| 2019-09-06 14:38:03 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19080722 |
| | ADD: 2465 MERCER AVE. SUITE: 303 |
| | CONT: METICULOUS SERVICES, LLC |
| | TEL: 561-201-2430 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. SEPT. 06/2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1.0: |
| | |
| | 1A) THE FLOOR PLAN DEPICTS 3 GLASS WALL SYSTEMS WITH |
| | WALL IDENTIFICATION TAG (W3). THE DETAIL ON THE SAME |
| | SHEET FOR WALL TAG W3 INDICATES TYPICAL INTERIOR |
| | STOREFRONT WALL PER THE MANUFACTURES SPECIFICATION. |
| | SHEET A-2.0 SHOWS ELEVATION VIEWS OF THE 3 GLASS WALLS |
| | AND SWING DOORS BUT IN NEITHER DETAIL HAS ANY |
| | INFORMATION BEEN GIVEN TO THE TYPE OF FRAME, TYPE OF |
| | GLAZING, THICCKNESS OF THE GLAZING FOR THE WINDOW WALL |
| | SYSTEM NOR THE GLASS DOOR, NOR ANCHORING OF THE WALL TO |
| | THE FLOOR NOR TOP TRACK. |
| | PLEASE PROVIDE THE DESIGN PERIMTERS FOR THE SAFETY |
| | GLAZING FOR THE WINDOW WALL SYSTEM AND GLAZED SWING |
| | DOORS, 2017 FBC-B TABLE 2406.2(1) & TABLE 2406.2(2). |
| | |
| | 1B) THE FLOOR PLAN DOES NOT PROVIDE THE DEPTH OF ROOM |
| | NUMBER 3 THE RESTROOM THE WIDTH OF THE RESTROOM IS |
| | GIVEN AS 6 FEET 3 INCHES. PLEASE SHOW COMPLIANCE WITH |
| | THE 2 SECTIONS OF THE 2017 FBC-ACCESSIBILITY CODE |
| | LISTED BELOW: |
| | |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE |
| | WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER |
| | CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY |
| | NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE |
| | ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT |
| | OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER |
| | FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE |
| | REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 1C) THE REAR WALL AND PORTION OF THE FRONT WALL OF THE |
| | RESTROOM HAS A WALL IDENTIFICATION TAG W5. THE WALL TAG |
| | W5 DOES INDICATE THESE WALLS ARE TO BE CONCRETE BLOCK |
| | WALLS? IS THIS CORRECT? THE PLAN CALLS FOR 2X4 WOOD |
| | STUD WALLS FOR SIDE WALLS. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. HOW ARE THE BLOCK WALLS TO BE |
| | ANCHORED WHEN THEY DO NOT AJOIN TO MAKE EITHER INSIDE |
| | OR OUTSIDE CORNERS? |
| | |
| | 1D) DEPENDING ON WHICH DETAIL YOU LOOK AT ON THE |
| | RESTROOM WALLS WALL TYPE W4 THE CEILING FRAMING MEMBERS |
| | ARE SHOWN TO BE 2X6 WOOD RAFTERS BUT WHEN YOU LOOK AT |
| | WALL TYPE W5 THE CEILING FRAMING IS METAL FRAMING AT 24 |
| | INCHES O. C. THE SIZE OF THE METAL FRAMING IS NOT |
| | GIVEN. DISCREPANCY IN THE PLANS. |
| | |
| | 2) SHEET A-1.0. IN THE AREA OF THE BREAKROOM THERE IS A |
| | ELEVATION SYMBLE FOR THE BREAK ROOM BOTTOM CABINETS, |
| | DETAIL 1 SHEET A2.0. THIS ELEVATION DETAIL DOES NOT |
| | PROVIDE AN ELEVATION TO THE TOP OF THE COUNTERTOP NOR |
| | LIP OF THE SINK. THE PLANS DO INDICATE THE COUNTERTOP |
| | IS TO BE 2 INCHES THICK. PLEASE SHOW COMPLIANCE WITH |
| | THE 2017 FBC-ACCESSIBILITY CODE SECTION: 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3) SHEET A-2.0 SHOWS THE ELEVATION VIEW OF THE LAV AND |
| | WATER CLOSET ELEVATION. THE PLAN SHOWS THE GRAB BAR |
| | BEING DIMENSIONED CENTERLINE OF THE GRAB BAR. PLEASE |
| | NOTE A CHANGE IN THE CODE AS FAR AS DIMENSIONING. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 4) SHEET A-2.0 THE NEW RESTROOM ELEVATION. PLEASE ADD |
| | THE HORIZONTAL MEASUREMENTS FOR THE GRAB BAR BACK OF |
| | THE WATER CLOSET AND SHOW THE SIDE WALL ELEVATION FOR |
| | THE SIDEWALL GRAB BAR LENGTH AND POSITION ON THE WALL. |
| | PLEASE ALSO INCLUDE THE POSITIONING OF THE TOLIET PAPER |
| | DISPENSER. MISSING INFORMATION, ADDITIONAL INFORMATION |
| | IS REQUIRED. 107.2.1.2. |
| | |
| | 5) SHEET A-2.0 RESTROOM ELEVATION THE HEIGHT OF THE |
| | MIRROR CAN NOT BE RED. PLEASE SHOW COMPLIANCE WITH: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF |
| | GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 6) # SETS OF PLANS WERE SUBMITTED ONLY 2 SETS OF PLANS |
| | WERE SIGNED AND SEALED. IF THE CONTRACTOR PREFERS TO |
| | HAVE 2 SETS OF STAMPED PLANS RETURNED THEN A 3RD SET OF |
| | SIGNED AND SEALED PLANS WILLBE REQUIRED. FL ADMIN CODE |
| | 61G16.003(1) ARCHITECTS. PLANS, SPECIFICATIONS, REPORTS |
| | OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL |
| | AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | 5) |
| | |
| | |
| | |
| | |