Plan Review Details - Permit 19080722
Plan Review Stops For Permit 19080722
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-09-06 Cont ID  
Sent By jwitmer Date 2019-09-06 Time 13:32 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2019-09-06 13:32:06BUILT IN 2005. 30 YEARS AFTER ASBESTOS WAS BAND. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-30 Cont ID  
Sent By jwitmer Date 2019-09-30 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By jwitmer Date 2019-09-06 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2019-09-06 Time 13:32 Sent To  
Notes
2019-09-06 14:38:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080722
 ADD: 2465 MERCER AVE. SUITE: 303
 CONT: METICULOUS SERVICES, LLC
 TEL: 561-201-2430
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 06/2019
 ACTION: DENIED
  
 1) SHEET A-1.0:
  
 1A) THE FLOOR PLAN DEPICTS 3 GLASS WALL SYSTEMS WITH
 WALL IDENTIFICATION TAG (W3). THE DETAIL ON THE SAME
 SHEET FOR WALL TAG W3 INDICATES TYPICAL INTERIOR
 STOREFRONT WALL PER THE MANUFACTURES SPECIFICATION.
 SHEET A-2.0 SHOWS ELEVATION VIEWS OF THE 3 GLASS WALLS
 AND SWING DOORS BUT IN NEITHER DETAIL HAS ANY
 INFORMATION BEEN GIVEN TO THE TYPE OF FRAME, TYPE OF
 GLAZING, THICCKNESS OF THE GLAZING FOR THE WINDOW WALL
 SYSTEM NOR THE GLASS DOOR, NOR ANCHORING OF THE WALL TO
 THE FLOOR NOR TOP TRACK.
 PLEASE PROVIDE THE DESIGN PERIMTERS FOR THE SAFETY
 GLAZING FOR THE WINDOW WALL SYSTEM AND GLAZED SWING
 DOORS, 2017 FBC-B TABLE 2406.2(1) & TABLE 2406.2(2).
  
 1B) THE FLOOR PLAN DOES NOT PROVIDE THE DEPTH OF ROOM
 NUMBER 3 THE RESTROOM THE WIDTH OF THE RESTROOM IS
 GIVEN AS 6 FEET 3 INCHES. PLEASE SHOW COMPLIANCE WITH
 THE 2 SECTIONS OF THE 2017 FBC-ACCESSIBILITY CODE
 LISTED BELOW:
  
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 1C) THE REAR WALL AND PORTION OF THE FRONT WALL OF THE
 RESTROOM HAS A WALL IDENTIFICATION TAG W5. THE WALL TAG
 W5 DOES INDICATE THESE WALLS ARE TO BE CONCRETE BLOCK
 WALLS? IS THIS CORRECT? THE PLAN CALLS FOR 2X4 WOOD
 STUD WALLS FOR SIDE WALLS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. HOW ARE THE BLOCK WALLS TO BE
 ANCHORED WHEN THEY DO NOT AJOIN TO MAKE EITHER INSIDE
 OR OUTSIDE CORNERS?
  
 1D) DEPENDING ON WHICH DETAIL YOU LOOK AT ON THE
 RESTROOM WALLS WALL TYPE W4 THE CEILING FRAMING MEMBERS
 ARE SHOWN TO BE 2X6 WOOD RAFTERS BUT WHEN YOU LOOK AT
 WALL TYPE W5 THE CEILING FRAMING IS METAL FRAMING AT 24
 INCHES O. C. THE SIZE OF THE METAL FRAMING IS NOT
 GIVEN. DISCREPANCY IN THE PLANS.
  
 2) SHEET A-1.0. IN THE AREA OF THE BREAKROOM THERE IS A
 ELEVATION SYMBLE FOR THE BREAK ROOM BOTTOM CABINETS,
 DETAIL 1 SHEET A2.0. THIS ELEVATION DETAIL DOES NOT
 PROVIDE AN ELEVATION TO THE TOP OF THE COUNTERTOP NOR
 LIP OF THE SINK. THE PLANS DO INDICATE THE COUNTERTOP
 IS TO BE 2 INCHES THICK. PLEASE SHOW COMPLIANCE WITH
 THE 2017 FBC-ACCESSIBILITY CODE SECTION: 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET A-2.0 SHOWS THE ELEVATION VIEW OF THE LAV AND
 WATER CLOSET ELEVATION. THE PLAN SHOWS THE GRAB BAR
 BEING DIMENSIONED CENTERLINE OF THE GRAB BAR. PLEASE
 NOTE A CHANGE IN THE CODE AS FAR AS DIMENSIONING. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4) SHEET A-2.0 THE NEW RESTROOM ELEVATION. PLEASE ADD
 THE HORIZONTAL MEASUREMENTS FOR THE GRAB BAR BACK OF
 THE WATER CLOSET AND SHOW THE SIDE WALL ELEVATION FOR
 THE SIDEWALL GRAB BAR LENGTH AND POSITION ON THE WALL.
 PLEASE ALSO INCLUDE THE POSITIONING OF THE TOLIET PAPER
 DISPENSER. MISSING INFORMATION, ADDITIONAL INFORMATION
 IS REQUIRED. 107.2.1.2.
  
 5) SHEET A-2.0 RESTROOM ELEVATION THE HEIGHT OF THE
 MIRROR CAN NOT BE RED. PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 6) # SETS OF PLANS WERE SUBMITTED ONLY 2 SETS OF PLANS
 WERE SIGNED AND SEALED. IF THE CONTRACTOR PREFERS TO
 HAVE 2 SETS OF STAMPED PLANS RETURNED THEN A 3RD SET OF
 SIGNED AND SEALED PLANS WILLBE REQUIRED. FL ADMIN CODE
 61G16.003(1) ARCHITECTS. PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 5)
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By jleahy Date 2019-10-01 Time 12:48 Rev Time 0.00
Received By jleahy Date 2019-10-01 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By jleahy Date 2019-09-09 Time 14:51 Rev Time 0.00
Received By jleahy Date 2019-09-09 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By jleahy Date 2019-10-01 Time 12:48 Rev Time 0.00
Received By jleahy Date 2019-10-01 Time 12:48 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By jleahy Date 2019-09-09 Time 14:51 Rev Time 0.00
Received By jleahy Date 2019-09-09 Time 14:51 Sent To  
Notes
2019-09-09 14:52:19TELEPHONE AND DATA ONLY JL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By pleduc Date 2019-09-24 Time   Rev Time 0.00
Received By pleduc Date 2019-09-24 Time 13:46 Sent To  
Notes
2019-09-24 13:47:29THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LIFE SAFETY SHEET INDICATED INCORRECT EDITIONS
 OF MANY FIRE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 THE CURRENT EDITIONS OF EACH CODE CAN BE FOUND IN NFPA
 101, CHAPTER 2.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
 FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL COMPLY WITH
 NFPA 30, 2015 EDITION
 MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES
 SHALL COMPLY WITH NFPA 30 A, 2015 EDITION
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2015 EDITION
 INSPECTION, TESTING & MAINTENANCE SHALL COMPLY WITH
 NFPA 25, 2014 EDITION.
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND UPDATE YOUR
 RECORDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-16 Cont ID  
Sent By pleduc Date 2019-08-16 Time   Rev Time 0.00
Received By pleduc Date 2019-08-16 Time 14:21 Sent To  
Notes
2019-08-16 14:24:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE LIFE SAFETY SHEET INDICATED INCORRECT EDITIONS
 OF MANY FIRE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 THE CURRENT EDITIONS OF EACH CODE CAN BE FOUND IN NFPA
 101, CHAPTER 2.
  
 THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
 FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL COMPLY WITH
 NFPA 30, 2015 EDITION
 MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES
 SHALL COMPLY WITH NFPA 30 A, 2015 EDITION
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2015 EDITION
 INSPECTION, TESTING & MAINTENANCE SHALL COMPLY WITH
 NFPA 25, 2014 EDITION.
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND UPDATE YOUR
 RECORDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-03 Cont ID  
Sent By jesmith Date 2019-10-03 Time 09:04 Rev Time 0.00
Received By jesmith Date 2019-10-03 Time 08:34 Sent To  
Notes
2019-09-23 15:12:05B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-14 Time 13:12 Sent To  
Notes
2019-08-15 13:12:50B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-06 Cont ID  
Sent By jwitmer Date 2019-09-06 Time 13:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By ccole Date 2019-09-27 Time 08:17 Rev Time 0.00
Received By ccole Date 2019-09-26 Time 17:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By ccole Date 2019-09-12 Time 15:11 Rev Time 0.00
Received By ccole Date 2019-09-12 Time 15:04 Sent To  
Notes
2019-09-12 15:23:56 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080722
 9/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1 & M1.1: PROVIDE ENGINEER'S TITILE BLOCK
 ON M0.1 & TITKLE BLOCK AND SEAL AND SIGNATURE ON M1.1-
 SECTION 61G15-23.002 FAC.
  
 2) M0.1: VERIFY THE O/A INTAKE OPENING IS 10' FROM THE
 DRIVEWAY AND PARKING LOT- SECTION 401.4 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By jesmith Date 2019-10-03 Time 08:33 Rev Time 0.00
Received By jesmith Date 2019-10-01 Time 14:14 Sent To  
Notes
2019-10-03 08:33:30PLUMBING COMMENTS: APPROVED W/PROVISO
 THE SUBMITTED EEMAX SP2412T IS NOT ASSE 1070 COMPLIANT
 FOR USE AS A TEMPERATURE DEVICE IN ACCORDANCE WITH FBC
 PL 416.5. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL, TWO (2) COPIES OF
 MANUFACTURER?S SPECIFICATION/DATA SHEET FOR AN ASSE
 1070 COMPLIANT TANKLESS WATER HEATER. CONTACT EEMAX
 TECHNICAL SUPPORT AT 1-800-543-6163 FOR HELP IN THIS
 MATTER. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON
 SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK
  
 NOTE: A SECOND SIGNED AND SEALED PLAN SHEET A-2 HAS
 BEEN INSERTED INTO THE DOCUMENTS TO SUPPLEMENT THE
 ORIGINAL PLAN SHEET A-2, SATISFYING ORIGINAL PLUMBING
 COMMENTS.BOTH SHEETS ARE NOW PART OF THE PERMIT SET.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080722 2465 MERCER AVE 303

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By gjohnson Date 2019-08-30 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2019-08-30 Time 15:33 Sent To  
Notes
2019-08-30 17:36:111ST REVIEW: 18080722
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE DIMENSIONS OF BATHROOM. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHOW THE CLEAR FLOOR FOR TOILET SHALL COMPLY WITH
 FBC ACC 604.3.1
  
 3. LABEL ALL CLEAR FLOOR SPACES WITH DIMENSIONS. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHOW COMPLIANCE OF THE BREAK ROOM SINK SHALL COMPLY
 WITH FBC ACC 606.2-3
  
 5. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. FBS ACC 609.4
  
 6. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 7. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE.PER FBC ACC 604.5.2
  
 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR.PER FBC ACC 604.7
  
 9. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES \ MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION,PER FBC
 ACC 604.2
  
 10. THE DIMENSIONS FOR THE LAVATORY AND THE MIRROR
 PLEASE CLARIFY. PER FBC ACC 603.3, 606.2-3
  
 11. SHT P1.1 THE BREAK ROOM SINK SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP PER FBC PL 912.1 ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 12. UNDER THE DOMESTIC WATER SERVICE NOTES #2 #3 LIST
 2014 CODE THE THE CORRECT CODE SHALL BE 2017. PER WPB
 AMEND TO FBC 107.2.1
  
 13. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]