Plan Review Details - Permit 19080624
Plan Review Stops For Permit 19080624
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By pvalenti Date 2019-08-30 Time 08:06 Rev Time 0.00
Received By pvalenti Date 2019-08-30 Time 08:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By pvalenti Date 2019-08-13 Time 15:21 Rev Time 0.00
Received By pvalenti Date 2019-08-13 Time 15:21 Sent To  
Notes
2019-08-13 15:23:36***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REVIEW DENIED:
  
 PLEASE PROVIDE THE ASBESTOS SURVEY REPORT, OR PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 14:57 Rev Time 0.00
Received By shill Date 2019-09-13 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-09-12 Cont ID  
Sent By pvalenti Date 2019-09-12 Time 13:13 Rev Time 0.00
Received By pvalenti Date 2019-09-12 Time 13:13 Sent To  
Notes
2019-09-12 13:17:13****CORRECTIONS****
  
 PETER E. VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 PROVIDE EACH OF THE FOLLOWING ITEMS VIA EMAIL AS THEY
 ARE AVAILABLE; SEND TO [email protected], INCLUDE THE
 PERMIT NUMBER IN THE SUBJECT LINE.
  
 PLEASE SEE THE "DEMOLITION PERMIT APPLICATION
 CHECKLIST" WHICH YOU CAN FIND AT THE FOLLOWING WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT:
  
  
 1. COMPLIED
 2. COMPLIED
 3. COMPLIED
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED; SCHEDULE A
 FINAL PLUMBING #703. PLEASE NOTIFY US VIA EMAIL AFTER
 FINAL INSPECTION HAS PASSED. (NOT COMPLIED)
 5. COMPLIED
 6. COMPLIED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-30 Cont ID  
Sent By pvalenti Date 2019-08-30 Time 08:06 Rev Time 0.00
Received By pvalenti Date 2019-08-30 Time 07:33 Sent To  
Notes
2019-08-30 07:55:50 
 PETER E. VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
  
 2ND BUILDING REVIEW:
  
  
 PROVIDE EACH OF THE FOLLOWING ITEMS VIA EMAIL AS THEY
 ARE AVAILABLE; SEND TO [email protected], INCLUDE THE
 PERMIT NUMBER IN THE SUBJECT LINE.
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT:
  
 1. UTILITY RELEASE ? FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION. ( COMPLIED )
  
 2. UTILITY RELEASE ? FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION. ( COMPLIED )
  
 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION" ( NOT COMPLIED/PROVIDE A BACK
 FLOW PREVENTER DEVICE PERMIT )
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B
 UILDING?PERMIT?FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183. AFTER THEY FAX THE RELEASE TO YOU, SEND A
 COPY VIA EMAIL TO [email protected] WITH THE PERMIT
 NUMBER IN THE SUBJECT LINE.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED; SCHEDULE A
 FINAL PLUMBING #703. PLEASE NOTIFY US VIA EMAIL AFTER
 FINAL INSPECTION HAS PASSED. ( NOT COMPLIED/PROVIDE A
 SEWER LATERAL CAPPING PERMIT AND A #703 PASSED FINAL
 INSPECTION ).
  
 5. EXTERMINATION LETTER ? LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS. ( COMPLIED)
  
 6. COMPLETE THE DEMO DEBRIS FORM AND PAY THE FEES,
 "DEMOLITION DEBRIS DISPOSAL FEE": ( COMPLIED).
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B
 UILDING?PERMIT?FORMS
 AFTER THE FORM IS SENT TO [email protected], THE FEES
 WILL BE ADDED TO YOUR PERMIT. YOU CAN THEN PAY THE FEES
 ONLINE PRIOR TO PERMIT ISSUANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By pvalenti Date 2019-08-13 Time 15:04 Rev Time 0.00
Received By pvalenti Date 2019-08-13 Time 14:54 Sent To  
Notes
2019-08-13 15:05:59****CORRECTIONS****
  
 PETER E. VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 PROVIDE EACH OF THE FOLLOWING ITEMS VIA EMAIL AS THEY
 ARE AVAILABLE; SEND TO [email protected], INCLUDE THE
 PERMIT NUMBER IN THE SUBJECT LINE.
  
 PLEASE SEE THE "DEMOLITION PERMIT APPLICATION
 CHECKLIST" WHICH YOU CAN FIND AT THE FOLLOWING WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION. ( COMPLIED )
  
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION. ( NOT COMPLIED )
  
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION" ( NOT COMPLIED/PROVIDE A BACK
 FLOW PREVENTER DEVICE PERMIT )
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183. AFTER THEY FAX THE RELEASE TO YOU, SEND A
 COPY VIA EMAIL TO [email protected] WITH THE PERMIT
 NUMBER IN THE SUBJECT LINE.
  
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED; SCHEDULE A
 FINAL PLUMBING #703. PLEASE NOTIFY US VIA EMAIL AFTER
 FINAL INSPECTION HAS PASSED. ( NOT COMPLIED/PROVIDE A
 SEWER LATERAL CAPPING PERMIT AND A #703 PASSED FINAL
 INSPECTION ).
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS. ( COMPLIED
 ).
  
 6. COMPLETE THE DEMO DEBRIS FORM AND PAY THE FEES,
 "DEMOLITION DEBRIS DISPOSAL FEE": ( NOT COMPLIED/THE
 FORM NEEDS TO BE COMPLETED AND FEES PAID ).
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 AFTER THE FORM IS SENT TO [email protected], THE FEES
 WILL BE ADDED TO YOUR PERMIT. YOU CAN THEN PAY THE FEES
 ONLINE PRIOR TO PERMIT ISSUANCE.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By rrossano Date 2019-09-13 Time   Rev Time 0.00
Received By rrossano Date 2019-09-13 Time   Sent To  
Notes
2019-09-13 15:10:18PASSED WITH PROVISOS:
  
 1) MAINTAIN STORM WATER POLLUTION PREVENTION PLAN
 ONSITE SHOWING:
  
 A) WHERE SILT SCREENS WILL BE INSTALLED,
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS
  
 GUIDELINES: HTTPS://WWW.EPA.GOV/SITES/PRODUCTION/FILES/
 2015-10/DOCUMENTS/SW_SWPPP_GUIDE.PDF
 TEMPLATE: HTTPS://FLORIDADEP.GOV/SITES/DEFAULT/FILES/CO
 NSTRUCTIONSWPPP_0.PDF
  
 2) THERE ARE WATER AND SEWER LINES IN THE VICINITY OF
 THIS PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE
 STATUTES, YOU MUST CALL 811 FOR UTILITY LOCATES AT
 LEAST TWO FULL BUSINESS DAYS IN ADVANCE OF ANY
 CONSTRUCTION OR DEMOLITION WORK. MORE INFORMATION CAN
 BE FOUND HERE: HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By rrossano Date 2019-08-13 Time   Rev Time  
Received By rrossano Date 2019-08-13 Time   Sent To  
Notes
2019-08-13 15:25:07PLEASE ADDRESS BUILDING DEPT. COMMENTS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By fmittner Date 2019-08-13 Time 14:09 Rev Time 0.00
Received By fmittner Date 2019-08-13 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-16 Cont ID  
Sent By sholder Date 2019-09-16 Time 09:11 Rev Time 0.00
Received By sholder Date 2019-09-16 Time 09:11 Sent To  
Notes
***NONE***