| 2019-09-09 14:07:51 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | ADVISORY: PERMIT TYPE HAS BEEN CHANGED FROM INTERIOR |
| | DEMO TO INTERIOR WORK TO COMPLY WITH CE 19020179 AS TO |
| | ILLEGAL CONVERSION TO 3 UNIT BUILDING. ZONING FOR THIS |
| | PARCEL IS LIMITED TO 1 SINGLE FAMILY RESIDENCE. |
| | |
| | 1. PROVIDE AN EXISTING FLOOR PLAN OF STRUCTURE. |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: AS APPLICABLE |
| | |
| | 2. PROVIDE A PROPOSED FLOOR PLAN. |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: AS APPLICABLE |
| | |
| | 3. ALL ILLEGAL WORK, INCLUDING BUT NOT LIMITED TO |
| | MECHANICAL, ELECTRICAL & PLUMBING SYSTEMS SHALL BE |
| | REMOVED. |
| | |
| | 4. DESINER SHALL PRINT NAME AND SIGN PLANS. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | 5. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |