| 2019-09-18 08:44:05 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | SEC. 702.6 FBC-EXISTING BUILDING CODE: MATERIALS AND |
| | METHODS. |
| | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE, |
| | BUILDING; FLORIDA BUILDING CODE, ENERGY CONSERVATION; |
| | FLORIDA BUILDING CODE, MECHANICAL; AND FLORIDA BUILDING |
| | CODE, PLUMBING, AS APPLICABLE, THAT SPECIFY MATERIAL |
| | STANDARDS, DETAIL OF INSTALLATION AND CONNECTION, |
| | JOINTS, PENETRATIONS, AND CONTINUITY OF ANY ELEMENT, |
| | COMPONENT, OR SYSTEM IN THE BUILDING. |
| | |
| | 1- FLOORING SOUND INSULATION MATERIAL: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| | (2017). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND |
| | PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR |
| | 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING. |
| | TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS |
| | IN THESE BUILDINGS |
| | |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |