Plan Review Details - Permit 19080544
Plan Review Stops For Permit 19080544
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-22 Cont ID  
Sent By rmcdouga Date 2020-04-22 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2020-04-22 Time 10:08 Sent To  
Notes
2020-04-22 10:45:17BUILDING PROVISO:
 THE PROPOSAL STATES THAT THE GENERATOR SLAB WILL BE
 PROVIDED BY OTHERS. A SEPARATE PERMIT IS REQUIRED FOR
 THE SLAB. THE GENERATOR IS TO BE INSTALLED PER THE
 MANUFACTURER'S SPECIFICATIONS. THE DISTANCE FROM
 GENERATOR EXHAUST TO ANY OPENINGS SHALL BE AS SPECIFIED
 IN THE MANUFACTURER'S SPECIFICATIONS OR 10 FEET IF NOT
 PROVIDED IN THE SPECIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By rmcdouga Date 2019-10-11 Time 12:57 Rev Time 0.00
Received By rmcdouga Date 2019-10-11 Time 12:57 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-09-11 Cont ID  
Sent By rmcdouga Date 2019-09-11 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2019-09-11 Time 09:50 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-04-30 Cont ID  
Sent By jleahy Date 2020-04-30 Time 14:03 Rev Time 0.00
Received By jleahy Date 2020-04-30 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-04-24 Cont ID  
Sent By jleahy Date 2020-04-24 Time 12:48 Rev Time 0.00
Received By jleahy Date 2020-04-24 Time 12:48 Sent To  
Notes
2020-04-24 12:52:11 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO RISER DIAGRAM SHOWN SHOWING THE WIRE SIZES AND
 BREAKER SIZES. 215.5
  
 2) SHOW SERVICE GROUNDING 250.32
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-11 Cont ID  
Sent By fgiaquin Date 2019-10-11 Time 05:57 Rev Time 0.00
Received By fgiaquin Date 2019-10-11 Time 05:54 Sent To B
Notes
2019-10-11 05:57:28PREVIOUS PLAN REVIEW COMMENTS NOT SATISFIED. SEE LAST
 PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-30 Cont ID  
Sent By fgiaquin Date 2019-08-30 Time 07:09 Rev Time 0.00
Received By fgiaquin Date 2019-08-30 Time 06:40 Sent To  
Notes
2019-08-30 07:09:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION IS INCORRECT.
  
 CALCULATED LOAD IS 96.5AMPS BUT IS SHOWN AS 82 AMPS PER
 PROVIDED LOAD CALC, ALSO,LOAD CALC SHOWS "DISHWASHER
 AND DISPOSAL EACH @ 1500WATTS BUT ONLY 1500 WATTS IS
 PROVIDED FOR THAT LINE, NOT 3000WATTS AS IT SHOULD BE.
 PLEASE ADD IN ALL LOADS AND PROVIDE CORRECT LOAD
 CALCULATION. NEC 220; FBC RE E3602.2
  
 42,894WATTS TOTAL
  
 1ST 10,000 WATTS @ 100%= 10,000 WATTS
  
 32,894 WATTS @ 40%= 13,895 WATTS.
  
 10,000+13,895+ 23,895
  
 23,895/240= 96.5AMPS
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. (ALL PAGES INCLUDING
 LOAD CALC) PROVIDE CORRECTION. FS 471.003(2)(H);
 471.025; WPB FBC 107.1
  
 3. VALUE LOW FOR AMOUNT OF WORK SHOWN, RAISE VALUE.
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-08-20 Cont ID  
Sent By lcrespo Date 2019-08-20 Time 16:05 Rev Time 0.00
Received By lcrespo Date 2019-08-20 Time 16:05 Sent To  
Notes
2019-08-20 16:07:39GAS LINES INSTALLED UNDER PERMIT 19080544

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-28 Cont ID  
Sent By lmarchan Date 2020-04-28 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2020-04-16 Time 10:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-11 Cont ID  
Sent By rmcdouga Date 2019-10-11 Time 12:57 Rev Time 0.00
Received By rmcdouga Date 2019-10-04 Time 14:05 Sent To  
Notes
2019-10-07 14:05:52RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-11 Cont ID  
Sent By rmcdouga Date 2019-09-11 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2019-08-09 Time 14:37 Sent To  
Notes
2019-08-12 14:37:30ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-28 Cont ID  
Sent By rfalcone Date 2020-04-28 Time 10:30 Rev Time 0.00
Received By rfalcone Date 2020-04-28 Time 10:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By rfalcone Date 2019-10-08 Time   Rev Time 0.00
Received By rfalcone Date 2019-10-08 Time 11:23 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By ajones Date 2019-08-13 Time 14:04 Rev Time 0.00
Received By ajones Date 2019-08-13 Time 14:04 Sent To  
Notes
2019-08-13 14:08:548/13/19- FAILED
  
 SECTION 94-305 (4) PERMITS A GENERATOR TO ENCROACH 4
 FEET INTO ANY REQUIRED SETBACK. THE REQUIRED SETBACK
 FOR THIS HOME ALONG SENECA CIRCLE IS 25 FEET. THE
 GENERATOR CAN BE NO CLOSER THAN 21 FEET FROM THE
 PROPERTY LINE.
  
 ANGELLA VANN
 561-822-1441
 [email protected]