Plan Review Details - Permit 19081141
Plan Review Stops For Permit 19081141
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-09-16 Cont ID  
Sent By jwitmer Date 2019-09-16 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2019-09-16 Time 09:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By rmcdouga Date 2019-11-12 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2019-11-07 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By jwitmer Date 2019-09-16 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2019-09-16 Time 09:39 Sent To  
Notes
2019-09-16 14:41:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081141
 ADD: 7391 RIVERWALK CIR.
 CONT: PALM BEACH COUNTY CONTRACTOR CORP.
 TEL: 561-257-3706 [email protected]
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 16/2019
 ACTION: DENIED
  
 1) SHEET 1.1. SHEET 1.1 DOES NOT SHOW ANY DRINKING
 FOUNTAINS. PLEASE SHOW COMPLIANCE WITH 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 2) THIS SHEET 1.1. THERE IS NO DIMENSIONS NOR DETAILS
 FOR THE RESTROOMS. MISSING ENLARGED FLOOR PLAN DETAIL
 SHOWING COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 2A) 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL
 BE 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR
 FROM THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 2B) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
  
 2C) 606 LAVATORIES AND SINKS. 2017 FBC-ACCESSIBILITY
 CODE 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 2D) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2E) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS
 FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED
 METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS
 MINIMUM.
  
 2F) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
  
  
 2G) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2H) GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2I) TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE
 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-18 Cont ID  
Sent By jpearson Date 2019-11-18 Time 11:17 Rev Time 0.00
Received By jpearson Date 2019-11-18 Time 11:17 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By jpearson Date 2019-09-17 Time 14:20 Rev Time 0.00
Received By jpearson Date 2019-09-17 Time 13:49 Sent To  
Notes
2019-09-17 14:20:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE CLARIFICATION FOR LIGHTING PLAN. ARE THESE
 NEW OR EXISTING FIXTURES? SCOPE OF WORK FOR LIGHTING
 NOT CLEAR. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-09-17 Cont ID  
Sent By jpearson Date 2019-09-17 Time 14:20 Rev Time 0.00
Received By jpearson Date 2019-09-17 Time 14:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-23 Cont ID  
Sent By pleduc Date 2019-08-23 Time   Rev Time 0.00
Received By pleduc Date 2019-08-23 Time 14:28 Sent To  
Notes
2019-08-23 14:29:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-27 Time 15:01 Sent To  
Notes
2019-12-02 15:01:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-28 Time 15:00 Sent To  
Notes
2019-10-29 15:00:51B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-22 Time 16:12 Sent To  
Notes
2019-08-22 16:12:16B23

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By ccole Date 2019-12-04 Time 15:31 Rev Time 0.00
Received By ccole Date 2019-12-04 Time 14:53 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-11-08 Cont ID  
Sent By ccole Date 2019-11-08 Time 10:08 Rev Time 0.00
Received By ccole Date 2019-11-08 Time 08:56 Sent To  
Notes
2019-11-08 10:45:342ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19081141
 11/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2.1: I WAS UNABLE TO LOCATE A PERMIT FOR THE
 NEW 5-TON SYSTEM PER THE NOTE ON THE PLAN SHEET THAT
 INDICATES IT WAS DONE UNDER A SEPARATE PERMIT. I
 CHECKED THE ADDRESSES ON THE PLANS AND ON THE PERMIT
 APPLICATION AND UNDER THE APPLICATION ADDRESS OF 7391
 RIVERWALK CIR THERE WAS A 2.5 TON AC CHANGEOUT PERMIT
 ISSUED ON 12/04/2018 (PERMIT #18120044).
 PLEASE NOTE THE PLANS ARE INDICATING AN INCORRECT
 PROJECT ADDRESS- 7459 RIVERWALK CIR.- PLEASE CORRECT.
  
 2) SHEET 2.1: 2ND REQUEST FOR AN AC EQUIPMENT SCHEDULE
 AND VENTILATION CALCULATIONS ON THE PLAN, AND AC
 COOLING AND HEATING CALCULATIONS TO BE SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By ccole Date 2019-09-17 Time 12:00 Rev Time 0.00
Received By ccole Date 2019-09-17 Time 08:31 Sent To  
Notes
2019-09-17 12:21:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081141
 9/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2.1: PROVIDE AN AC EQUIPMENT SCHEDULE ON THE
 PLAN- SECTION 107.1 WPB
  
 2) 2.1: THE OUTSIDE AIR CALCULATIONS ARE INDICATING
 1046 CFMS OF O/A PROVIDED BY AN RTU, HOWEVER A 4-TON
 SPLIT SYSTEM IS SHOWN ON THE PLAN. PLEASE NOTE THAT A
 4-TON SYSTEM WILL GENERALLY PROVIDE 1600 CFMS OF AIR
 AND CAN TYPICALLY CONDTION AND DEHUMIDIFY APPROXIMATELY
 15-25% OF THAT VOLUME IN OUTSIDE AIR, OR IN THIS CASE,
 APPROXIMATELY 400 CFMS MAX. IN ORDER TO PROVIDE 1046
 CFMS OF O/A A LARGER CAPACITY SYSTEM IS REQUIRED.
  
 3) 2.1: PROVIDE AC COOLING AND HEATING CALCULATIONS FOR
 THE NEW SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC
 EC, AND SECTION 312.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-11-15 Cont ID  
Sent By gjohnson Date 2019-11-15 Time 09:09 Rev Time 0.00
Received By gjohnson Date 2019-11-14 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By gjohnson Date 2019-09-13 Time 14:03 Rev Time 0.00
Received By gjohnson Date 2019-09-13 Time 14:03 Sent To  
Notes
2019-09-13 14:41:291ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE OVERALL DIMENSIONS FOR THE BATHROOM AND SHOW
 DIMENSIONS ON THE CLEAR FLOOR SPACE FOR ACCESSIBILITY.
 PER WPB AMEND TO FBC 107.2.1 ADDITIONAL INFORMATION
 REQUIRED
  
 2. SHOW THE COMPLIANCE WITH THE FOLLOWING FBC ACC
 602.1 GENERAL. DRINKING FOUNTAINS SHALL COMPLY WITH 307
 AND 602.
  
 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
  
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR
  
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
  
 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
  
 604.4 SEATS. THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF
 THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A
 LIFTED POSITION.
  
 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE,
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]