| Plan Review Stops For Permit 19080446 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2020-01-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-30 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-09 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2019-12-09 11:01:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SLS DOCUMENT INDICATES 89 PAGES, ON REVIEW PAGES | | | 46 THRU 89 ARE BLACK. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 2) THERE ARE NO INDICATIONS OF CHANGES TO THE SLS | | | DOCUMENT. | | | | | | ARE THERE CHANGES TO THIS DOCUMENT? | | | | | | PLEASE PROVIDE PAGE NUMBERS FOR THE CHANGES. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-10-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-10-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-10-09 |
Time |
12:28 |
Sent To |
I |
|
| Notes |
| 2019-10-18 15:24:04 | PLEASE ADDRESS MECHANICAL COMMENTS AS FIRE IS IN | | | AGREEMENT WITH THOSE ITEMS AND WILL NOT BE LISTED | | | SEPARATELTY HERE. | | | | | | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-08-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-08-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-08-13 |
Time |
11:31 |
Sent To |
M |
|
| Notes |
| 2019-08-13 13:33:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PAPERWORK DOES NOT INDICATE WHAT THE | | | REVISIONS IS AND WHERE, HOW AND WHY THE REVISIONS TAKE | | | PLACE. | | | | | | BASICALLY, WHAT CHANGED AND WHY? THERE SHOULD BE SOME | | | SORT OF NARRATIVE EXPLAINING THE CHANGE. | | | | | | AM I TO BELEIVE THE ENTIRE DOCUMENT IS THE REVISION? | | | | | | PER NFPA 1 | | | 1.14 PLAN REVIEW. | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE | | | REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS, | | | ARE LOCATED. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-01-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-12-30 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-12-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-02 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-10-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-10-18 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-10-08 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-08-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-08-19 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-08-08 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2019-08-09 15:42:51 | ROUTED TO FIRE INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-06 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-06 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-12-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-12 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-12 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2019-12-12 12:17:43 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19080446 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENTS #1 & 2 FROM THE 1ST REVIEW HAVE NOT BEEN | | | COMPLETELY ADDRESSED- SEE BELOW AND COMPLY. | | | | | | 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED | | | NARRATIVE TO CLARIFY THE SCOPE OF WORK RELATING TO THE | | | SLS PERFORMANCE BASED SMOKE ANALYSIS. | | | | | | 2) THE SLS PERFORMANCE BASED SMOKE ANALYSIS SHALL EACH | | | BE ELECTRONICALLY SIGNED AND SEALED- SECTION | | | 61G15-23.005 FAC AND SECTION 471.025 FL. STATUTES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-10-18 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-10-18 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-10-11 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2019-10-18 08:56:52 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19080446 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED | | | NARRATIVE TO CLARIFY THE SCOPE OF WORK RELATING TO THE | | | FLAMEBAR SUBMITTAL AND THE SLS PERFORMANCE BASED SMOKE | | | ANALYSIS. IT APPEARS THAT THESE TWO ITEMS ARE NOT | | | RELATED BECAUSE THE USE OF THE FLAMEBAR AS AN ALTERNATE | | | TO CONSTRUCTED SHAFTS IS NOT INCLUDED IN THE ANALYSIS | | | FOR THE ATRIUM. | | | | | | 2) THE TWO SUBMITTAL DOCUMENTS- IBC 104.11 ALTERNATE | | | MEANS AND METHODS- FIRE RATED VENTILATION DUCT THE | | | CANOPY HOTEL BY HILTON BY STEVEN FELLER P.E., AND THE | | | SLS PERFORMANCE BASED SMOKE ANALYSIS SHALL EACH BE | | | ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005 | | | FAC. | | | | | | 3) IBC 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED | | | VENTILATION DUCT THE CANOPY HOTEL BY HILTON- SHEET | | | AC-2-4 LEVEL-2 WEST: THE FLAMEBAR LAUNDRY EXHAUST DUCTS | | | PENETRATING THE INTERIOR EXIT STAIR #2 APPEAR TO BE NOT | | | IN COMPLIANCE WITH SECTION 1023.5 FBC B WHICH PROHIBITS | | | PENETRATIONS INTO AND THROUGH THE STAIRWAY ENCLOSURE. | | | PLEASE NOTE THAT NO DETAIL FOR THIS ALTERNATE | | | INSTALLATION HAS BEEN PROVIDED IN THE PACKAGE, AND THE | | | USE OF FLAMEBAR FOR THE INSTALLATION IS NOT INCLUDED IN | | | THE FLORIDA BUILDING COMMISSION DECALARATORY STATEMENT | | | DS 2016-078 THAT WAS SUBMITTED WITH THE ALTERNATE | | | APPROVAL LETTER. | | | | | | 4) SHEET M2.08A: THERE ARE VARIOUS FLAMEBAR/NON-RATED | | | DUCT CONNECTORS CALLED OUT IN THE ENLARGED PENETRATION | | | DETAIL. PLEASE SELECT ONE SPECIFIC CONNECTOR AND | | | SUBMIIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE CONNECTOR. PLEASE INDICATE WHERE | | | THE CONNECTORS ARE SHOWN AND INCLUDED IN THE | | | ALTERNATIVE APPROVAL PACKAGE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-08-19 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-08-19 |
Time |
11:07 |
Sent To |
I |
|
| Notes |
| 2019-08-19 11:08:14 | PLAN DENIED | | | SEE FIRE COMMENTS HM. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-01-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-06 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-06 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-12-12 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-12 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-12 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2019-12-12 12:20:50 | AS NOTED IN THE PREVIOUS MECHANICAL AND SIGNATURE | | | REVIEWS, THE SLS SMOKE CONTROL ANALYSIS SHALL BE | | | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER WHO | | | PREPARED THE DOCUMENT- SECTION 471.025 FL. STATUTE, AND | | | SECION 61G15-23.005 FAC. | | | CCOLE- 12/12/19 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-10-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-10-18 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-10-18 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2019-10-18 15:42:07 | THE TWO DOCUMENTS ARE NOT DIGITALLY SIGNED. |
|
|