Plan Review Details - Permit 19080417
Plan Review Stops For Permit 19080417
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By jleahy Date 2019-10-02 Time 09:01 Rev Time 0.00
Received By jleahy Date 2019-10-02 Time 09:01 Sent To  
Notes
2019-10-02 09:01:54PASSED ON ELECTRICAL BASED ON COMMENTS FROM RMD JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-14 Cont ID  
Sent By pvalenti Date 2019-09-14 Time 16:56 Rev Time 0.00
Received By pvalenti Date 2019-09-14 Time 16:56 Sent To  
Notes
2019-09-14 16:58:45***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 1609.1.1(8) THERE ARE NO ATTACHMENT DETAILS (FOR
 WINDLOADS) OF GENERATOR TO PAD CONNECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By rmcdouga Date 2019-08-20 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2019-08-20 Time 07:11 Sent To  
Notes
2019-08-20 08:31:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD DETAILS. SPECIFY
 THE GENERATOR TO PAD ATTACHMENT DETAILS. FBC 1609.1.1
 (8)

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-01 Cont ID  
Sent By jleahy Date 2019-10-01 Time 16:31 Rev Time 0.00
Received By jleahy Date 2019-10-01 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-17 Cont ID  
Sent By fgiaquin Date 2019-09-17 Time 07:18 Rev Time 0.00
Received By fgiaquin Date 2019-09-17 Time 06:45 Sent To Z
Notes
2019-09-17 07:11:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. COPIES OF SIGNATURES ARE NOT SUFFICIENT. PLEASE WET
 SIGN PLAN. . FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. PROVIDE SHORT-CIRCUIT CALCULATION FOR ATS. . NEC
 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 12:42 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 12:42 Sent To  
Notes
2019-09-06 12:42:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE TO
 CONFIRM CAPACITY OF GENERATOR IS ADEQUATE. NEC 702.4
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS,
 TRANSFER SWITCH, AND PANELS. NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-09-27 Cont ID  
Sent By pleduc Date 2019-09-27 Time   Rev Time 0.00
Received By pleduc Date 2019-09-27 Time 11:39 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-09-09 Cont ID  
Sent By lcrespo Date 2019-09-19 Time 13:51 Rev Time 0.00
Received By pleduc Date 2019-09-09 Time 13:38 Sent To B
Notes
2019-09-09 13:49:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING
 GENERATOR REPLACEMENT OR NEW.
  
 PLEASE CLARIFY.
  
 COMPLIED WITH WRITTEN "NEW" ON PLAN.
  
  
  
 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF
 APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM,
 FIRE ALARM AND/OR FIRE SPRINKLER.
  
 NOT COMPLIED
  
 PLEASE PROVIDE A NOTE OF COMPLIANCE WITH THE NOTED
 CODES.
  
  
  
 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE
 NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN
 CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST
 FUMES.
  
 NOT COMPLIED
  
 THE ACCUMULATION OF EXHAUST FUMES CAN BE TRAPPED UNDER
 CANOPYS AND SEEP THRU OVERHANGS, WINDOWS AND DOORS.
  
 PER NFPA 37
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE A ALL APPLICABLE DIMENSIONS.
  
  
  
 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP
 OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR
 PIPING.
  
 NOT COMPLIED
  
 IT APPEARS TO BE NG.....
  
 PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-20 Cont ID  
Sent By pleduc Date 2019-08-20 Time   Rev Time 0.00
Received By pleduc Date 2019-08-20 Time 14:00 Sent To E
Notes
2019-08-20 14:07:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING
 GENERATOR REPLACEMENT OR NEW.
  
 PLEASE CLARIFY.
  
  
  
 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF
 APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM,
 FIRE ALARM AND/OR FIRE SPRINKLER.
  
  
  
 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE
 NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN
 CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST
 FUMES.
  
  
  
 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP
 OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR
 PIPING.
  
 PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By lcrespo Date 2019-10-02 Time 07:05 Rev Time 0.00
Received By lcrespo Date 2019-10-02 Time 07:05 Sent To  
Notes
2019-10-02 07:05:4210/01/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-09-19 Cont ID  
Sent By lcrespo Date 2019-09-19 Time 13:50 Rev Time 0.00
Received By lcrespo Date 2019-09-19 Time 13:50 Sent To  
Notes
2019-09-19 13:51:2309/19/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By lcrespo Date 2019-08-14 Time 07:03 Rev Time 0.00
Received By lcrespo Date 2019-08-14 Time 07:03 Sent To  
Notes
2019-08-14 14:39:0408/14/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY RECORDS SHOW AN EXISTING SYSTEM BUT THERE ARE
 NO PERMIT OR INSPECTIONS ON FILE FOR THIS SYSTEM. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. 2017 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2) REGULATOR REQUIRED AT GENERATOR AND MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG
 SEC. 410.1 OR 2017 FBC RES. SEC. G2421.1.
  
 3) SHOW THE BTU LOAD FOR ALL APPLIANCES ON ISOMETRIC.
 LABEL SHUTOFF VALUE ON EXISTING KITCHEN PER THE 2017
 FBC FG SEC. 402.2.
  
 4) THE ADDRESS OF THE PROJECT MUST BE ON PLAN ON SP1
 AND ISOMETRIC PER WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5) SHOW UNION ON THE ISOMETRIC DRAWING PER 2017 FBC FG
 410.2.
  
 6) A SEPARATE PERMIT IS REACQUIRED FOR GAS PER WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 7) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-02 Cont ID  
Sent By jleahy Date 2019-10-02 Time 09:01 Rev Time 0.00
Received By jleahy Date 2019-09-24 Time 13:18 Sent To  
Notes
2019-09-25 13:18:30RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-19 Cont ID  
Sent By lcrespo Date 2019-09-19 Time 13:51 Rev Time 0.00
Received By lcrespo Date 2019-09-06 Time 10:16 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-08 Time 14:19 Sent To  
Notes
2019-08-09 14:19:38ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-09-26 Cont ID  
Sent By rfalcone Date 2019-09-26 Time 14:14 Rev Time 0.00
Received By rfalcone Date 2019-09-26 Time 14:14 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-09-18 Cont ID  
Sent By rfalcone Date 2019-09-18 Time 11:48 Rev Time 0.00
Received By rfalcone Date 2019-09-18 Time 11:48 Sent To G
Notes
2019-09-18 11:50:159/18/19 FAILED.
  
 PREVIOUS ZONING COMMENTS WERE NOT ADDRESSED. PLEASE
 ADDRESS THE PREVIOUS COMMENTS FROM 8/13/19.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  
 -------------------------------------------------------
 -------------
  
 8/13/19- FAILED.
  
 THE SITE PLAN DOES NOT SHOW THE EXISTING TREE LOCATED
 IN THE LOCATION OF THE PROPOSED GENERATOR. A TREE
 ALTERATION PERMIT IS REQUIRED TO REMOVE OR RELOCATED
 ANY TREES.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By ajones Date 2019-08-13 Time 13:35 Rev Time 0.00
Received By ajones Date 2019-08-13 Time 13:35 Sent To  
Notes
2019-08-13 13:37:418/13/19- FAILED.
  
 THE SITE PLAN DOES NOT SHOW THE EXISTING TREE LOCATED
 IN THE LOCATION OF THE PROPOSED GENERATOR. A TREE
 ALTERATION PERMIT IS REQUIRED TO REMOVE OR RELOCATED
 ANY TREES.
  
 ANGELLA VANN
 561-822-1441
 [email protected]