| 2019-08-26 16:33:40 | 08/26/2019 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GENERATOR GAS EQUIPMENT |
| | TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 2. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC RES. SECS. G2413.2 AND G2404.3. |
| | |
| | 3. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC. G2421.2. |
| | |
| | 4. LABEL SHUTOFF VALVE ON GAS ISOMERIC PER THE 2017 FBC |
| | RES. SEC. G2401.1.3. |
| | |
| | 5. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| | FBC RES. SEC. G2419.2 |
| | |
| | 6. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 8. A SUB PLUMBING PERMIT IS REQUIRED FOR TANKLESS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 9. TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE |
| | COST OF ALL EQUIPMENT INCLUDING TANKLESS. PROVIDED ON |
| | THE BONA FIDE CONTRACT PER THE WPB AMENDMENTS TO THE |
| | FBC 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |