| 2019-08-26 13:29:33 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19080396 |
| | ADD: 2425 PRESIDENTIAL WAY SUITE: 403 |
| | CONT: O & D TOTAL HOME REPAIR CORP. |
| | TEL: 561-969-3121 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 26/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA: |
| | 1A) THE PLAN INDICATES THE CONSTRUCTION TYPE AS V-B. |
| | PLEASE NOTE THIS SUITE IS LOCATED IN A HIGHRISE |
| | BUILDING AND BUILDING TYPE IS TYPE I-A. SEE THE 2017 |
| | FBC-B TABLE 504.4. |
| | |
| | 1B) THE SHEET 1-1 UNDER THE HEADING OF DESIGN CRITERIA |
| | LIST THE OCCUPANCY TYPE AS A R-3. PLEASE NOTE MOST R-3 |
| | ARE SINGLE FAMILY RESIDENCES. FEW R-3 ARE A MIXED |
| | OCCUPANCY WHERE IS A BUSINESS OR MERCANTILE ON THE 1ST |
| | FLOOR AND A SINGLE DWELLING UNIT ON THE 2ND FLOOR. |
| | APARTMENT BUILDINGS AND CONDOMINIUMS THAT ARE PRIMARILY |
| | PERMANENT IN NATURE ARE CONSIDERED OCCUPANCY TYPE R2. |
| | PLEASE REVIEW THE 2017 FBC-B 310.2. |
| | |
| | 2) PLEASE NOTE THE SUBMITTED SALES BROCHURE DOES NOT |
| | HAVE THE CORRECT DATA AND TESTING RESULTS TO OBTAIN A |
| | PERMIT. WE HAVE TO DATE NOT PERMITTED THE PRODUCT SAM |
| | 90 CONTROL MEMBRANE. WE DO HAVE THE ACTUAL TEST RESULT |
| | THAT HAVE PASSED FOR SUPER SAM125. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO |
| | ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY |
| | TO COMPLY WITH THE STATE & FEDERAL ASBESTOS |
| | REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61- |
| | NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS |
| | SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: * |
| | DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 355-3070 |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |