| Plan Review Stops For Permit 19080419 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-11-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-21 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-21 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-09-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-16 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-13 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2019-09-16 08:20:14 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19080419 | | | REVIEWED: SEPTEMBER 16, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) PROVISOS: | | | DEFERRED SUBMITTALS- | | | INTERIOR STAIRWAY, RAILS AND GUARDS | | | EXTERIOR STAIRWAY RAILS AND GUARDS | | | SEPARATE PERMITS REQUIRED FOR-LANDSCAPE, FENCES | | | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM | | | SAT-SUN | | | - NO RESPONSE REQUIRED. PROVISOS WILL BE ADDED TO THE | | | PLANS AT FINAL STAMPING. | | | | | | 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH | | | CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN | | | ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL | | | COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK. | | | | | | 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: | | | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN | | | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF | | | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED | | | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY | | | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. | | | - PLEASE PROVIDE DOCUMENTATION TO SUPPORT THE METHOD | | | CHOSEN FOR COMPLIANCE. | | | | | | 4) 408.1 FBC[R] PROVIDE VENTING CALCULATIONS FOR UNDER | | | FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED. | | | - IF ADDITION CRAWL SPACE COMMUNICATES WITH EXISTING | | | PLEASE INCLUDE EXISTING IN CALCULATION. | | | | | | 5) 408.4 FBC[R] PROVIDE ACCESS TO THE UNDER FLOOR SPACE | | | 18X24 MINIMUM. | | | - SHOW EXISTING ACCESS, OR PROVIDE ACCESS POINT TO | | | FLOOR CRAWL SPACE IF APPLICABLE. | | | | | | 6) 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE ATTIC | | | AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW | | | R806.5 FOR UNVENTED. | | | - PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION | | | AND ATTACHMENT ACCORDING TO GENERAL LIMITATIONS 7 ON | | | NOA 15-0729.18 | | | | | | 7) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED | | | RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE | | | INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL | | | ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH | | | SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE | | | INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL | | | SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE | | | INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING | | | IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR | | | CONDENSATION CONTROL. | | | - PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE | | | INSULATION AT ROOF DECK. | | | | | | 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOW MULL AND GARAGE DOORS, OR INDICATE THAT YOU | | | WOULD LIKE THEM DEFERRED. | | | - | | | | | | 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT ATTACHMENT | | | FOR ROOF INSULATION, OR INDICATE THAT YOU WOULD LIKE IT | | | DEFERRED. | | | - ALSO, PROVIDE ENHANCED NAILING ENGINEERED FOR | | | EXPOSURE C IN THE 3 WIND ZONES ESTABLISHED ON SHEET | | | A-2C. PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF | | | INSULATION AND ATTACHMENT ACCORDING TO GENERAL | | | LIMITATIONS 7 ON NOA 15-0729.18 | | | | | | 10) 107.2.1.2 FBC[AMENDED] SUBMIT TWO SETS OF SHOP | | | DRAWINGS FOR STAIRCASE, APPROVED BY DESIGNER OF RECORD, | | | FOR REVIEW BY WPB BUILDING DEPARTMENT AS A SUBMITTAL. | | | | | | NOTES: | | | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-01-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-01-09 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-09 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-12-09 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-12-09 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2019-12-09 15:15:19 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 (NOT PROVIDED.) | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. RISER DIAGRAM SHOWS A 225 AMP DISCONNECT AND PANEL | | | FOR MAIN HOUSE. THE WIRE SIZE SHOWN FEEDING THESE ITEMS | | | IS 2/0. THIS WIRE SIZE IS NOT RATED FOR A 225 AMP | | | SERVICE. PROVIDE CORRECTION. NEC 310.15(B)(7) AND | | | (B)(16); FBC RE E3603.1, E3705.1 (THE RISER NOW SHOWS A | | | 200 AMP DISCONNECT TO THE MAIN HOUSE, BUT THE WIRE IS | | | STILL TOO SMALL. 2/0 WIRE IS ONLY RATED FOR 175 AMPS, | | | UNLESS THE EXCEPTION IN NEC 310.15(B)(7) APPLIES, WHICH | | | IN THIS CASE IT DOES NOT. PROVIDE CORRECTION.) | | | 5. CORRECTED. | | | 6. CORRECTED. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-08-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-08-30 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-30 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2019-08-30 10:32:39 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 2. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS | | | PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB | | | FBC 107.2.1; NEC 230.2; FBC RE E3601.2 | | | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 4. RISER DIAGRAM SHOWS A 225 AMP DISCONNECT AND PANEL | | | FOR MAIN HOUSE. THE WIRE SIZE SHOWN FEEDING THESE ITEMS | | | IS 2/0. THIS WIRE SIZE IS NOT RATED FOR A 225 AMP | | | SERVICE. PROVIDE CORRECTION. NEC 310.15(B)(7) AND | | | (B)(16); FBC RE E3603.1, E3705.1 | | | 5. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS | | | LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY | | | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS | | | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE | | | CORRECTION. NEC 410.16; FBC RE E4003.12 | | | 6. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC | | | 410.10(D); FBC RE E4003.11 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-26 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-26 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2019-08-26 07:18:57 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT | | | THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-11-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-11-25 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-11-25 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-08-29 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-08-29 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-08-29 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-01-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-12-27 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-12-10 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-11-15 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2019-12-09 17:31:30 | TO HM DESK | | | | | 2019-11-18 15:23:55 | R37 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-09-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-16 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-08 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-01-30 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-30 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-30 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2020-01-30 14:16:44 | MU 2020-002693-0000 | | | NO FEES PAID | | | PLANS STAMPED - OK |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-13 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-13 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2019-09-13 14:14:26 | 109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU | | | MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-01-03 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2020-01-03 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2020-01-03 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-12-10 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-12-10 |
Time |
10:36 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-09-09 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-09-09 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2019-09-09 13:26:51 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - NEED MANUAL J OR OTHER APPROVED HEATING AND COOLING | | | CALCULATION METHODOLOGIES. PER 2017 FLORIDA BUILDING | | | CODE - RESIDENTIAL SEC M1401.3 EQUIPMENT AND APPLIANCE | | | SIZING. | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-21 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-21 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2020-01-21 08:50:02 | ELEVATION CERTIFICATE RECEIVED. | | | BFE WITH FREEBOARD = 8' NAVD | | | PROPOSED BFE 8.55' NAVD |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2020-01-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-01-13 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-01-13 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2020-01-13 14:27:40 | THIS PROJECT IS A SUBSTANTIAL IMPROVEMENT AND WE WILL | | | NEED AN ELEVATION CERTIFICATE TO SHOW THE ADDITION | | | FINISHED FLOOR AT OR ABOVE 8' NAVD. | | | THE EXISTING SURVEY SHOWS FLOOR AT 8.55 NAVD SO THERE | | | SHOULD BE NO PROBLEM TO COMPLY WITH FLOOD ZONE | | | ORDINANCES IF THE FLOOR OF ADDITION MATCHES THE | | | EXISTING. | | | | | | THE INITIAL ELEVATION CERTIFICATE CAN BE E-MAILED TO ME | | | SO THE PERMIT CAN BE ISSUED. | | | HOWEVER, THE FINAL CONSTRUCTION ELEVATION CERTIFICATE | | | NEEDS TO BE ORIGINAL. | | | | | | DYLAN BATTLES | | | 561-805-6718 | | | [email protected] | | | | | | THE CITY OF WEST PALM BEACH | | | BUILDING PLANS EXAMINER PX4191 | | | | | | SUBSTANTIAL IMPROVEMENT REVIEW | | | ONLY THE PROPOSED RENOVATION AND DEMO | | | $35,000.00 19051565 DEMO PERMIT | | | $62,000.00 19080419 RENOVATION | | | $97,000.00 / 189,116.00 = 51% | | | | | | BFE=6' NAVD +2' FREEBOARD = 8' NAVD | | | ALL EXISTING AND NEW WORK IS ABOVE BFE. | | | CONFIRMED SURVEY SHOWS AT 8.55' NAVD | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-01-07 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-01-07 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-01-07 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2020-01-07 13:47:15 | PLUMBING COMMENTS: APPROVED; SEE PROVISOS ON MP-1 AND | | | MP-1C | | | | | | 1. A BACKFLOW DEVICE (REDUCED PRESSURE ZONE PRINCIPAL | | | BACKLFOW ASSEMBLY) MAY BE REQUIRED PER CITY OF WEST | | | PALM BEACH UTILITIES DEPARTMENT CROSS CONNECTION MANUAL | | | AND ORD #2853-95, PLEASE CALL 561-822-2240 FOR MORE | | | INFORMATION SINCE THIS IS A DUAL DWELLING. | | | 2. A SEPARATE GAS PLAN REVIEW WILL BE REQUIRED A GAS, A | | | GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | | ENTIRE SCOPE OF GAS WORK TO BE DONE AT THIS TIME PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | 3. PER FBC RES P3114.5, ACCESS SHALL BE PROVIDED TO AIR | | | ADMITTANCE VALVES. SUCH VALVES SHALL BE INSTALLED IN A | | | LOCATION THAT ALLOWS AIR TO ENTER THE VALVE. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-12-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-12-09 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-12-09 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2019-12-09 12:10:12 | 1) SHTS. D-1, A-1, A-2, A1C, & A-2C DO NOT BEAR THE | | | SEAL OF THE DESIGN PROFESSIONAL AS REQUIRED BY FL. | | | ADMIN. CODE RULE 61G1--16.001. PLEASE SEAL THE | | | AFOREMENTIONED SHEETS. | | | 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER FOR | | | THE MAIN HOUSE ON THE ARCHITECTURAL PLANS. THE TANKLESS | | | WATER HEATER IS USUALLY REQUIRED TO BE A MINIMUM OF 48 | | | INCHES FROM ANY OPERABLE DOOR, WINDOW OR BUILDING | | | OPENING INCLUDING SOFFIT VENTS PER THE MANUFACTURER'S | | | INSTALLATION MANUAL. | | | 3) SIZE ALL THE DRAINAGE LINES AND VENT LINES ON ALL | | | RISER DIAGRAMS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) MASTER BATH SANITARY RISER - THE TUB, WATER CLOSET | | | AND SHOWER ARE NOT VENTED. 2017 FBCR SEC. P3101.2, | | | P3108.1. | | | 5) ACCESS SHALL BE PROVIDED TO THE SHUTOFF VALVES FOR | | | THE WASHING MACHINE. 2017 FBCR SEC. P2903.9.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-26 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-26 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2019-08-26 15:51:19 | 08/26/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON RISER DIAGRAM MP-1 FIRST FLOOR GUEST BATH SHOWER | | | LABELED AS LAV AND LAV NOT LABELED PLEASE MAKE CHANGES, | | | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) | | | RESIDENTIAL PLUMBING. | | | | | | 2. BATH 2 SHOWER IS NOT VENTED CORRECTLY, WET VENT | | | REQUIRED BETWEEN WATER CLOSET AND SHOWER, WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL | | | PLUMBING. | | | | | | 3. BATH 3 DIAGRAM HAS A WASHING MACHINE ON A 2" DRAIN, | | | PER MANUFACTURE SPECIFICATION ON MOST UNITS REQUIRE A | | | 3" DRAIN LINE, PLEASE SUBMIT SPECS ON WASHING MACHINE | | | OR MAKE CHANGES ON PIPE SIZE, WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING. | | | | | | 4. SANITARY RISER DIAGRAM MC-1C FOR CABANA BATH FIRST | | | FLOOR STACK TO THE SECOND FLOOR MUST BE ON ITS OWN | | | SYSTEM AND CANNOT VENT ON STACK, NEED KITCHEN ON ITS | | | OWN STACK AND LAV ON ITS OWN BATHROOM GROUP, WILL NEED | | | A AIR ADMITTANCE OR A VENT THROUGH ROOF FOR KITCHEN AND | | | BATHROOM GROUP DOWNSTAIRS, WPB AMENDMENTS TO THE FBC | | | SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING. | | | | | | 5. SANITARY RISER DIAGRAM MC-1C FOR CABANA BATH SECOND | | | FLOOR WAS LABELED AS 1ST FLOOR PLEASE CHANGE TO 2ND | | | FLOOR AND WASHING MACHINE STACK MUST BE 3" (REFER TO | | | COMMENT 3), SHOWER NEEDS WET VENT BETWEEN WC AND | | | SHOWER, PLEASE CHANGE, WPB AMENDMENTS TO THE FBC SEC. | | | 107.3.5.3 (11) RESIDENTIAL PLUMBING. | | | | | | 6. A BACKFLOW DEVICE (REDUCED PRESSURE ZONE PRINCIPAL | | | BACKLFOW ASSEMBLY) MAY BE REQUIRED PER CITY OF WEST | | | PALM BEACH UTILITIES DEPARTMENT CROSS CONNECTION MANUAL | | | AND ORD #2853-95, PLEASE CALL 561-822-2240 FOR MORE | | | INFORMATION SINCE THIS IS A DUAL DWELLING. | | | | | | 7. A SEPARATE GAS PLAN REVIEW WILL BE REQUIRED A GAS, A | | | GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | | ENTIRE SCOPE OF GAS WORK TO BE DONE AT THIS TIME PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 8. SHOWER PAN DETAIL REFERS TO PLB 471.5.2 WHICH IS NOT | | | THE RESIDENTIAL CODE 2017 FBC RES. SEC 2709.2 LINING | | | REQUIRED, PLEASE REVISE TO REFLECT RESIDENTIAL CODE, | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF | | | BUILDING PLANS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-09-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-16 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-13 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2019-09-16 08:18:40 | SEE BUILDING COMMENTS 6,7 AND 9. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-11-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-11-25 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-11-25 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-08-29 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-08-29 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-08-29 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|