Plan Review Details - Permit 19080894
Plan Review Stops For Permit 19080894
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 11:14 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 11:14 Sent To  
Notes
2019-10-30 11:18:11MET WITH MARCO. HE SAID THEY ARE INSTALLING THE
 CONNECTORS ON ENTIRE HOUSE. GAVE HIM COPY OF THE
 PRESCRIPTIVE METHOD SEC. 706.8.1.3 FBC-EXISTING
 BUILDING. HE AGREED TO USE THE PRESCRIPTIVE METHOD AND
 SIMPSON HGA10 CONNECTOR WILL BE INSTALLED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 10:59 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 10:22 Sent To  
Notes
2019-10-30 10:59:31RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 RESPONSE:
 HURRICANE MITIGATION RETROFIT LETTER FROM MARK MESIANO
 (PROFESSIONAL ENGINEER) IS TOO GENERAL AND IT DOESN'T
 PROVIDE SPECIFIC INFORMATION AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS. THERE ARE TOO MANY RIGHT ANGLE
 GUSSET BRACKETS IN THE MARKET. ENGINEER NEED TO BE
 SPECIFIC. IN ADDITION, THE ENGINEER IS NOT CLEAR WHERE
 THE CONNECTORS ARE GOING TO BE INSTALLED. ARE THEY
 GOING TO BE INSTALLED JUST ON THE CORNER AREAS OR ON
 ENTIRE HOUSE. IF CORNER AREAS, THEN PROVIDE DIMENSIONS
 OF CORNER AREAS TO BE COVERED. SEC. 107.2.1 CITY
 AMENDMENTS
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-22 Cont ID  
Sent By jgomez Date 2019-10-22 Time 10:58 Rev Time 0.00
Received By jgomez Date 2019-10-22 Time 10:51 Sent To  
Notes
2019-10-22 11:19:55RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 RESPONSE:
 CONTRACTOR SUBMITTED PALM BEACH COUNTY FORM 200 SIGNED
 BY JOSEPH PISCIOTTI (BUILDING CONTRACTOR). THE
 INFORMATION SHOWN ON THE FORM DOESN'T COMPLY WITH THE
 REQUIREMENTS OF SEC. 706.8.1 FBC-EXISTING BUILDING.
 THIS IS NOT AN ENGINEERED DESIGN OR INFORMATION
 SUBMITTED DOESN'T COMPLY WITH THE PRESCRIPTIVE RETROFIT
 SOLUTIONS PROVIDED IN SEC. 706.8.1.1. THE
 SPECIFICATIONS FOR THE STRAP ARE INCOMPLETE. CONTRACTOR
 HIMSELF SPECIFIES THAT THE ADDITIONAL FASTENERS IN THE
 EXISTING ANCHORS DON'T PROVIDE COMPLIANCE. IN ADDITION,
 CONTRACTOR SPECIFIED THAT THERE ARE NO EXISTING ANCHORS
 AND FASTENERS AT THE LOCATIONS PROPOSED FOR MITIGATION
 RETROFIT. EXTERIOR WALLS ARE WOOD, NOT CBC. THE ROOF
 GEOMETRY IS GABLE AND THERE IS A FLAT ROOF ALSO. THERE
 IS NOT ADDRESS IDENTIFYING THE HOUSE.
 NEED TO PROVIDE AND ENGINEERED DESIGN OR PROVIDE
 PRESCRIPTIVE DESIGN. SEC. 706.8.1 FBC-RESIDENTIAL.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By jgomez Date 2019-08-19 Time 15:21 Rev Time 0.00
Received By jgomez Date 2019-08-19 Time 14:44 Sent To HIST
Notes
2019-08-19 15:26:03RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY
 WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC.
 706.8 FBC-EXISTING-BUILDING.
  
 SEC. 706.8:
 WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT
 SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND
 REPLACED ON A BUILDING THAT IS LOCATED IN THE
 WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
 (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 706.8.1.
 (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF REROOFING.
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-21 Cont ID  
Sent By jgomez Date 2019-08-20 Time 11:01 Rev Time 0.00
Received By aborngra Date 2019-08-21 Time 16:09 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 11:26 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 10:59 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-22 Cont ID  
Sent By jgomez Date 2019-10-22 Time 11:20 Rev Time 0.00
Received By jgomez Date 2019-10-22 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-22 Cont ID  
Sent By lmarchan Date 2019-08-22 Time 10:23 Rev Time 0.00
Received By lmarchan Date 2019-08-16 Time 14:52 Sent To  
Notes
***NONE***