Plan Review Details - Permit 19080717
Plan Review Stops For Permit 19080717
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-09-12 Cont ID  
Sent By jesmith Date 2019-09-12 Time 10:24 Rev Time 0.00
Received By jesmith Date 2019-09-10 Time 16:05 Sent To  
Notes
2019-09-12 10:24:40GAS COMMENTS: APPROVED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 14:57 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 12:21 Sent To  
Notes
2019-08-20 14:57:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 2. SITE PLAN SHOWING LAYOUT OF EQUIPMENT AND PIPING IS
 NOT LEGIBLE. PER WPB FBC 107.2.1, PROVIDE LEGIBLE SITE
 PLAN WITH LAYOUT SHOWING LOCATION OF TANK AND RANGE.
 TANK SHALL BE LOCATED IN ACCORDANCE WITH NFPA 58
 SECTION 6.4.4.1.
 3. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, SECTION 6.4.4.1.
 4. PROVIDE COPY OF HOUSE PLAN SHOWING LOCATION OF RANGE
 AND TANK AND PIPE ROUTING.
 5. PROVIDE RISER DIAGRAM SHOWING ALL HORIZONTAL AND
 VERTICAL DIMENSIONED INTERVALS FROM TANK TO RANGE. SIZE
 IN ACCORDANCE WITH FBC FG 402.4 SIZING TABLES OR NFPA
 58 CHAPTER 16 SIZING TABLES. SHOW ALL VALVES AND
 REGULATORS. IDENTIFY ABOVE GROUND TO UNDERGROUND AND
 THROUGH THE WALL TRANSITIONS. IDENTIFY 10 PSI AND
 12-13? WC SECTIONS. SHOW TYPE OF MATERIAL BEING USED.
 INDICATE TYPE OF GAS.
 6. THE SUBMITTED REGULATOR(S) DOES/DO NOT MATCH THE
 INFORMATION PROVIDED. PLEASE CLARIFY.
 7. THE SUBMITTED VESSEL (HORIZONTAL CONFIGURATION) DOES
 NOT MATCH UP TO THE VERTICAL CONFIGURATION OF THE
 ANCHORING DETAILS (SHEET T-1). PLEASE CLARIFY. PLEASE
 INDICATE ON SUBMITTAL FOR ABOVE OR BELOW GROUND USE AND
 HIGHLIGHT SIZE.
 8. PROVIDE ENGINEER?S DIGITAL SIGNATURE WITH PROPER 3RD
 PARTY VERIFICATION ON SHEET T-1.
 9. REFERENCE SIZING TABLE(S) SPECIFY TYPE K & L COPPER
 TUBING OR ACR. HIGHLIGHT OR POINT TO THE APPLICABLE
 DISTANCE.
 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 RANGE PER FBC FG SEC.304.1
 11. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 SEC. 402.2.
 12. PER WPB FBC 107.2.1, IF USING COPPER, PROVIDE AN
 AFFIDAVIT THAT THE GAS BEING CONVEYED DOES NOT CONTAIN
 MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN SULFIDE
 PER 100 STANDARD CU. FT. OF GAS TO SHOW COMPLIANCE WITH
 FBC FG 403.4.3.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080717 1273 SLASH PINE CIR
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-12 Cont ID  
Sent By jesmith Date 2019-09-12 Time 10:25 Rev Time 0.00
Received By jesmith Date 2019-09-12 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 15:00 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 15:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 14:57 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 09:29 Rev Time 0.00
Received By shill Date 2019-09-13 Time 09:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 14:58 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 14:58 Sent To  
Notes
2019-08-20 14:59:55PROVIDE ENGINEER?S DIGITAL SIGNATURE WITH PROPER 3RD
 PARTY VERIFICATION ON SHEET T-1.