Plan Review Details - Permit 19080600
Plan Review Stops For Permit 19080600
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2019-09-23 Cont ID  
Sent By jpearson Date 2019-09-23 Time 08:29 Rev Time 0.00
Received By jpearson Date 2019-09-23 Time 08:29 Sent To  
Notes
2019-09-23 08:28:14ELECTRICAL APPROVED ON 19011252

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-09-12 Cont ID  
Sent By fstal Date 2019-09-12 Time   Rev Time 0.00
Received By fstal Date 2019-09-12 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-10-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-10 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-04 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By ccole Date 2019-10-11 Time 12:03 Rev Time 0.00
Received By ccole Date 2019-10-11 Time 10:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-20 Cont ID  
Sent By ccole Date 2019-09-20 Time 09:41 Rev Time 0.00
Received By ccole Date 2019-09-18 Time 17:12 Sent To  
Notes
2019-09-20 10:15:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M04.02: THE PLAN IS INCOMPLETE- DISHWASHER
 EXHAUST DUCT NOT SHOWN, AND NO DETAILS AND
 SPECIFICATIONS PROVIDED- SECTION 107.2.1 WPB.
  
 2) M0.04: THE PLAN SHOWS A NEW GAS-FIRED FRYER AND A
 NEW FIRE SUPPRESSION SYSTEM WHICH EACH REQUIRE A
 SEPARATE PERMT- PLEASE ACKNOWLEDGE- SECTION 107.2.1
 WPB.
  
 3) THE ENGINEER OF RECORD SHALL PROVIDE A SHOP DRAWING
 STAMP OF APPROVAL ON THE FAN SUBMITTAL SHEET, AND
 PROVIDE ENGINEERING FOR THE ROOF TOP INSTALLATION-
 SECTION 107.2..1.2 WPB, AND SECTION 301.15 FBC M.
 PLEASE NOTE THE ENGINEERING MAY BE A DEFERRED SUBMITTAL
 IF REQUESTED- SECTION 107.3.4.1 WPB.
  
 4) M0.04: VERIFY THE NEW HOOD WILL HAVE AN 18"
 CLEARANCE TO COMBUSTIBLES PER SECTION 507.2.6. FBC M.
 CLARIFY IF THE WALL BEHIND THE HOOD IS COMBUSTIBLE OR
 NON-COMBUSTBLE AND PROVIDE A CLEARANCE RECUTION METHOD
 IN COMPLIANCE WITH TABLE 308.4.2 FBC M.
  
 5) M0.04: VERIFY THAT THE TEMPERATURE DIFFERENTIAL
 BETWEEN THE EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE DOES NOT EXCEED 10 DEGREES F- SECTION
 508.1.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-09-20 Cont ID  
Sent By ccole Date 2019-09-20 Time 10:16 Rev Time 0.00
Received By ccole Date 2019-09-20 Time 10:16 Sent To  
Notes
***NONE***