Plan Review Details - Permit 19080850
Plan Review Stops For Permit 19080850
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-27 Cont ID  
Sent By pvalenti Date 2019-08-27 Time 13:25 Rev Time 0.00
Received By pvalenti Date 2019-08-27 Time 13:22 Sent To  
Notes
2019-08-27 13:40:49***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION PLEASE PROVIDE:
  
 1. FBC B 107.2.1 PROVIDE LAYOUT/FLOOR PLAN SHOWING
 LOCATIONS OF WORK.
 2. MAINTAIN FIRE RATING WITH DRYWALL AT SEPERATION
 WALLS AND MOISTURE BARRIERS WITH CEMENT BOARD AS
 REQUIRED BY CODE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 14:49 Rev Time 0.00
Received By lcrespo Date 2019-08-29 Time 11:04 Sent To  
Notes
2019-08-30 11:04:21RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-27 Cont ID  
Sent By pvalenti Date 2019-08-27 Time 13:41 Rev Time 0.00
Received By pvalenti Date 2019-08-16 Time 14:52 Sent To  
Notes
2019-08-19 14:52:19PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 14:49 Rev Time 0.00
Received By lcrespo Date 2019-08-30 Time 14:49 Sent To  
Notes
2019-08-30 14:50:2008/30/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By lcrespo Date 2019-08-20 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2019-08-20 Time 14:13 Sent To  
Notes
2019-08-20 14:14:0108/20/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. PLUMBING PERMIT REQUIRED BY A LICENSED CONTRACTOR
 AND ALL PLUMBING MUST COMPLY WITH THE FLORIDA BUILDING
 CODE 2017 6TH EDITION.
  
 2. SHOW A LAYOUT OF UNIT AND INDICATE ON THE PLANS IF
 THE LOCATION OF SHOWER HEAD AND VALVE, THIS MAY BE DONE
 BY HAND (NOT IN PENCIL BY CONTRACTOR), WPB AMENDMENTS
 TO THE 2017 TO FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4) THE ADDRESS OF PROJECT OR RESIDENCE MUST BE ON PLAN,
 WPB AMENDMENTS TO THE 2017 TO FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  