SHALL BE SIZED IN ACCORDANCE WITH
 FBC PL TABLE 911.3.
 13. RE: PLAN SHEET P-2, WATER HEATER SCHEDULE; PER WPB
 FBC 107.2.1, REFER TO MANUFACTURER'S SPECIFICATION
 SHEET ON
 HTTPS://WWW.RHEEM.COM/PRODUCT/LIGHT-DUTY-ELD80-FTB.
 OPEN THE DOCUMENTS TAB AND FIND SPECIFICATION SHEET PDF
 AT BOTTOM OF DOCUMENTS. PROVIDE FULL ELECTRICAL
 CHARACTERISTICS OF THE WATER HEATER INCLUSIVE OF THE
 VOLTAGE (I.E. 240V), WATTAGE (I.E. 4500 WATTS
 NON-SIMULTANEOUS, SINGLE PHASE), STORAGE CAPACITY (I.E.
 80 GALLONS). RECONCILE ELECTRICAL CHARACTERISTICS WITH
 PLAN SHEET E-1 NEW PANEL A SCHEDULE.
 14. RE: PLAN SHEET P-2, WATER HEATER; PER WPB FBC
 107.2.1, PLEASE SHOW PAN DRAIN ROUTING AND POINT OF
 TERMINATION IN COMPLIANCE WITH FBC PL 504.7.2. THIS IS
 A SECOND REQUEST.
 15. RE: PLAN SHEET P-2, HOT WATER DISTRIBUTION; PER WPB
 FBC 107.2.1, PROVIDE TYPE, SIZE AND LOCATION OF THERMAL
 EXPANSION CONTROL DEVICE AS REQUIRED BY FBC PL 607.3
 16. RE: PLAN SHEET P-2, WATER RISER DIAGRAM AND PLAN
 VIEW; PER WPB FBC 107.2.1, PROVIDE SOURCE, SIZE AND
 LOCATION OF DOMESTIC WATER SERVICE/SUPPLY. PROVIDE
 PROTECTION OF WATER SUPPLE AS REQUIRED BY FBC PL
 SECTION 608
 17. RE: PLAN SHEET P-2, WATER RISER DIAGRAM AND PLAN
 VIEW; PER WPB FBC 107.2.1, PROVIDE AND SHOW WATER TO
 THE WATER CLOSETS AND THE SHOWERS. INCLUDE SIZING.
 18. RE: PLAN SHEET P-2, PLUMBING FIXTURE SCHEDULE/FLOW
 RATE REGARDING THE WATER HEATER; MANUFACTURER HAS
 PROVIDED 3/4 INCH WATER CONNECTIONS. AS SUCH IN KEEPING
 WITH MANUFACTURES RECOMMENDATIONS, WATER IN AND OUT
 SHALL BE SIZED 3/4 INCH.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19081206 1920 PALM BEACH LAKES BLVD # 214
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By gjohnson Date 2019-09-16 Time 12:21 Rev Time 0.00
Received By gjohnson Date 2019-09-13 Time 13:47 Sent To  
Notes
2019-09-16 12:22:121ST REVIEW: 19081206
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT A-1 THERE ARE NOTES IN THE BATHROOM REFERRING TO
 A SHOWER NONE IS SHOWN ON THE PLAN PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. THE INSIDE WIDTH OF THE BATHROOMS NEEDS TO BE A MIN
 OF 7'1" TO PROVIDE THE REQUIRED CLEAR FLOOR SPACE FOR
 ACCESSIBILITY. PER WPB AMEND TO FBC 107.2.1
  
 3.SHOW DIMENSIONS ON THE CLEAR FLOOR FOR THE LAVATORY
 AND TOILET. PER FBC ACC 604.3.1 SIZE. CLEARANCE AROUND
 A WATER CLOSET SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL.
 606.2-305.3 SIZE. THE CLEAR FLOOR OR GROUND SPACE SHALL
 BE 30 INCHES MINIMUM BY 48 INCHES MINIMUM.
  
 4.THE BREAK ROOM SINK, INFUSION SINK AND AT LEAST ONE
 OF THE EXAM ROOM SINK SHALL COMPLY WITH ACCESSIBILITY.
 PER FBC ACC 212.2, 212.3, 606.2, 606.3
  
 5. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 6. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.PER FBC ACC 603.3
  
 7. SHT. A-2 DETAIL #4 THE DRAWING ON THE RIGHT OF THE
 LAVATORY HAS A DIMENSION OF 3'4" TO THE LIP OF THE
 LAVATORY IT SHALL BE A MAXIMUM OF 34". PER FBC ACC
 606.3
  
 8.SHT. P-1 SANITARY THERE SHALL BE AT LEAST ONE VENT
 SHALL EXTEND THROUGH ROOF. PER FBC PL 904.1
  
 9. SHT. P-1 THE SANITARY ISOMETRIC SHOWS A SHOWER THE
 FLOOR PLAN IS MISSING A SHOWER PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 10. THE BREAK ROOM SINK SHALL CONNECT TO THE BUILDING
 DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL
 912.1
  
 11. SHT P-1 ON THE THE SANITARY ISOMETRIC THE VENTS
 SHALL BE SHOWN ON THE LAVATORY STACKS. PER FBC PL
 901.2.1
  
 12. SHT P-2 SHUT OFF VALVES ARE ON ALL DOWN FED WATER
 PIPING SHOWN ON THE WATER ISOMETRIC. PER FBC PL
 606.1(5)
  
 13.PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC PL
 504.7.2,607.3
  
 14.LIST MANUFACTURE SIZE AND MODEL OF THE WATER HEATER.
 PER WPB AMEND TO FBC 107.2.1
  
 15. PLEASE SIZE THE PIPING ON THW WATER ISOMETRIC. PER
 WPB AMEND TO FBC 107.2.1
  
 16. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-09-05 Cont ID  
Sent By llouie Date 2019-09-05 Time   Rev Time  
Received By llouie Date 2019-09-05 Time   Sent To  
Notes
2019-09-05 09:25:33CHANGE OF USE TO A MEDICAL OFFICE. PROFESSIONAL OFFICES
 PERMITTED IN THE GC ZONING DISTRICT.