| Plan Review Stops For Permit 19080417 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-10-02 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-10-02 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2019-10-02 09:01:54 | PASSED ON ELECTRICAL BASED ON COMMENTS FROM RMD JLEAHY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-09-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-09-14 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-09-14 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2019-09-14 16:58:45 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | FBC B 1609.1.1(8) THERE ARE NO ATTACHMENT DETAILS (FOR | | | WINDLOADS) OF GENERATOR TO PAD CONNECTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-08-20 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-08-20 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2019-08-20 08:31:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD DETAILS. SPECIFY | | | THE GENERATOR TO PAD ATTACHMENT DETAILS. FBC 1609.1.1 | | | (8) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-10-01 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-10-01 |
Time |
16:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-09-17 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-09-17 |
Time |
06:45 |
Sent To |
Z |
|
| Notes |
| 2019-09-17 07:11:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. COPIES OF SIGNATURES ARE NOT SUFFICIENT. PLEASE WET | | | SIGN PLAN. . FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | | | 2. PROVIDE SHORT-CIRCUIT CALCULATION FOR ATS. . NEC | | | 110.9, 110.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-09-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-09-06 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-09-06 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2019-09-06 12:42:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC | | | 107.1, 107.2.1, 107.3.5.1.2 | | | 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE TO | | | CONFIRM CAPACITY OF GENERATOR IS ADEQUATE. NEC 702.4 | | | 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS, | | | TRANSFER SWITCH, AND PANELS. NEC 110.3, 110.9 | | | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-09-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-09-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-09-27 |
Time |
11:39 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-09-09 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-09-19 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-09-09 |
Time |
13:38 |
Sent To |
B |
|
| Notes |
| 2019-09-09 13:49:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING | | | GENERATOR REPLACEMENT OR NEW. | | | | | | PLEASE CLARIFY. | | | | | | COMPLIED WITH WRITTEN "NEW" ON PLAN. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | | CODES. | | | | | | THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF | | | APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM, | | | FIRE ALARM AND/OR FIRE SPRINKLER. | | | | | | NOT COMPLIED | | | | | | PLEASE PROVIDE A NOTE OF COMPLIANCE WITH THE NOTED | | | CODES. | | | | | | | | | | | | 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE | | | NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN | | | CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST | | | FUMES. | | | | | | NOT COMPLIED | | | | | | THE ACCUMULATION OF EXHAUST FUMES CAN BE TRAPPED UNDER | | | CANOPYS AND SEEP THRU OVERHANGS, WINDOWS AND DOORS. | | | | | | PER NFPA 37 | | | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | | STRUCTURE | | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | | COMBUSTION | | | WILL DISCHARGE TO A SAFE LOCATION. | | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | | DIRECTED TOWARD | | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | | COMBUSTIBLE | | | DUSTS. | | | | | | PLEASE PROVIDE A ALL APPLICABLE DIMENSIONS. | | | | | | | | | | | | 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP | | | OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR | | | PIPING. | | | | | | NOT COMPLIED | | | | | | IT APPEARS TO BE NG..... | | | | | | PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-08-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-08-20 |
Time |
14:00 |
Sent To |
E |
|
| Notes |
| 2019-08-20 14:07:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE APPEARS TO BE CONFUSION IF THIS IS AN EXISTING | | | GENERATOR REPLACEMENT OR NEW. | | | | | | PLEASE CLARIFY. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | | CODES. | | | | | | THE INSTALLATION SHALL COMPLY WITH NFPA 37, 54 AND IF | | | APPLICABLE 110 IF PROVIDEING FOR A LIFE SAFETY SYSTEM, | | | FIRE ALARM AND/OR FIRE SPRINKLER. | | | | | | | | | | | | 3) PLEASE PROVIDE DIMENSIONS AND LOCATIONS TO THE | | | NEAREST BUILDING AND OF ALL DOORS, WINDOWS, AND OPEN | | | CANOPIES THAT CAN ALLOW FOR ACCUMULATION OF EXHAUST | | | FUMES. | | | | | | | | | | | | 4) THERE IS NO CLEAR INDICATION OF EITHER POWERED BY LP | | | OR NG AND THE LOCATIONS OF ANY PROPOSED TANKS OR | | | PIPING. | | | | | | PLEASE CLARIFY AND PROVIDE APPLICABLE DETAILS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-10-02 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-10-02 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2019-10-02 07:05:42 | 10/01/19 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-09-19 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-09-19 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2019-09-19 13:51:23 | 09/19/19 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-14 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-14 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2019-08-14 14:39:04 | 08/14/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) CITY RECORDS SHOW AN EXISTING SYSTEM BUT THERE ARE | | | NO PERMIT OR INSPECTIONS ON FILE FOR THIS SYSTEM. THE | | | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO | | | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. 2017 FBC RES. SECS. | | | G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | | | 2) REGULATOR REQUIRED AT GENERATOR AND MANUFACTURER?S | | | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG | | | SEC. 410.1 OR 2017 FBC RES. SEC. G2421.1. | | | | | | 3) SHOW THE BTU LOAD FOR ALL APPLIANCES ON ISOMETRIC. | | | LABEL SHUTOFF VALUE ON EXISTING KITCHEN PER THE 2017 | | | FBC FG SEC. 402.2. | | | | | | 4) THE ADDRESS OF THE PROJECT MUST BE ON PLAN ON SP1 | | | AND ISOMETRIC PER WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5) SHOW UNION ON THE ISOMETRIC DRAWING PER 2017 FBC FG | | | 410.2. | | | | | | 6) A SEPARATE PERMIT IS REACQUIRED FOR GAS PER WPB | | | AMENDMENTS TO THE FBC SEC. 105.1. | | | | | | 7) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE | | | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS | | | SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES. | | | SEC. G2413.3 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-10-02 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-09-24 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2019-09-25 13:18:30 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-09-19 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-09-19 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-09-06 |
Time |
10:16 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-09-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-08 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2019-08-09 14:19:38 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-09-26 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-09-26 |
Time |
14:14 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-09-18 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-09-18 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-09-18 |
Time |
11:48 |
Sent To |
G |
|
| Notes |
| 2019-09-18 11:50:15 | 9/18/19 FAILED. | | | | | | PREVIOUS ZONING COMMENTS WERE NOT ADDRESSED. PLEASE | | | ADDRESS THE PREVIOUS COMMENTS FROM 8/13/19. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: (561) 822-1442 | | | E-MAIL: [email protected] | | | | | | ------------------------------------------------------- | | | ------------- | | | | | | 8/13/19- FAILED. | | | | | | THE SITE PLAN DOES NOT SHOW THE EXISTING TREE LOCATED | | | IN THE LOCATION OF THE PROPOSED GENERATOR. A TREE | | | ALTERATION PERMIT IS REQUIRED TO REMOVE OR RELOCATED | | | ANY TREES. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-08-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2019-08-13 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2019-08-13 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2019-08-13 13:37:41 | 8/13/19- FAILED. | | | | | | THE SITE PLAN DOES NOT SHOW THE EXISTING TREE LOCATED | | | IN THE LOCATION OF THE PROPOSED GENERATOR. A TREE | | | ALTERATION PERMIT IS REQUIRED TO REMOVE OR RELOCATED | | | ANY TREES. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|