| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE |
| | SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| | ASSEMBLIES: COLUMN HEADING ?ANCHOR SPACING?; VERIFY |
| | INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL FL1850; |
| | EXAMPLE: CONNECTION TYPE D WALL SILL MOUNTING |
| | INSTALLATION FOR CONCRETE, MAXIMUM SHUTTER SPAN 10?-0? |
| | DESIGN NEGATIVE LOAD 60 PSI, SYSTEM COMPONENT 14 USING |
| | TAPCON WITH ADVANCED THREADFORM TECHNOLOGY ANCHOR |
| | SPACING IS 5.5?; YOU MUST ALSO MULTIPLY THE ANCHOR |
| | SPACING GIVEN BY THE FACTOR OF .9 TO ACHIEVE THE |
| | CORRECT ANCHOR SPACING. |
| | |