Plan Review Details - Permit 19080828
Plan Review Stops For Permit 19080828
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-25 Cont ID  
Sent By jleahy Date 2019-10-25 Time 07:39 Rev Time 0.00
Received By jleahy Date 2019-10-25 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-08 Cont ID  
Sent By sathomas Date 2019-10-23 Time 09:35 Rev Time 0.00
Received By jleahy Date 2019-10-08 Time 09:21 Sent To  
Notes
2019-10-08 09:22:12SEE ADDRESS COMMENTS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By fgiaquin Date 2019-09-10 Time 06:27 Rev Time 0.00
Received By fgiaquin Date 2019-09-10 Time 06:00 Sent To I
Notes
2019-09-10 06:27:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ACCESS CONTROL IS REQUIRED TO BE A SEPARATE STAND
 ALONE PERMIT AS PER THE BUILDING OFFICIAL. FBC 105.1
  
 2. PLANS PROVIDED ARE DIGITALLY SIGNED AND ARE NOT
 CONSIDERED TO BE SIGNED OR SEALED PER FLORIDA STATUTES
 AND F.A.C.
  
 PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 3. THE UL OR OTHER NRTL (NATIONALLY RECOGNIZED TESTING
 LABORATORY) LISTING HAS NOT BEEN PROVIDED FOR THE
 FOLLOWING ITEMS:
  
 AXIS F1025 CAMERA
  
 AXIS M3105-LVE
  
 AXIS P1245
  
 AXIS P3225-LV MKII
  
 DUO 240 INSTRUSION DETECTION DEVICE
  
 FLEX POWER RS SERIES RACK MOUNT SYSTEM.
  
 PLEASE PROVIDE UL OR OTHER NRTL LISTINGS. FBC 107.2.1
 NEC 90.7, 110.2, 110.3B
  
 4. INCORRECT ADDRESS ON PLANS. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By sathomas Date 2019-09-19 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-10-23 Time 00:00 Sent To E
Notes
2019-09-19 15:17:18THE FOLLOWING COMMENTS WERE NOT ADDRESSED DURING THIS
 SUBMISSION CYCLE:
  
 1. ADDRESS TO BE CORRECTED ON COVER SHEET. - COMPLIED
 10/23/19
 2. ACCESS CONTROL RISER DIAGRAM INDICATED ACS 14 & 15,
 WHILE PALN SHOWS ACS 15 & 16. - COMPLIED 10/23/19
 3. NO SPEC SHEET PROVIDED FOR KEY OVERRIDE SWITCH
 (HONEYWELL 4005K801) - COMPLIED 10/23/19
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-21 Cont ID  
Sent By sathomas Date 2019-08-21 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-08-21 Time 00:00 Sent To E
Notes
2019-08-21 12:41:171. ADDRESS TO BE CORRECTED ON COVER SHEET.
 2. ACCESS CONTROL RISER DIAGRAM INDICATED ACS 14 & 15,
 WHILE PALN SHOWS ACS 15 & 16.
 3. NO SPEC SHEET PROVIDED FOR KEY OVERRIDE SWITCH
 (HONEYWELL 4005K801)
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-25 Cont ID  
Sent By jleahy Date 2019-10-25 Time 07:39 Rev Time 0.00
Received By jleahy Date 2019-09-17 Time 14:03 Sent To  
Notes
2019-09-18 14:03:33RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-10 Cont ID  
Sent By fgiaquin Date 2019-09-10 Time 06:28 Rev Time 0.00
Received By fgiaquin Date 2019-08-15 Time 13:22 Sent To  
Notes
2019-08-16 13:22:36ROUTED TO FIRE INBOX