| Plan Review Stops For Permit 19080493 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2020-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-14 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-14 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2020-11-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-11-12 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-11-12 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2020-11-12 16:23:41 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC 2014 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: NEW PERMIT APPLICATION | | | | | | 1. SUBMIT A NEW PERMIT APPLICATION WITH REVISED SCOPE | | | OF WORK AND NEW VALUE BASED ON NEW SOW. | | | PERMITS - 105.1 REQUIRED. | | | | | | NOTE: E-MAIL THE NEW PERMIT APP, WITH YOUR NOTARIZED | | | SIGNATURE, TO ME AT THE E-MAIL ADDRESS ABOVE. I WILL | | | UPLOAD IT TO YOUR FILE AND ADJUST THE PERMIT VALUE. | | | YOU DO NOT HAVE TO SUBMIT A NEW OWNER /BUILDER | | | AFFIDAVIT. | | | | | | | | | | | 2020-11-03 11:29:57 | BLDG TO VERIFY NEW VALUATION & SCOPE OF WORK, AMEND | | | PERMIT APPLICATION DESCRIPTION AS NEEDED | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-23 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2020-05-27 14:09:52 | PLAN REVIEW - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 3RD REVIEW - NEW SOW - SINGLE STORY GARAGE ONLY | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, DOORS AND | | | OHD. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-04-30 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2020-05-05 14:00:23 | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | PLAN REVIEW - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROJECT INCLUDES TWO STRUCTURES. SEPERATE PERMIT | | | REQUIRED FOR EACH. PERMIT. 19080493 SHALL BE APPLIED TO | | | THE ONE STORY DWELLING UNIT. | | | SUBMIT A SEPERATE PERMIT FOR THE TWO STORY GARAGE. | | | | | | NOTE: BOTH STRUCTURES MAY REMAIN ON SINGLE SET OF | | | PLANS. | | | | | | 2. VALUE - CITY OF WPB CHPT. 1 VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. | | | | | | BASED ON THE ICC BUILDING VALUATION TABLES, THE VALUES | | | FOR EACH STRUCTURE WILL BE AS FOLLOWS: | | | ONE STORY DWELLING UNIT - $112,663.00. (920 SQ/FT X | | | $122.46 PER SQ/FT) | | | TWO STORY GARAGE - $73,872.00. (1200 SQ/FT X $ 61.56 | | | PER SQ/FT) | | | PLEASE APPLY THESE VALUES TO EACH PERMIT UPON | | | RE-SUBMITTAL. | | | | | | | | | 3. PROVIDE SITE DRAINAGE PLAN. | | | FBC R401.3 SITE DRAINAGE | | | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBC R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | | | | 4. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH | | | OPENINGS AND DESIGN PRESSURES FOR EACH OPENING. | | | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. | | | | | | 5. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 6. STRUCTURAL ANALYSIS PROVIDED FOR TWO STORY GARAGE. | | | PROVIDE ANALYSIS FOR ONE STORY DWELLING UNT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-13 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-13 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2019-09-13 11:17:19 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. LOT IS ZONNED AS SF-7 LOW DENSITY. ZONING APPROVAL | | | REQUIRED FOR 2ND STRUCTURE. | | | | | | NO REVIEW PERFORMED AT THIS TIME |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-10-08 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-10-08 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2020-06-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-24 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-24 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2020-06-24 08:47:12 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SEPARATE STRUCTURE (GARAGE) TO HAVE A PANEL | | | INSTALLED BECAUSE OF THE NUMBER OF BRANCH CIRCUITS | | | INSTALLED, SEE 225.30 | | | | | | 225.30 NUMBER OF SUPPLIES A BUILDING OR OTHER STRUCTURE | | | THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE | | | LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL BE | | | SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS | | | PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF | | | THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE | | | CONSIDERED A SINGLE CIRCUIT. | | | | | | 2) SEPARATE STRUCTURES TO HAVE GROUNDING ELECTRODE | | | SYSTEMS INSTALLED, SEE 250.32 | | | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE. | | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | | PART III OF ARTICLE 250 | | | | | | 3) PANEL SCHEDULE REQUIRED FOR NEW PANEL IN GARGE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-05-04 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-05-04 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-05-04 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2020-05-04 15:45:30 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 (NOT PROVIDED.) | | | 8. CORRECTED. | | | 9. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 10. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | | FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC | | | 225.30 | | | 11. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR | | | A BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | | 12. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER AT THE PANEL FOR PANEL P.1. NEC 225.31, | | | 225.32 | | | 13. HOW WILL PANELP.1 BE FED? IF THERE IS A 200 AMP | | | MAIN BREAKER AS THE RISER DIAGRAM SHOWS, THEN THE WIRE | | | TO PANEL P.1 WILL NEED TO BE RATED FOR 200 AMPS. IF | | | THERE IS A 150 AMP BREAKER FEEDING THIS, PROVIDE | | | DETAILS IN RISER DIAGRAM AND PANEL SCHEDULE. TYPICALLY, | | | A 200 AMP METER MAIN HAS FEED THROUGH LUGS AND BREAKER | | | SPACES THAT COULD BE USED FOR THE GARAGE. HOWEVER, THIS | | | INFORMATION IS NOT CLEAR ON PLAN. PROVIDE | | | CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED. NEC 215.2, | | | 240.4, 310.15; FBC RE E3603.1, E3705.1; WPB FBC 107.2.1 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-09-05 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-30 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2019-09-05 13:08:07 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS | | | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB | | | FBC 107.2.1; NEC 230.2; FBC RE E3601.2 | | | 2. IDENTIFY ELECTRICAL PANELS ON PLAN, SHOW EACH PANEL | | | LOCATION. WPB FBC 107.2.1 | | | 3. RISER DIAGRAM INDICATES THAT THERE ARE 3 ELECTRICAL | | | PANELS, PANEL A, B, AND C. ONLY 2 PANEL SCHEDULES ARE | | | PROVIDED. WHERE IS PANEL A, AND IS PANEL C FED FROM | | | THIS? PROVIDE CLARIFICATIONS AND CORRERCTIONS AS | | | NEEDED. WPB FBC 107.2.1; NEC 215.5 | | | 4. ELECTRICAL NOTE # 3 STATES THAT RECEPTACLES SHALL BE | | | TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION DOES | | | NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | | CORRECTION. NEC 406.12; FBC RE E4002.14 | | | 5. GENERAL NOTE # 14 STATES THAT ALL LIGHTING IN | | | CLOSETS SHALL COMPLY WITH NEC 410.8. THIS CODE SECTION | | | DOES NOT APPLY TO CLOSETS. PROVIDE CORRECTION. NEC | | | 410.16; FBC RE E4003.12 | | | 6. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, | | | 801.2, OR 901.2 AS APPLICABLE. | | | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 8. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | | FBC EC C405.1, R404.1 | | | 9. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
2 |
Status |
N |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-23 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-05 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2020-05-05 12:52:28 | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | PLAN REVIEW - LOW VOLTAGE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PROVIDE AN ELECTRICAL PLAN FOR NEW DWELLING UNIT. | | | ELECTRICAL PLAN SUBMITTED FOR REVIEW IS FOR THE | | | NON-HABITABLE 2 STORY GARAGE BUT INCLUDES A LOAD | | | CALCULATION WHICH INCLUDES AIR CONDITIONING, SMALL | | | APPLIANCES, ETC. | | | | | | CANNOT DETERMINE IF LOW VOLTAGE APPLYS. 2ND REVIEW | | | REQUIRED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2021-01-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-01-07 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-12-30 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2020-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-14 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-03 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2020-12-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-12-03 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-11-03 |
Time |
16:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-10-29 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-10-22 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-29 |
Time |
10:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2020-06-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-24 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-09 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-05-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-05-15 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-21 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-04-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-17 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-16 |
Time |
11:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-13 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-08-09 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-05 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2020-05-05 12:36:20 | PROJECT CONSISTS OF TWO SEPERATE STRUCTURES REQUIRING | | | TWO SEPERATE PERMITS. | | | | | | IMPACT FEES WILL ONLY APPLY TO THE HABITABLE STRUCTURE. | | | THE GARAGE IS EXEMPT FROM IMPACT FEES PER WILLIE SWOOP, | | | PALM BEACH COUNTY IMPACT FEE OFFICE. | | | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-13 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-13 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2019-09-13 11:18:35 | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-04-30 |
Time |
11:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-09-09 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-09-09 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-05 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2020-05-05 13:30:28 | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | PLAN REVIEW - PLUMBING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. | | | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PLEASE PROVIDE MANUFACTURES SPECIFICATION FOR INSTA | | | HOT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. | | | INFORMATION ON CONSTRUCTION DOCUMENTS. (NOT ADDRESSED) | | | | | | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | | PLUMBING. (NOT ADDRESSED) | | | | | | 3. BACKFLOW PREVENTER FOR IRRIGATION AND MAIN SERVICE | | | REQUIRED PER THE CITY OF WEST PALM BEACH ORD #2853-95. | | | A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND MUST BE | | | CERTIFIED BY UTILITIES PRIOR TO FINAL INSPECTION. | | | PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 | | | FOR FURTHER DIRECTIONS. (NOT ADDRESSED) | | | | | | NEW COMMENT: | | | | | | 1. PROVIDE WATER DISTRIBUTION DIAGRAHM. | | | | | | P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. | | | THE WATER SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL | | | BE DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT | | | UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE | | | POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN | | | IN TABLE P2903.1. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-27 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-27 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2019-08-27 07:20:57 | 08/27/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE PROVIDE MANUFACTURES SPECIFICATION FOR INSTA | | | HOT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | | PLUMBING. | | | | | | 3. BACKFLOW PREVENTER FOR IRRIGATION AND MAIN SERVICE | | | REQUIRED PER THE CITY OF WEST PALM BEACH ORD #2853-95. | | | A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND MUST BE | | | CERTIFIED BY UTILITIES PRIOR TO FINAL INSPECTION. | | | PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 | | | FOR FURTHER DIRECTIONS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-23 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2020-05-27 14:11:57 | PLAN REVIEW - ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 3RD REVIEW - NEW SOW - SINGLE STORY GARAGE ONLY | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM | | | COMPONETS. | | | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-05 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-04-30 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2020-05-05 13:04:04 | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | PLAN REVIEW - ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? BUILDING - PX3169 | | | PLANS EXAMINER ? 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | PERMITS | | | 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | | SYSTEM COMPONENTS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-13 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-13 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2019-09-13 11:17:52 | SEE COMMENTS UNDER BUILDING REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2020-12-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-14 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-14 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2020-11-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-11-12 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-11-12 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-10-09 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-10-09 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-23 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-05-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-05-27 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-05-27 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-21 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-21 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2020-04-21 07:19:22 | ORIGINAL PAPER PLANS PROVIDED FOR REVIEW CYCLE #1 | | | (CONVERTED TO DIGITAL) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
P |
Date |
2021-01-07 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-01-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-01-07 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-01-07 13:39:11 | REFERENCE: SEPARATE DRIVEWAY PERMIT #20120604. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
F |
Date |
2020-12-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-12-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-12-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-09 10:48:53 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($56,820) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | [6/22/2020, 10/22/2020,10/29/2020 AND 11/13/2020 REPEAT | | | COMMENTS: NOT ADDRESSED. NO RECORD OF LANDSCAPE PERMIT | | | SUBMITTED. LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR TO | | | ZONING APPROVAL OF PERMIT.] | | | | | | | | | | | | NOTES: | | | | | | * SPOKE TO MARCELA BURBANO OF FLORIDA BUILDING PLANS ON | | | 10/29/20 TO GO OVER OUTSTANDING COMMENTS NOT ADDRESSED | | | FOR ZONING. | | | | | | * SEPARATE PERMIT REQUIRED FOR THE PROPOSED DRIVEWAY | | | EXTENSION LEADING TO THE NEW 750 SQ. FT. ACCESSORY | | | GARAGE STRUCTURE. DRIVEWAY PERMIT MUST BE SUBMITTED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | | FOR THE GARAGE STRUCTURE. ALTHOUGH A SEPARATE PERMIT IS | | | REQUIRED FOR THE DRIVEWAY, THE PROPOSED DRIVEWAY MUST | | | BE SHOWN IN THE PLANS AND MUST ALSO DEMONSTRATE | | | CONSISTENCY WITH THE ZLDRS. | | | | | | * MINIMUM 3 FT. SETBACK REQUIRED FOR NEW DRIVEWAY | | | EXTENSION FROM PROPERTY LINE (ADD CONDITION). | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561) | | | 822-1458 IF THERE ARE ANY QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | * SPOKE TO DEENA MAY, PROPERTY OWNER, ON 12/9/2020 | | | INFORMING THAT ZONING REVIEW CANNOT PASS UNTIL A | | | SEPARATE LANDSCAPE PERMIT IS SUBMITTED. ALSO, A | | | SEPARATE DRIVEWAY PERMIT WILL BE REQUIRED FOR NEW | | | DRIVEWAY EXTENSION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
F |
Date |
2020-11-13 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-11-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-11-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-11-13 14:56:59 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($56,820) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | [6/22/2020, 10/22/2020 AND 10/29/2020 REPEAT COMMENTS: | | | NOT ADDRESSED. NO RECORD OF LANDSCAPE PERMIT SUBMITTED. | | | LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR TO ZONING | | | APPROVAL OF PERMIT.] | | | | | | | | | | | | NOTES: | | | | | | * SPOKE TO MARCELA BURBANO OF FLORIDA BUILDING PLANS ON | | | 10/29/20 TO GO OVER OUTSTANDING COMMENTS NOT ADDRESSED | | | FOR ZONING. | | | | | | * SEPARATE PERMIT REQUIRED FOR THE PROPOSED DRIVEWAY | | | EXTENSION LEADING TO THE NEW 750 SQ. FT. ACCESSORY | | | GARAGE STRUCTURE. DRIVEWAY PERMIT MUST BE SUBMITTED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | | FOR THE GARAGE STRUCTURE. ALTHOUGH A SEPARATE PERMIT IS | | | REQUIRED FOR THE DRIVEWAY, THE PROPOSED DRIVEWAY MUST | | | BE SHOWN IN THE PLANS AND MUST ALSO DEMONSTRATE | | | CONSISTENCY WITH THE ZLDRS. | | | | | | * MINIMUM 3 FT. SETBACK REQUIRED FOR NEW DRIVEWAY | | | EXTENSION FROM PROPERTY LINE (ADD CONDITION). | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561) | | | 822-1458 IF THERE ARE ANY QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-10-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-10-29 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-29 15:21:18 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PERMIT PLANS KEEP CHANGING TO SHOW INCONSISTENCIES | | | WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS | | | (ZLDRS). FOR THIS PERMIT RESUBMITTAL, A NEW DRIVEWAY | | | WAS ADDED (SEE "PROPOSED DRIVEWAY" IN PERMIT PLAN). PER | | | ZLDR S.94-312(1), ONLY ONE DRIVEWAY AT A MAXIMUM WIDTH | | | OF 20 FT. SHALL BE PROVIDED FOR A SINGLE-FAMILY | | | RESIDENCE, AND AT LEAST 1,000 SQ. FT. OR 75% (WHICHEVER | | | IS LESS) OF THE REQUIRED FRONT YARD SHALL REMAIN | | | LANDSCAPED. [ZLDR S.94-482] [10/22/20 REPEAT COMMENT - | | | ALL PERMIT PLANS SHALL BE MADE CONSISTENT] | | | | | | 2.) DRIVEWAY EXTENSION MUST BE SET BACK AT LEAST 3 FT. | | | FROM THE SIDE PROPERTY LINE. [NOTE: ERROR BY STAFF ON | | | LAST REVIEW.] [10/22/20 REPEAT COMMENT] | | | | | | 3.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($56,820) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | [6/22/2020 AND 10/22/2020 REPEAT COMMENT: NOT | | | ADDRESSED. NO RECORD OF LANDSCAPE PERMIT SUBMITTED. | | | LANDSCAPE PERMIT SHALL BE SUBMITTED PRIOR TO ZONING | | | APPROVAL OF PERMIT.] | | | | | | | | | | | | NOTES: | | | | | | * SPOKE TO MARCELA BURBANO OF FLORIDA BUILDING PLANS ON | | | 10/29/20 TO GO OVER OUTSTANDING COMMENTS NOT ADDRESSED | | | FOR ZONING. | | | | | | * SEPARATE PERMIT REQUIRED FOR THE PROPOSED DRIVEWAY | | | EXTENSION LEADING TO THE NEW 750 SQ. FT. ACCESSORY | | | GARAGE STRUCTURE. DRIVEWAY PERMIT MUST BE SUBMITTED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | | FOR THE GARAGE STRUCTURE. ALTHOUGH A SEPARATE PERMIT IS | | | REQUIRED FOR THE DRIVEWAY, THE PROPOSED DRIVEWAY MUST | | | BE SHOWN IN THE PLANS AND MUST ALSO DEMONSTRATE | | | CONSISTENCY WITH THE ZLDRS. | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561) | | | 822-1458 IF THERE ARE ANY QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2020-10-02 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-10-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-02 08:56:23 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PERMIT PLANS KEEP CHANGING TO SHOW INCONSISTENCIES | | | WITH THE ZONING AND LAND DEVELOPMENT REGULATIONS | | | (ZLDRS). FOR THIS PERMIT RESUBMITTAL, A NEW DRIVEWAY | | | WAS ADDED (SEE "PROPOSED DRIVEWAY" IN PERMIT PLAN). PER | | | ZLDR S.94-312(1), ONLY ONE DRIVEWAY AT A MAXIMUM WIDTH | | | OF 20 FT. SHALL BE PROVIDED FOR A SINGLE-FAMILY | | | RESIDENCE, AND AT LEAST 1,000 SQ. FT. OR 75% (WHICHEVER | | | IS LESS) OF THE REQUIRED FRONT YARD SHALL REMAIN | | | LANDSCAPED. [ZLDR S.94-482] | | | | | | 2.) DRIVEWAY EXTENSION MUST BE SET BACK AT LEAST 3 FT. | | | FROM THE SIDE PROPERTY LINE. [NOTE: ERROR BY STAFF ON | | | LAST REVIEW.] | | | | | | 3.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($56,820) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | [6/22/2020 REPEAT COMMENT: NOT ADDRESSED. NO RECORD OF | | | LANDSCAPE PERMIT SUBMITTED. LANDSCAPE PERMIT SHALL BE | | | SUBMITTED PRIOR TO ZONING APPROVAL OF PERMIT.] | | | | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMIT REQUIRED FOR THE PROPOSED DRIVEWAY | | | EXTENSION LEADING TO THE NEW 750 SQ. FT. ACCESSORY | | | GARAGE STRUCTURE. DRIVEWAY PERMIT MUST BE SUBMITTED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | | FOR THE GARAGE STRUCTURE. ALTHOUGH A SEPARATE PERMIT IS | | | REQUIRED FOR THE DRIVEWAY, THE PROPOSED DRIVEWAY MUST | | | BE SHOWN IN THE PLANS AND MUST ALSO DEMONSTRATE | | | CONSISTENCY WITH THE ZLDRS. | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561) | | | 822-1458 IF THERE ARE ANY QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2020-06-22 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-06-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-06-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-06-22 09:56:41 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) WHAT IS THE SETBACK DIMENSION FROM THE PROPOSED NEW | | | DRIVEWAY EXTENSION TO THE PROPERTY LINE? PLEASE NOTE | | | THAT PURSUANT TO ZLDR S.94-305(7), THE PROPOSED | | | DRIVEWAY EXTENSION SHALL BE SETBACK A MINIMUM OF 2 FT. | | | FROM THE SIDE PROPERTY LINE. | | | | | | 2.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE?S | | | VALUE ($56,820) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * SEPARATE PERMIT REQUIRED FOR THE PROPOSED DRIVEWAY | | | EXTENSION LEADING TO THE NEW 750 SQ. FT. ACCESSORY | | | GARAGE STRUCTURE. DRIVEWAY PERMIT MUST BE SUBMITTED | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | | FOR THE GARAGE STRUCTURE. | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-05-14 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-05-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-05-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-05-14 17:27:26 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE PROPERTY IS ZONED SINGLE-FAMILY LOW DENSITY | | | (SF7) RESIDENTIAL. THE SF7 ZONING DISTRICT DOES NOT | | | ALLOW FOR AN ACCESSORY DWELLING UNIT. [8/16/20 REPEAT | | | COMMENT] | | | | | | 2.) ALL OTHER ACCESSORY STRUCTURES SHALL NOT EXCEED | | | 1,000 SQ. FT. OR 75% OF THE GROSS FLOOR AREA OF THE | | | EXISTING STRUCTURE, WHICHEVER IS LESS (INCLUDES THE | | | GARAGE AND LOFT SPACE). [ZLDR S.94-304(B)] [8/16/20 | | | REPEAT COMMENT] | | | | | | NOTES: | | | | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-08-16 |
Time |
11:51 |
Rev Time |
|
| Received By |
llouie |
Date |
2019-08-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-08-16 11:53:32 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE PROPERTY IS ZONED SINGLE-FAMILY LOW DENSITY | | | (SF7) RESIDENTIAL. THE SF7 ZONING DISTRICT DOES NOT | | | ALLOW FOR AN ACCESSORY DWELLING UNIT. | | | | | | 2.) ALL OTHER ACCESSORY STRUCTURES SHALL NOT EXCEED | | | 1,000 SQ. FT. OR 75% OF THE GROSS FLOOR AREA OF THE | | | EXISTING STRUCTURE, WHICHEVER IS LESS (INCLUDES THE | | | GARAGE AND LOFT SPACE). [ZLDR S.94-304(B)] | | | | | | NOTES: | | | | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|