Plan Review Details - Permit 19080838
Plan Review Stops For Permit 19080838
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By cthroop Date 2019-09-09 Time 16:24 Rev Time 0.00
Received By cthroop Date 2019-09-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 15:04 Rev Time 0.00
Received By cthroop Date 2019-08-21 Time 15:03 Sent To  
Notes
2019-08-21 15:07:58BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 *
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER).
 4. STATED VALUE OF WORK.
 5. EXISTING SITE CONDITIONS:
 A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL)
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-09 Cont ID  
Sent By cthroop Date 2019-09-09 Time 16:24 Rev Time 0.00
Received By cthroop Date 2019-08-27 Time 16:41 Sent To  
Notes
2019-08-27 16:41:42RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 15:08 Rev Time 0.00
Received By cthroop Date 2019-08-15 Time 13:31 Sent To  
Notes
2019-08-16 13:31:18BLDG MISC 1