| 2019-08-28 05:59:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. UNABLE TO COMPLETE REVIEW. NOTES ON PLAN FROM P.E. |
| | DENNIS J. HERGENRETHER LICENSE #73535 "PLANS HAVE BEEN |
| | RELEASED FOR INTERIM REVIEW ONLY AND ARE NOT TO BE USED |
| | FOR CONSTRUCTION, BIDDING, OR PERMITTING. |
| | |
| | 2. PERMIT APPLICATION SAYS "LOW VOLTAGE" ONLY. PLEASE |
| | BE MORE SPECIFIC IN THE DESCRIPTION. WHICH LOW VOLTAGE |
| | SYSTEMS ARE TO BE INSTALLED IN THIS SCOPE OF WORK? FBC |
| | 107.2.1 |
| | |
| | 3. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF ALL LOW |
| | VOLTAGE DEVICES. FBC 107.2.1 NEC 90.7,110.2, 110.3B |
| | |
| | 4. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |