Plan Review Details - Permit 19080997
Plan Review Stops For Permit 19080997
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By jwitmer Date 2019-09-09 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2019-09-08 Time 16:42 Sent To  
Notes
2019-09-09 08:42:29ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By jwitmer Date 2019-09-09 Time 08:41 Rev Time 0.00
Received By jwitmer Date 2019-09-08 Time 16:42 Sent To  
Notes
2019-09-09 08:41:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080997
 ADD: 329-B CLEMATIS ST.
 CONT: BLUE WATER VENTURES OF PALM BEACH
 TEL: 561-339-6128
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY SEPT. 09/ 2019
 ACTION: DENIED
  
 1) PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 NEEDS TO BE CLARIFIED. UNDER THE DESCRIPTION OF WORK
 THE APPLICATION INDICATES A NEW BATHROOM ADDITION WILL
 BE ADDED TO THE BUILDING. THE DEFINITION OF AN ADDITION
 IS AN EXTENSION OR INCREASE IN FLOOR AREA, NUMBER OF
 STORIES OR HEIGHT OF A BUILDING OR STRUCTURE.
 PLEASE NOTE THAT IS NOT THE CASE THE FOOTPRINT IS NOT
 BEING INCREASED, THIS IS AN COMMERCIAL INTERIOR
 REMODEL.
  
 2) SHEET A1:
 2A) SHEET A1 INDICATES THIS IS A CHANGE OF OCCUPANCY.
 IF SO PLEASE INDICATE WHAT THE CHANGE OF OCCUPANCY IS?
 ADDITIONAL INFORMATION IS REQUIRED. IT WOULD APPEAR
 THAT THIS IS STILL AN A2 OCCUPANCY BUT THE CHANGE IS A
 DENSER (MORE OCCUPANTS) AND THE CREATION OF A NEW
 UNISEX RESTROOM. PLEASE CORRECT THE FLOOR PLAN WITH THE
 REMOVAL OF CHANGE IN OCCUPANCY. PLEASE PROVIDE WHAT
 LEVEL OF ALTERATION THIS IS UNDER THE 2017 EXIST.
 BUILD. CODE WORK AREA METHOD OF ALTERATION? EXIST.
 BUILDING CODE SECTION 503-505. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2B) THIS REVIEW ONLY A FLOOR PLAN WAS SUBMITTED, NO
 LIFE SAFETY PLAN WAS SUBMITTED. PLEASE INCLUDE ON THE
 LIFE SAFETY PLAN THE OCCUPANT LOAD BREAK DOWN FOR EACH
 AREA. PLEASE ALSO SHOW THE EXIT ACCESS AISLE, PLEASE
 NOTE NO OCCUPANT LOAD CAN BE TAKEN FOR THE MEANS OF
 EGRESS. TRAVEL DISTANCES. 2 MEANS OF EGRESS SINCE THE
 OCCUPANT LOAD IS 50 OR MORE. PLEASE NOTE THE 2017 FBC-B
 SECTION 1016.2(3) EGRESS THROUGH INTERVENING SPACES
 DOES ALLOW EGRESS THROUGH INTERVENING SPACES AS LONG AS
 THE EXIT ACCESS SHALL NOT PASS THROUGH A ROOM THAT CAN
 BE LOCKED TO PREVENT EGRESS, THIS ROOM IS BEING
 DECLARED AN OFFICE. IT WOULD APPEAR THE LIFE SAFETY
 CODES NFPA MAYBE THE STRICTER OF THE 2 CODES. WHEN
 THERE IS A DISCREPANCY IN THE CODES, THE STRICTER OF
 THE 2 CODES SHALL RULE.
  
 2C) THE OTHER ISSUE THAT THE FIRE SAFETY CODE (NFPA)
 WILL RULE ON IS THE WIDTH OF THE EGRESS PATH FOR THE
 OCCUPANT LOAD DECLARED. THE 2017 FBC-B GIVES UNDER THE
 SECTION 1005.3.2 SIZING OR REQUIRED CAPACITY BASED ON
 THE OCCUPANT LOAD, FACTOR OF 0.2 INCH PER OCCUPANT.
 SECTION 1018.2 GIVES MINIMUM CLEAR WITH FOR B & M
 OCCUPANCIES. SECTION 1018.2 AISLES IN ASSEMBLY SPACES,
 AISLES AND AISLE ACCESS BUT THIS IS FOR TABLE AND
 CHAIRS, NOT FOR STANDING ONLY. AGAIN THE FIRE SAFETY
 CODES (NFPA) WILL BE THE STRICTER OF THE 2 CODES AND
 GOVERN THE ACCESS AISLE WIDTHS.
  
 3) SHEET A1 PLEASE PROVIDE A DETAIL A LARGER FLOOR PLAN
 OF THE NEW UNISEX RESTROOM AND ELEVATION VIEWS WITH
 DIMENSIONS FOR ROOM, CLEAR FLOOR SPACE, DIMENSIONS FOR
 ALL FIXTURES- HEIGHT FOR THE LAV, WATER CLOSET, MIRROR,
 GRAB BARS, TOILET PAPER DISPENSERS, ETC. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
 604.3.1
 604.3.2.
 606-1-5
 603.3
 609.4
 604.7
  
 4A) PLEASE NOTE THE BAR DOES NOT SHOW A DROPPED SECTION
 FOR A PERSON IN A WHEEL CHAIR AND COMPLIANCE WITH:
 2017 ACCESS. CODE 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
  
 4B)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By jpearson Date 2019-09-13 Time 09:42 Rev Time 0.00
Received By jpearson Date 2019-09-13 Time 09:38 Sent To  
Notes
2019-09-13 09:42:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-21 Cont ID  
Sent By pleduc Date 2019-08-21 Time   Rev Time 0.00
Received By pleduc Date 2019-08-21 Time 14:02 Sent To  
Notes
2019-08-21 14:23:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE INDICATIONS OF CHANGE OF OCCUPANCY AS WELL
 AS ADD ONE UNI-SEX BATHROOM
  
 PLEASE CLARIFY WHAT THE INTENT OF THIS PERMIT IS FOR.
  
  
 2) IF THIS IS A CHANGE OF OCCUPANCY, WHAT IS THE
 PROPOSED OCCUPANCY?
  
 IT APPEARS TO BE A BAR/NIGHCLUB WHICH IS ASSEMBLY IF
 OVER 50 PEOPLE.
  
 PLEASE CLARIFY OCCUPANCY AND PROVIDE A LIFE SAFETY PLAN
 SHOWING ALL DIMENSIONS, OCCUPANCY LOADS, TRAVLE
 DISTANCES, FIRE ALARM AND/OR FIRE SPRINKLERS, EXIT
 SIGNS, EXITS LEADING TO PUBLIC WAYS, EMERGENCY LIGHTS,
 ETC.
  
  
 3) THERE IS AN OFFICE AREA IN THE REAR OF THE
 OCCUPANCY. THE 2ND EXIT FROM THE ASSEMBLY AREA CAN NOT
 PASS THRU THIS OFFICE AREA.
  
 PER NFPA 101
  
 12.2 MEANS OF EGRESS REQUIREMENTS.
 12.2.1 GENERAL. ALL MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 CHAPTER 7 AND THIS CHAPTER.
  
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF
 EGRESS.
 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER
 OBJECTS SHALL
 OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE
 FROM, OR
 VISIBILITY THEREOF.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 4) THERE IS AN INDICATION OF A PROPOSED BAR. IS THIS
 PROPOSED BAR PART OF THIS PERMIT? THERE ARE NO DETAILS.
  
 PLEASE CLARIFY AND SEE # 1 & 2 ABOVE, PROVIDE DETAILS
 AS APPLICABLE.
  
  
 5) THERE IS NO DOOR SCHEDULE TO CONFIRM EXIT HARDWARE.
  
 PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WITH
 THE ASSEMBLY CHAPTER(12) OF NFPA 101 AND MEANS OF
 EGRESS (7)
  
  
 6) THERE ARE NO INDICATIONS OF A EXISTING FIRE
 SPRINKLER OF FIRE ALARM SYSTEM.
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AN
 EVALUATION OF CODE COMPLIANT COVERAGE BY A CERTIFIED
 CONTRACTOR.
  
 ANY WORK ON THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE INDICATE EXISTING SYSTEMA AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 12:52 Rev Time 0.00
Received By hmoser Date 2019-08-20 Time 15:25 Sent To  
Notes
2019-08-20 15:25:21B15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 12:51 Rev Time 0.00
Received By hmoser Date 2019-09-13 Time 11:36 Sent To I
Notes
2019-09-13 12:51:48PLAN DENIED
 NO MECHANICAL PLAN SUBMITTED HM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-11 Cont ID  
Sent By gjohnson Date 2019-09-11 Time 12:18 Rev Time 0.00
Received By gjohnson Date 2019-09-10 Time 17:14 Sent To  
Notes
2019-09-11 08:58:311ST REVIEW: 19080997
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. WITH AN OCCUPANT LOAD OF 160 ITS REQUIRED TO HAVE
 TWO TOILETS FOR WOMEN AND TWO FOR MEN OR ONE TOILET AND
 ONE URINAL THE MENS BATHROOM CAN NO LONGER BE
 CONSIDERED A SINGLE USER BATHROOM AND WILL NEED THE
 FOLLING MODIFICATION FOR CODE COMPLIANCE.
 A) THE TOILET AND LAVATORY WILL NEED PARTITIONS FOR THE
 ACCESSIBLE STALL AND SHALL COMPLY WITH FBC ACC CH 6 AND
 FBC PL 405.3.4
 B) THE URINAL SHALL HAVE PARTITIONS AND BE OUT SIDE THE
 ACCESSIBLE STALL. PER FBC PL 405.3.5
 C) A LAVATORY IS REQUIRED OUTSIDE THE ACCESSIBLE TOILET
 STALL.PER FBC ACC 213.3.4
  
 2. PROVIDE A WATER ISOMETRIC.PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 4. SHEET A1 PLEASE PROVIDE A DETAIL A LARGER FLOOR PLAN
 OF THE NEW UNISEX RESTROOM AND ELEVATION VIEWS WITH
 DIMENSIONS FOR ROOM, CLEAR FLOOR SPACE, DIMENSIONS FOR
 ALL FIXTURES- HEIGHT FOR THE LAV, WATER CLOSET, MIRROR,
 GRAB BARS, TOILET PAPER DISPENSERS, ETC. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
 604.3.1
 604.3.2.
 606-1-5
 603.3
 609.4
 604.7
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
  
  
  