Plan Review Details - Permit 19080672
Plan Review Stops For Permit 19080672
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-29 Cont ID  
Sent By jgomez Date 2019-10-29 Time 15:37 Rev Time 0.00
Received By jgomez Date 2019-10-29 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-07 Cont ID  
Sent By jgomez Date 2019-10-07 Time 18:33 Rev Time 0.00
Received By jgomez Date 2019-10-07 Time 11:15 Sent To  
Notes
2019-10-07 18:34:36RESIDENTIAL (R3) REVISION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ORIGINAL COMMENT:
 1- REVISION SUBMITTED IS FOR THE DETACHED REAR
 STRUCTURE. THE MASTER PERMIT WAS FOR WORK ON THE MAIN
 HOUSE ONLY. A REVISION SUBMITTAL WAS PERMITTED FOR THIS
 PROJECT BY ROBERT BROWN (BUILDING OFFICIAL). A SEPARATE
 PERMIT APPLICATION IS USUALLY REQUIRED FOR EACH
 STRUCTURE. STRUCTURAL, ELECTRICAL AND MECHANICAL SHEETS
 SUBMITTED ARE THE SAME NUMBERS AS SHOWN ON THE MASTER
 PERMIT APPLICATION. NEED TO REVISE THE DRAWINGS NUMBERS
 ON EACH SHEET OR NEED TO ADD THE SCOPE OF WORK SHOWN ON
 THE MASTER PERMIT THAT WAS ALREADY APPROVED.
 SEC. 107.2.1.3 CITY AMENDMENTS. SEE NOTE BELOW STATING
 HOW ROBERT BROWN PERMITTED THE REVISION INSTEAD OF
 SEPARATE PERMIT APPLICATION.
  
 RESPONSE:
 PARTIALLY COMPLIED. SHEET NUMBERS WERE REVISED, BUT THE
 LAST STRUCTURAL DRAWING WAS S-9. THEREFORE, THE FIRST
 OF NUMBER FOR THIS ADDITIONAL WORK ON THE REAR
 STRUCTURE SHOULD BE S-10 NOT S-9 AS SUBMITTED.
 OTHERWISE, THERE WILL BE TWO S-9 SHEETS. REVISE AS
 REQUIRED. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- SECOND FLOOR JOIST LAYOUT, ROOF FRAMING PLAN,
 EXTERIOR DOOR OPENING WINDOW/WALL FRAMING & STRAPPING
 DETAIL, STAIRWAY FRAMING PLAN AND ELEVATION A ON SHEET
 S-2 AND SECTION A, SECTION B SECTION C ON SHEET S-3 ARE
 MISSING SOME STRUCTURAL CONNECTORS AT THE ENDS OF EACH
 STRUCTURAL MEMBER. PLEASE REVIEW ALL FRAMING PLANS,
 DETAILS AND SECTIONS AND CLEARLY PROVIDE THE CONNECTOR
 AT EACH FRAMING MEMBER. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 STRUCTURAL PLANS AND DETAILS DON'T PROVIDE
 DETAILS/SPECIFICATIONS FOR STRUCTURAL CONNECTORS AT THE
 BASE OF ALL NEW JACKS SPECIFIED ON THE FRAMING PLANS.
 SEE JACKS SPECIFIED AT THE END OF EACH BEAM AND AT THE
 END OF THE GARAGE DOORS FRAMING. PROVIDE
 DETAILS/SPECIFICATIONS FOR STRUCTURAL CONNECTIONS
 SHOWING THE LOAD PATH. SEC. 801.3 FBC-EXISTING BUILDING
 AND SEC. R601.2 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 3- ENGINEER OF RECORD TO CLARIFY WHY THE DESIGN
 PRESSURES SHOWN ON SHEET S-1 ARE HIGHER FOR THE WINDOWS
 LOCATED ON ZONE 4. DESIGN PRESSURES ARE HIGHER FOR
 WINDOWS LOCATED ON ZONE 5.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 DESIGN PRESSURES WERE REVISED BUT ENGINEER NEEDS TO
 CLARIFY WHY THE DESIGN PRESSURES SPECIFIED FOR THE
 LARGER WINDOWS ARE HIGHER THAN THE DESIGN PRESSURE FOR
 SMALLER WINDOWS. TYPICALLY, THE SMALLER THE EFFECTIVE
 WIND AREA THE HIGHER THE DESIGN PRESSURES. ALSO,
 COORDINATE WITH ITEM #3(B) BELOW AND REVISE AS
 REQUIRED. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 B) DESIGN PRESSURES FOR ZONE 5 SEEM TO BE LOW. BASED ON
 TABLE R301.2(2) AND TABLE R301.2(3) FBC-RESIDENTIAL,
 THE DESIGN PRESSURES FOR ZONE 5 ARE HIGHER THAN THOSE
 SHOWN ON SHEET S-1. REVISE AS REQUIRED. KEEP IN MIND
 THE BUILDING EXPOSURE D, WINDOW EFFECTIVE AREA AND
 HEIGHT.
  
 RESPONSE:
 DESIGN PRESSURES ARE STILL LOW. ENGINEER OF RECORD TO
 CLARIFY WHY THE DESIGN PRESSURES ARE LOWER THAN THOSE
 DESIGN PRESSURES SPECIFIED ON THE MASTER PERMIT
 18090722. ALSO, COORDINATE WITH ITEM #3(A) ABOVE. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
  
 4- OK
  
 5- ELEVATION A ON SHEET S-2:
 ORIGINAL COMMENT:
 A)IT LOOKS LIKE THE NEW STAIRWAY DOESN'T PROVIDE THE
 REQUIRED HEADROOM REQUIRED BY SEC. R311.7.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 THE STAIRWAY DOESN'T HAVE THE REQUIRED HEADROOM
 (6'-8"). ELEVATION A SHOWS THE MEASUREMENT FROM THE
 STAIR NOSING TO A POINT THAT IS SETBACK ABOUT 4" FROM
 THE EDGE OF THE CEILING ABOVE. THIS IS NOT THE WAY THE
 HEADROOM IS MEASURED. THE HEADROOM IS MEASURED
 VERTICALLY FROM THE SLOPED LINE ADJOINING THE TREAD
 NOSING. SEE SEC. R311.7.2 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
 NOTE: ENGINEER CAN ALSO REVIEW THE COMMENTARY BOOK
 WHICH SHOWS A FIGURE OF HOW THE HEADROOM IS MEASURED.
  
 B) OK.
  
 6- OK.
  
 ORIGINAL COMMENT:
 7- PROVIDE COMPLETE STORM SHUTTERS INSTALLATION
 SCHEDULE AS REQUIRED BY CITY POLICY FOR SHUTTERS
 INSTALLATION. SEE NOTE ON PROPOSED FIRST FLOOR PLAN ON
 SHEET S-1. IT SPECIFIED THAT EXISTING CYPRESS DOORS
 WILL HAVE HURRICANE PANELS.
  
 RESPONSE:
 PROPOSED INSTALLATION DOESN'T SEEM TO WORK.
 INSTALLATION DETAIL "ALTERNATIVE 9" SHOWN ON SHEET 13
 OF 15 OF SHUTTERS DRAWINGS SUBMITTED IS FOR WOOD
 INSTALLATION. IF THE STORM SHUTTERS ARE INSTALLED
 VERTICALLY, THEN IT MEANS THAT ALTERNATIVE 9 IS THE
 BOTTOM OF THE EXISTING GARAGE DOORS. IT DOESN'T LOOK
 LIKE THE FLOOR BY THE GARAGE DOORS IS WOOD.
 REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 ALSO, PROVIDE ALL THE 15 DRAWINGS OF THE SHUTTERS.
  
 ORIGINAL COMMENT:
 8-PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE "AIR
 IMPERMEABLE R-30 INSULATION" SPECIFIED ON SECTION B ON
 SHEET S-3 TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 BASED ON EVALUATION REPORT SUBMITTED, THE R-30
 INSULATION DOESN'T FIT ON THE EXISTING 2X4 CEILING
 JOISTS SHOWN ON THE ROOF FRAMING PLAN. SEE TABLE 1 ON
 PAGE 2 OF 5 OF EVALUATION REPORT FOR THICKNESS REQUIRED
 AND REVISE AS REQUIRED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 PER ROBERT BROWN, A REVISION IS PERMITTED FOR THIS
 PROJECT. THE GARAGE IS BEING ADDED TO THE PERMIT.
 HOWEVER, THE SHEETS SUBMITTED NEED TO BE CHECKED
 CAREFULLY TO ENSURE THE ORIGINAL PROJECT IS NOT
 REPLACED WITH THE GARAGE PROJECT. THE SHEETS SUBMITTED
 SHALL EITHER BE NEW SHEETS, OR A REVISION THAT INCLUDES
 THE ORIGINAL INFORMATION AND WHAT HAS CHANGED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-11 Cont ID  
Sent By jgomez Date 2019-09-11 Time 16:11 Rev Time 0.00
Received By jgomez Date 2019-09-11 Time 09:50 Sent To  
Notes
2019-09-11 16:12:15RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- REVISION SUBMITTED IS FOR THE DETACHED REAR
 STRUCTURE. THE MASTER PERMIT WAS FOR WORK ON THE MAIN
 HOUSE ONLY. A REVISION SUBMITTAL WAS PERMITTED FOR THIS
 PROJECT BY ROBERT BROWN (BUILDING OFFICIAL). A SEPARATE
 PERMIT APPLICATION IS USUALLY REQUIRED FOR EACH
 STRUCTURE. STRUCTURAL, ELECTRICAL AND MECHANICAL SHEETS
 SUBMITTED ARE THE SAME NUMBERS AS SHOWN ON THE MASTER
 PERMIT APPLICATION. NEED TO REVISE THE DRAWINGS NUMBERS
 ON EACH SHEET OR NEED TO ADD THE SCOPE OF WORK SHOWN ON
 THE MASTER PERMIT THAT WAS ALREADY APPROVED.
 SEC. 107.2.1.3 CITY AMENDMENTS. SEE NOTE BELOW STATING
 HOW ROBERT BROWN PERMITTED THE REVISION INSTEAD OF
 SEPARATE PERMIT APPLICATION.
  
  
 "PER ROBERT BROWN, A REVISION IS PERMITTED FOR THIS
 PROJECT. THE GARAGE IS BEING ADDED TO THE PERMIT.
 HOWEVER, THE SHEETS SUBMITTED NEED TO BE CHECKED
 CAREFULLY TO ENSURE THE ORIGINAL PROJECT IS NOT
 REPLACED WITH THE GARAGE PROJECT. THE SHEETS SUBMITTED
 SHALL EITHER BE NEW SHEETS, OR A REVISION THAT INCLUDES
 THE ORIGINAL INFORMATION AND WHAT HAS CHANGED."
  
 2- SECOND FLOOR JOIST LAYOUT, ROOF FRAMING PLAN,
 EXTERIOR DOOR OPENING WINDOW/WALL FRAMING & STRAPPING
 DETAIL, STAIRWAY FRAMING PLAN AND ELEVATION A ON SHEET
 S-2 AND SECTION A, SECTION B SECTION C ON SHEET S-3 ARE
 MISSING SOME STRUCTURAL CONNECTORS AT THE ENDS OF EACH
 STRUCTURAL MEMBER. PLEASE REVIEW ALL FRAMING PLANS,
 DETAILS AND SECTIONS AND CLEARLY PROVIDE THE CONNECTOR
 AT EACH FRAMING MEMBER. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- A)ENGINEER OF RECORD TO CLARIFY WHY THE DESIGN
 PRESSURES SHOWN ON SHEET S-1 ARE HIGHER FOR THE WINDOWS
 LOCATED ON ZONE 4. DESIGN PRESSURES ARE HIGHER FOR
 WINDOWS LOCATED ON ZONE 5.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B) DESIGN PRESSURES FOR ZONE 5 SEEM TO BE LOW. BASED ON
 TABLE R301.2(2) AND TABLE R301.2(3) FBC-RESIDENTIAL,
 THE DESIGN PRESSURES FOR ZONE 5 ARE HIGHER THAN THOSE
 SHOWN ON SHEET S-1. REVISE AS REQUIRED. KEEP IN MIND
 THE BUILDING EXPOSURE D, WINDOW EFFECTIVE AREA AND
 HEIGHT.
  
 4- EGRESS DOOR NEEDS TO HAVE AT LEAST 32" CLEAR OPENING
 AS REQUIRED BY SEC. R311.1 FBC-RESIDENTIAL. 2'-10" DOOR
 DOESN'T COMPLY. REVISE AS REQUIRED.
  
 5- ELEVATION A ON SHEET S-2:
 A)IT LOOKS LIKE THE NEW STAIRWAY DOESN'T PROVIDE THE
 REQUIRED HEADROOM REQUIRED BY SEC. R311.7.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 B) SPECIFY THE UNDER-STAIR PROTECTION AS REQUIRED BY
 SEC. R302.7 FBC-RESIDENTIAL.
  
 6- WINDOWS LOCATED ON THE SECOND FLOOR NEED TO COMPLY
 WITH THE WINDOW OPENING CONTROL DEVICE IF THE WINDOW
 SILL IS LESS THAN 24" ABOVE THE FINISHED FLOOR. SEC.
 702.4 FBC-EXISTING BUILDING. CLEARLY SPECIFY/IDENTIFY
 ANY WINDOW HAVING THE WINDOW SILL
 LESS THAN 24" FORM FINISHED FLOOR AND SPECIFY HOW
 COMPLYING WITH THE WINDOW OPENING CONTROL DEVICE.
  
 7- PROVIDE COMPLETE STORM SHUTTERS INSTALLATION
 SCHEDULE AS REQUIRED BY CITY POLICY FOR SHUTTERS
 INSTALLATION. SEE NOTE ON PROPOSED FIRST FLOOR PLAN ON
 SHEET S-1. IT SPECIFIED THAT EXISTING CYPRESS DOORS
 WILL HAVE HURRICANE PANELS.
  
 8-PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE "AIR
 IMPERMEABLE R-30 INSULATION" SPECIFIED ON SECTION B ON
 SHEET S-3 TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
2019-09-06 07:13:02PER ROBERT BROWN, A REVISION IS PERMITTED FOR THIS
 PROJECT. THE GARAGE IS BEING ADDED TO THE PERMIT.
 HOWEVER, THE SHEETS SUBMITTED NEED TO BE CHECKED
 CAREFULLY TO ENSURE THE ORIGINAL PROJECT IS NOT
 REPLACED WITH THE GARAGE PROJECT. THE SHEETS SUBMITTED
 SHALL EITHER BE NEW SHEETS, OR A REVISION THAT INCLUDES
 THE ORIGINAL INFORMATION AND WHAT HAS CHANGED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-25 Cont ID  
Sent By jpearson Date 2019-10-25 Time 10:41 Rev Time 0.00
Received By ppetty Date 2019-10-28 Time 11:27 Sent To  
Notes
2019-10-25 10:41:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW.
  
 1.
 2.
 3.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-08 Cont ID  
Sent By jpearson Date 2019-10-08 Time 11:17 Rev Time 0.00
Received By jpearson Date 2019-10-08 Time 09:47 Sent To  
Notes
2019-10-08 11:17:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 2. GFCI PROTECTION IS REUIRED FOR ALL RECEPTACLE
 OUTLETS IN STORAGE AREA. NEC 210.8; FBC RE E3902.3
 3. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 07:12 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 07:12 Sent To  
Notes
2019-09-05 15:50:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ORIGINAL PLAN SHEET E-1 IS THE PLAN FOR THE MAIN
 HOUSE. IT IS NOT POSSIBLE TO SUBMIT THIS SHEET AS A
 REVISION AND SHOW THE DETAILS FOR A DIFFERENT
 STRUCTURE. IF THE SHEET IS NAMED DIFFERENTLY, THEN THE
 REVISION CAN CONTINUE. OTHERWISE, A SEPARATE PERMIT
 WOULD BE REQUIRED. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-11-04 Cont ID  
Sent By fmittner Date 2019-11-04 Time 15:56 Rev Time 0.00
Received By fmittner Date 2019-11-04 Time 15:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 11:38 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 11:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By fmittner Date 2019-08-28 Time 11:08 Rev Time 0.00
Received By fmittner Date 2019-08-28 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-06 Cont ID  
Sent By lcrespo Date 2019-11-06 Time 15:03 Rev Time 0.00
Received By lcrespo Date 2019-10-16 Time 13:14 Sent To  
Notes
2019-10-17 13:15:05R14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-08 Cont ID  
Sent By cmontell Date 2019-10-08 Time 14:19 Rev Time 0.00
Received By cmontell Date 2019-09-20 Time 15:15 Sent To  
Notes
2019-09-23 15:15:08R16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-11 Cont ID  
Sent By jgomez Date 2019-09-11 Time 16:14 Rev Time 0.00
Received By jgomez Date 2019-08-13 Time 14:40 Sent To I
Notes
2019-08-14 14:41:03R14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-11 Cont ID  
Sent By jgomez Date 2019-09-11 Time 16:13 Rev Time 0.00
Received By jgomez Date 2019-09-11 Time 16:13 Sent To  
Notes
2019-09-11 16:14:32CHANGE OF USE FROM GARAGE TO STORAGE. NO LIVABLE SPACE.
 IMPACT FEES NO REQUIRED.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By cmontell Date 2019-10-08 Time 14:19 Rev Time 0.00
Received By cmontell Date 2019-10-08 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-11 Cont ID  
Sent By cmontell Date 2019-08-27 Time 14:13 Rev Time 0.00
Received By cmontell Date 2019-09-11 Time 13:15 Sent To  
Notes
2019-09-11 13:13:59PER ROBERT BROWN, A REVISION IS PERMITTED FOR THIS
 PROJECT. THE GARAGE IS BEING ADDED TO THE PERMIT.
 HOWEVER, THE SHEETS SUBMITTED NEED TO BE CHECKED
 CAREFULLY TO ENSURE THE ORIGINAL PROJECT IS NOT
 REPLACED WITH THE GARAGE PROJECT. THE SHEETS SUBMITTED
 SHALL EITHER BE NEW SHEETS, OR A REVISION THAT INCLUDES
 THE ORIGINAL INFORMATION AND WHAT HAS CHANGED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-06 Cont ID  
Sent By lcrespo Date 2019-11-06 Time 15:03 Rev Time 0.00
Received By lcrespo Date 2019-11-06 Time 15:03 Sent To  
Notes
2019-11-06 15:03:5011/06/19 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 06:46 Rev Time 0.00
Received By lcrespo Date 2019-09-25 Time 06:28 Sent To  
Notes
2019-09-25 06:46:3409/25/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-29 Cont ID  
Sent By tklarge Date 2019-08-29 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2019-08-29 Time 07:25 Sent To  
Notes
2019-08-29 07:26:0108/29/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-11-04 Cont ID  
Sent By fmittner Date 2019-11-04 Time 15:56 Rev Time 0.00
Received By fmittner Date 2019-11-04 Time 15:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By fmittner Date 2019-10-03 Time 11:38 Rev Time 0.00
Received By fmittner Date 2019-10-03 Time 11:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By fmittner Date 2019-08-28 Time 11:11 Rev Time 0.00
Received By fmittner Date 2019-08-28 Time 11:11 Sent To  
Notes
***NONE***