Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By tklarge Date 2019-08-15 Time 07:47 Rev Time 0.00
Received By tklarge Date 2019-08-15 Time 07:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By tklarge Date 2019-08-14 Time 07:38 Rev Time 0.00
Received By tklarge Date 2019-08-13 Time 14:35 Sent To  
Notes
2019-08-13 14:42:471) THE GAS SIZING TABLE FOR THE CSST REFERENCED ON THE
 GAS DRAWING, 402.4 (16), IS FOR A GAS PRESSURE LESS
 THAN 2 PSI BUT THE GAS DRAWING IS SHOWING A 2 PSI
 SYSTEM. CLARIFY. SUBMIT TWO COPIES OF THE CORRECT
 SIZING TABLES OR PLACE A NOTE ON THE DRAWING SPECIFYING
 WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER
 STANDARD ARE BEING USED IN THE DESIGN OF THIS SYSTEM.
 2) THE SUBMITTED GAS DRAWING IS REFERENCING TWO
 DIFFERENT GAS SIZING TABLES, ONE FOR SCH. 40 METALLIC
 PIPE AND ONE FOR CSST. WHICH IS IT? CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) WHERE CONNECTED TO RIDGID PIPING, A UNION IS
 REQUIRED WITHIN ONE FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2 (7).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-15 Cont ID  
Sent By tklarge Date 2019-08-15 Time 07:47 Rev Time 0.00
Received By tklarge Date 2019-08-15 Time 07:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-14 Cont ID  
Sent By tklarge Date 2019-08-14 Time 07:38 Rev Time 0.00
Received By tklarge Date 2019-08-14 Time 07:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved