| 2019-08-27 06:48:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SERVICE APPEARS TO BE A 400AMP SERVICE BUT IS |
| | LABELED AS 200AMP AT METER-CAN. PROVIDE CORRECTION. FBC |
| | 107.2.1 |
| | |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NO LOAD CALC PROVIDED FOR NEW PANEL. NEC 220 |
| | |
| | 3. PROVIDE PANEL SCHEDULES FOR PANEL B AND NEW 125AMP |
| | SUB-PANEL. FBC 107.2.1 |
| | |
| | 4. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. (ALL PAGES) PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |